INSTALLATION INSTRUCTIONS FOR THE TECHNICIAN/FITTER

READ THIS INSTRUCTION SHEET AND THE SAFETY WARNING CAREFULLY BEFORE INSTALLING AND 

SAVE IT FOR FUTURE USE

REPAIR AND REPLACEMENT

Do not attempt to repair the T7000 thermostat. In case of improperly functioning control, contact the nearest Johnson Controls® 

representative, and specify the desired product code number. When con-tacting the supplier for a replacement please state the 

type/model number of the control located on the data plate or cover label.

IMPORTANT:

•  Use this T7000 thermostat only as an operating control. Where failure of malfunction of the T7000 thermostat could lead to 

personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the 

system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn 

of, or protect against, failure or malfunction of the T7000 thermostat.

• Do not install this thermostat in condensing, wet, or damp environment. Moisture may cause damage to the thermostat.

•  Do not remove PCB from the enclosure cover. Removing the PCB from the enclosure cover voids the product warranty.

•   Make all wiring connection in accordance with local, nation, and regional regulations. Do not exceed the T7000 thermostat 

electrical ratings.

•  Remove LCD plastic cover before use

WARNING:

Disconnect power supply before making electrical connections. Contact with components carrying hazardous voltages can cause 

electrical shock and may result in severe personal injury or death.

•  Risk of Electrical Shock: Ground the thermostat according to local, national, and regional regulations. Failure to ground the 

thermostat may result in electrical shock and severe personal injury and death.

•  Risk of Electrical Shock and Property Damage: Insulate and secure each unused wire lead before applying power to the 

thermostat. Failure to insulate and secure each unused wire lead may result property damage, electrical shock, and severe 

personal injury or death.

Setup and adjustment:

Press   and   button for 5 seconds at power off mode (only press   button for T7603-T000-...JF0), to get in parameter list, press 
M button (press   button for T7603-T000-...JF0 ) to switch over setting items and use   and   button to change parameter 

value.

Item

T7600-

TF21-

...JS0

T7601-

TF20-

...JS0

T7600-

TF20-

...JS0

T7603-

T000-

...JF0

T7600-

TB21-

...JA0

Parameter

Function

Default

01

Application

T7601-TF20-...JS0 with EC Motor control

00: 2-pipe relay valve; 

01: 4-pipe relay valve; 

02: 2-pipe 3-wire relay valve; 

03: 2-pipe relay valve with TiO2/ESP; 

04: 2-pipe relay valve with floor heating; 

05: water source heat pump; 

06: 2-pipe AO valve

T7600-TF21-...JS0 Proportional Control

00: 2-pipe AO valve; 

01: 4-pipe AO valve

T7600-TF20-...JS0 ON/OFF control

00: 2-pipe relay valve; 

01: 4-pipe relay valve; 

02: 2-pipe 3-wire relay valve; 

03: 2-pipe relay valve with TiO2/ESP; 

04: 2-pipe relay valve with floor heating; 

05: water source heat pump

00

02

Upper set point limit

Setting range 2~40

 (36~99

o

F)

35

03

Lower set point limit

Setting range 0~38

 (32~95

o

F)

5

04

Cooling set point unoccupied

Setting range 22~32

 (72~90

o

F)

26

05

Heating set point unoccupied

Setting range 10~21

 (50~70

o

F)

18

06

Frost protection

00: on; 01: off

00

07

Frost protection set point

Setting range 0~20

5

08

Fan mode when set point 

reach

00: off 01: low

00

09

Fan mode when unoccupied

00: low speed; 01: set speed

00

10

ECM Min voltage

Min voltage below which the fan output is 0%, range 0-10V. (0.5V)

3V

Содержание T7000 Series

Страница 1: ...the most up to date version of this document Figure 1 Figure 4 1 Figure 2 Figure 3 o F AUTO 50 cm 19 68 inch 150 cm 59 05 inch C Ambient Ambiante Umgebung Ambiente Ambiente Atmosfeer Omgivnin Prost e...

Страница 2: ...pipe AO valve Valve N A N A Notes F ON is line voltage relay output used for enable disable ECM fan in some case FAN AO1 F ON VAL2 VAL1 GND B A GND NTC OCC COM L N T7600 TF21 JS0 Application AO2 AO1 2...

Страница 3: ...cording to local national and regional regulations Failure to ground the thermostat may result in electrical shock and severe personal injury and death Risk of Electrical Shock and Property Damage Ins...

Страница 4: ...guage 00 Chinese 01 English 00 22 Mode selection 00 cooling heating ventilation 01 cooling only 02 heating 00 23 Back light The back light will be OFF in 05 60 Sec 30 25 Remote sensor type 00 China ma...

Страница 5: ...21 JA0 01 T7601 TF20 JS0 00 2 01 4 02 2 3 03 2 TiO2 ESP 04 2 05 06 2 T7600 TF21 JS0 00 2 01 4 T7600 TF20 JS0 00 2 01 4 02 2 3 03 2 TiO2 ESP 04 2 05 00 02 2 40 36 99o F 35 03 0 38 32 95o F 5 04 22 32 7...

Страница 6: ...03 04 00 15 00 01 00 16 00 01 2 FCU 10K NTC 00 17 BI 00 01 02 03 04 05 06 00 18 00 01 o F 00 19 5 5 9 9o F 0 20 00 01 MED LOW 02 LOW 03 00 21 00 01 00 22 00 01 02 00 23 05 60s xx 30 25 00 10KNTC 01 J...

Страница 7: ...Point of Contact JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 22 BLOCK D NEW DISTRICT WUXI JIANGSU PROVINCE 214142 CHINA Building Technologies Solutions Headquarters Milwaukee Wisconsin USA Br...

Отзывы: