TEC2045-2 Wireless Thermostat Controller with Single Proportional Output and One-Speed Fan Control
Installation Instructions
10
Lockout
Selectable Lockout Levels for
limiting end user keypad interaction.
Default:
0
Lockout
Level
Function
Mode
Setting
Fan
Setting
Local
Override
Occupied
Temperature
Setpoints
(0)
Access
Access
Access
Access
(1)
Access
Access
No Access
Access
(2)
No Access
No Access
Access
Access
(3)
No Access
No Access
No Access
Access
(4)
No Access
No Access
Access
No Access
(5)
No Access
No Access
No Access
No Access
SeqOpera
Determines the sequence of
operation.
Default:
1
(0):
Cooling Only (Off-Cool). The default is
Cool
.
(1):
Heating Only (Off-Heat). The default is
Heat
.
(2):
Cooling and Reheat (Off-Auto*-Heat-Cool). The default is
Heat
.
(3):
Heating and Reheat (Off-Heat). The default is
Heat
.
* Auto can be disabled with the
AutoMode
parameter.
Note:
Choose the selection option
(0): Cooling Only
when using a
changeover sensor to allow changeover to occur between
Cooling
Only
and
Heating Only
.
Unocc HT
Sets the Unoccupied Heating
setpoint value.
Default:
62.0°F/16.5°C
Range:
40.0°F/4.5°C
to
90.0°F/32.0°C
Note:
When adjusting the
temperature, press the
UP/
DOWN
arrow keys to
change the temperature in
0.5F°/0.5C° increments;
press and hold the
UP/DOWN
arrow keys
to change the temperature
in 5.0F°/5.0C° increments.
Unocc CL
Sets the Unoccupied Cooling
setpoint value.
Default:
80.0°F/26.5°C
Range:
54.0°F/12.0°C
to
100.0°F/37.5°C
Heat max
Sets the Occupied and Unoccupied
maximum Heating setpoint values.
Default:
90.0°F/32.0°C
Range:
40.0°F/4.5°C
to
90.0°F/32.0°C
Cool min
Sets the Occupied and Unoccupied
minimum Cooling setpoint values.
Default:
54.0°F/12.0°C
Range:
54.0°F/12.0°C
to
100.0°F/37.5°C
Set type
Provides the option of temporarily
changing the heating or cooling
setpoint by pressing the
UP/DOWN
arrow keys.
Default:
permnent
(temporar):
Local changes to the heating or cooling setpoints are
temporary, and remain effective for the specified TOccTime.
(permnent):
Local changes to the heating or cooling setpoints are
permanently stored in the thermostat controller memory.
TOccTime
Sets the duration of the Temporary
Occupancy Time when the heating
or cooling setpoints in the Occupied
mode are established by:
•
an Override Function enabled in
the Main User Menu (when the
thermostat controller is in the
Unoccupied mode)
•
a temporary heating or cooling
setpoint
Default:
2.0 hrs
Range:
0.0 to 24.0 hrs in 1-hour increments
DoorTime
Engages the Unoccupied mode if
the door stays open minimally for
the time specified.
Default:
2.0 min
Range:
1.0 to 10.0 min
Table 5: Installer Configuration Menu (Part 3 of 4)
Parameter
Appearing
on Display
Description and Default
Selection Options