T600HCx-3 Single-Stage Thermostats Installation Instructions

1

 Refer to the 

QuickLIT website

 for the most up-to-date version of this document.

Applications

The T600HCN-3 non-programmable and T600HCP-3 
programmable thermostats are specifically designed 
for control of single-stage commercial heating and 
cooling equipment.

North American Emissions Compliance

United States

Canada

Installation

Location Considerations

Locate the T600HCx-3 thermostat:

on a partitioning wall, approximately 5 ft (1.5 m) 
above the floor in a location of average 
temperature

away from direct sunlight, radiant heat, outside 
walls, behind doors, air discharge grills, stairwells, 
or outside doors

away from steam or water pipes, warm air stacks, 
unconditioned areas (not heated or cooled), or 
sources of electrical interference

Note:

Allow for vertical air circulation to the 

T600HCx-3 thermostat.

IMPORTANT:

The T600HCx-3 Thermostat is 

intended to provide an input to equipment under 
normal operating conditions. Where failure or 
malfunction of the thermostat could lead to personal 
injury or property damage to the controlled 
equipment or other property, additional precautions 
must be designed into the control system. 
Incorporate and maintain other devices, such as 
supervisory or alarm systems or safety or limit 
controls, intended to warn of or protect against 
failure or malfunction of the thermostat.

IMPORTANT:

Le T600HCx-3 Thermostat est 

destiné à transmettre des données entrantes à un 
équipement dans des conditions normales de 
fonctionnement. Lorsqu'une défaillance ou un 
dysfonctionnement du thermostat risque de 
provoquer des blessures ou d'endommager 
l'équipement contrôlé ou un autre équipement, la 
conception du système de contrôle doit intégrer des 
dispositifs de protection supplémentaires. Veiller 
dans ce cas à intégrer de façon permanente 
d'autres dispositifs, tels que des systèmes de 
supervision ou d'alarme, ou des dispositifs de 
sécurité ou de limitation, ayant une fonction 
d'avertissement ou de protection en cas de 
défaillance ou de dysfonctionnement du thermostat. 

This equipment has been tested and found to 
comply with the limits for a Class A digital device 
pursuant to Part 15 of the FCC Rules. These limits 
are designed to provide reasonable protection 
against harmful interference when this equipment is 
operated in a commercial environment. This 
equipment generates, uses, and can radiate radio 
frequency energy and, if not installed and used in 
accordance with the instruction manual, may cause 
harmful interference to radio communications. 
Operation of this equipment in a residential area is 
likely to cause harmful interference, in which case 
the user will be required to correct the interference 
at his/her own expense.

This Class (A) digital apparatus meets all the 
requirements of the Canadian Interference-Causing 
Equipment Regulations.

Cet appareil numérique de la Classe (A) respecte 
toutes les exigences du Règlement sur le matériel 
brouilleur du Canada.

T600HCx-3 Single-Stage Thermostats

Installation Instructions

T600HCN-3, T600HCP-3

Part No. 24-9890-560, Rev. A

Issued June 30, 2014

Содержание T600HCN-3

Страница 1: ...nn es entrantes un quipement dans des conditions normales de fonctionnement Lorsqu une d faillance ou un dysfonctionnement du thermostat risque de provoquer des blessures ou d endommager l quipement c...

Страница 2: ...at mounting base so that the arrow on the base points upward to indicate the top of the thermostat 6 Drill a 3 16 in 5 mm hole at each of the two marked locations and tap nylon anchors included with t...

Страница 3: ...ion avant de r aliser tout raccordement lectrique afin d viter tout risque de d charge lectrique CAUTION Risk of Property Damage Do not apply power to the system before checking all wiring connections...

Страница 4: ...conds Light Emitting Diodes LEDs Three LEDs are included to indicate the fan status call for heat or call for cooling The FAN LED is on when the fan is on The HEAT LED is on when heating is on The COO...

Страница 5: ...he scrolling Status Display Menu and when the message is displayed the backlight momentarily lights up Each input can be configured to the Selection Options included in Table 2 Table 2 Installer Confi...

Страница 6: ...0 sec Frost pr Provides a minimum heating setpoint of 42 0 F 5 5 C to prevent freezing in the zone controlled by the thermostat Default off on Enabled off Disabled Heat max4 Sets the Occupied and Unoc...

Страница 7: ...Main User Menu or DI1 or DI2 configured as a temporary override remote contact RemOVR Sets the effective duration of the Temporary heating or cooling setpoints set using the up down arrow keys defaul...

Страница 8: ...ve recovery is disabled if either DI1 or DI2 is configured as remote NSB Default off on Enabled provides the desired occupied temperature at the start of the occupied schedule off Disabled provides th...

Страница 9: ...DI2 is configured to operate as a remote override contact this menu is disabled To override the unoccupied state while in the Main User Menu 1 Press the NO key to all prompts until the Override Sched...

Страница 10: ...temperature setting menu Press the YES key to change the occupied cooling setpoint Press the NO key to advance to the occupied heating setpoint menu Press the UP DOWN arrow keys to set the temperature...

Страница 11: ...ress the YES key to select the desired system mode 2 Press the UP DOWN arrow keys to locate the desired system mode Press the YES key to select the desired system mode 3 Press the YES key to return to...

Страница 12: ...menu Press the YES key to set the schedule for Monday or press the NO key to advance to Tuesday Press the YES key to set the occupied start time for Monday or press the NO key to advance to Tuesday S...

Страница 13: ...he UP DOWN arrow keys to set the second unoccupied start time Press the YES key to enter the time Press the YES key to set the schedule for Tuesday or press the NO key to advance to Wednesday Press th...

Страница 14: ...no alarm or backlight should be present If the day or time is incorrect repeat the Setting the Day and Time procedure Setting Schedule Hold The schedule hold menu is used to set a permanent hold on t...

Страница 15: ...hermostat fails to operate within its specifications replace the unit For a replacement thermostat contact the nearest Johnson Controls representative Table 8 Accessories Order Separately Code Number...

Страница 16: ...5 Increments Heating Control 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Control 54 0 F 12 0 C to 100 0 F 38 0 C Accuracy Temperature 0 9F 0 5C at 70 0 F 21 0 C Typical Calibrated Minimum Deadband 2F 1C bet...

Отзывы: