21
21
21
To T8600-TB21-9JS0-M0: While entrance card is pulled out, the temperature
T8600-TB21-9JS0-M0
21
3
Lock function:
Lock function:
If Lock function is enabled, the thermostat will be locked
automatically after 30 seconds unused.
Unlock function:
Hold down the fan key 5 seconds to unlock.
Unoccupied mode (T8600-TB -9JS0-M0 ):
Occupied/Unoccupied mode "
" is active if monitor is equipped, which is operated
by entrance card.
automatically set to 26
℃
, fan is on LO-speed if the thermostat is in cool mode; the
temperature set to 18
℃
, fan is on LO-speed if in heat mode. Temperature Setting is
invalid until the entrance card is inserted again.
Remote Temperature sensor (T8600-TB -9JR0-M0 ):
When remote sensor is connected, the built-in sensor will be disable.
Timer Function:
On power on status, hold the " " button for 5s to enter the Timer interface, where
the thermostat's accumulated running time is showing.
On power off status, hold the " " button for 10s to enter the Timer interface,
accumulated running time can be cleared by pressing " ".
按键锁功能
:
锁按键功能:
如果温控器开启了锁按键功能,在没有人使用的情况下
30
秒后
会自动把按键锁上,禁止其他人员对温控器进行操作。
按键解锁:
按风速按键
5
秒即可解锁(在没有人使用的情况下
30
秒后会自动把
按键锁上)。
门卡功能
(T8600-TB -9JS0-M0 )
如安装了有人
/
无人监控装置,有人
/
无人模式“
”将会启动。可通过门卡
进入有人
/
无人模式。
在
型号中,当门卡拔出后,进入无人模式,此时液晶显
示“
”,如果温控器处于制冷模式时,温度自动设置为
26
℃,风机低速运
行。如果温控器处于制热模式时,温度自动设置为
18
℃,风机低速运行。此
时上下键调节温度功能失效。插入门卡后,恢复正常。
外接温度传感器
(T8600-TB -9JR0-M0 ):
当温控器接上外置传感器时,内置
NTC
自动失效。
计时功能
:
在开机状态下,长按“
”键
5S
,此时进入计时界面,此时显示的时间为温
控器累计运行的时间。
在关机状态下,长按“ ”键
10S
,进入计时界面,此时按“
”键可以将累
计时间清零。
系列触摸屏风机盘管温控器安装说明
Series Touch Screen Fan Coil Thermostat - Installation Instructions
T8600-TB21 -9JR0/S0-M0
T8600-TB21 -9JR0/S0-M0
低温保护功能:
温控器处于关机状态,当室内温度低于
5
℃时,温控器自动开启制热并显示
“
”符号,开启电动阀;当室内温度升高到
7
℃时,温控器自动关闭输
出。
待机功能:
当没有按键操作情况下,
30S
后进入待机界面,背光变为微亮,此时按下任意
按键,退出待机界面同时背光变亮。
地址查看:
在开机状态下,按下“
M
”键
5S,
此时在时钟区域显示温控器当前地址,
30S
后
或按下“ ”键退出。
Function /
功能
Function /
功能
Cool Mode /
制冷模式
Heat Mode /
加热模式
Fan only Mode /
仅风机
Low Temperature protection Function:
On power Off status and when room temperature is lower than 5
℃
, heat function
will be automatically switched on, "
" appears, the electrically operated valve is
opened. When the room temperature reaches 7
℃
, the setting will be automatically
canceled.
Standby Function:
The thermostat will change to standby interface after 30 seconds no pressed, and
backlight becomes slightly bright. Quit the standby interface by pressing any key
and backlight becomes normal again.
Address checking:
When thermostat is on, press "M" button for 5s, current address will be shown in
the clock area. Address checking will exit in 30s or by pressing " " button.
参数设定:
Parameter Setting:
关机状态下,同时按住“
”键和“∧”键
5
秒,即可进入参数设置界面,此界面下,按“
M
”键循环选择需要设定的参数,按“∧”或“∨”键调节参数。参数明细表如下:(调
整时一定慢些进行,尤其在按“
M
”键时,不能在一秒钟内按一次以上)
On power off status, hold the " "and "
∧
"keys for 5 seconds to enter parameter setting interface. Press "M" key to select the parameter, and then adjust it by "
∧
"or "
∨
" key. Setting
table is as following: (note to operate slowly, especially keep over 1 second interval between each "M" key pressing)
602Q-B01A-NB-Issue Date 1 2015
This document is subject to change without notice
本文档如有变化,恕不另行通知
602Q-B01A-NB-Issue Date 7 2017