Installation Instructions   

 

Issue Date  December 9, 2003 

 

©  2003 Johnson Controls, Inc.

 

1

 

 

T600HCN-1 Non-Programmable Thermostat 

 

Applications 

The T600HCN-1 is a single-stage non-programmable 
thermostat that provides exceptional accuracy through 
the use of a unique Proportional-Integral (PI) time 
proportioning algorithm. The thermostat’s proprietary 
adaptive logic algorithm provides a constant space 
temperature by controlling the Heating, Ventilating, 
and Air Conditioning (HVAC) equipment to minimize 
overshoot and maximize comfort. The algorithm 
virtually eliminates temperature offset associated with 
traditional, differential-based on/off thermostats. 
Additionally, the menu-driven backlit display, plain text 
menus, and five keys on the T600HCN-1 make 
operating the thermostat easy and intuitive. 

Installation 

Location Considerations 

Locate the T600HCN-1 thermostat as follows: 

• 

on a partitioning interior wall, and approximately 
5 ft (1.5 m) above the floor in a location of average 
temperature 

• 

away from direct sunlight, radiant heat, outside 
walls, behind doors, air discharge grills, stairwells, 
or outside doors 

• 

away from steam or water pipes, warm air stacks, 
unheated/uncooled areas, or sources of electrical 
interference 

To install the thermostat: 

1.  Remove the security screw on the bottom of the 

thermostat cover using a Phillips-head 
screwdriver. Open the thermostat by pulling on the 
bottom side of the thermostat cover (see Figure 1). 

2.  Unlock the Printed Circuit Board (PCB) by 

carefully pressing the locking tabs to the right 
(see Figure 2). Open the thermostat’s PCB to the 
left. 

3.  Pull out approximately 6 in. (152 mm) of wires 

from the wall and insert the cable through the hole 
in the base. 

4.  Align the base on the wall, and using the base as 

a template, mark the location of the two mounting 
holes on the wall. Confirm the thermostat base is 
installed with the proper side up. 

5.  Use the supplied anchors and screws for mounting 

on drywall or plaster. Drill two 3/16 in. (4.7 mm) 
holes at the marked locations and tap nylon 
anchors flush to wall surface (see Figure 3). 

6.  Position base on the wall, insert screws through 

mounting base, and fasten into wall anchors. Do 
not overtighten screws. 

7.  Swing the thermostat PCB back to the right to 

close. Gently press on the PCB to secure each of 
the locking tabs. 

8.  Pull out the screw terminal blocks using the pull 

tabs on each connector (see Figure 4). 

Note: 

The number of terminals on the terminal 

blocks varies depending on the T600 model. 

IMPORTANT: 

Use this T600HCN-1 

non-programmable thermostat only as an operating 
control. Where failure or malfunction of the 
T600HCN-1 could lead to personal injury or property 
damage to the controlled equipment or other 
property, additional precautions must be designed 
into the system. Incorporate and maintain other 
devices such as supervisory or alarm systems or 
safety or limit controls intended to warn of, or protect 
against, failure or malfunction of the T600HCN-1. 

  Part No. 24-9889-10, Rev. A 

www.johnsoncontrols.com 

Содержание T600HCN-1

Страница 1: ...the thermostat cover see Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tabs to the right see Figure 2 Open the thermostat s PCB to the left 3 Pull out approximatel...

Страница 2: ...e the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram see Figure 5 2 Gently push excess wire back into wall plug the wall hole with...

Страница 3: ...24 VAC from equipment transformer 24 VAC common from equipment transformer 24 VAC for heating stage Configurable digital input Configurable digital input Remote room sensor Sensor common Outdoor air s...

Страница 4: ...uring normal thermostat operation The menu continually scrolls through the following parameters see Figure 6 Room Temperature System Mode Schedule Status Occupied Unoccupied see Note Outdoor Temperatu...

Страница 5: ...Maximum Cooling Cycles per Hour Cool cph Sets the Minimum Heating Cooling Deadband Default 2 0 F 1 1 C See Setting the Heating Cooling Deadband Deadband Determines how the Fan Activates in Response to...

Страница 6: ...nfigure Digital Input 2 or NO to advance to the keypad lockout setup prompt 4 Use the UP DOWN arrow keys to locate the desired function for the Digital Input 2 Press YES to select the desired function...

Страница 7: ...ows the minimum cooling setpoint prompt See the Setting the Minimum Cooling Setpoint Cool min section for instructions Setting the Minimum Cooling Setpoint Cool min The minimum cooling setpoint establ...

Страница 8: ...hes the minimum difference between the heating and cooling setpoints The range is adjustable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in th...

Страница 9: ...the display Press YES to enter the outdoor sensor calibration menu 2 Use the UP DOWN arrow keys to adjust the correction that should be applied to the sensor reading Press YES to store the offset The...

Страница 10: ...de schedule prompt only appears when the thermostat is in the unoccupied state This menu selection gives the user the option of overriding the unoccupied setpoints with the occupied setpoints for the...

Страница 11: ...et prompt appears in the display it may be the first prompt Press YES to enter temperature setting menu Press YES to change occupied cooling setpoint Press NO to advance to occupied heating setpoint m...

Страница 12: ...rn to the Status Display Menu or NO to return to the fan mode selection menu Setting Permanent Hold Note Displayed only if Digital Input DI1 or DI2 is configured for remote NSB This menu is used to se...

Страница 13: ...d to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interferenc...