1.2.5
Session
When selecting the menu
Session
, the following picture appears:
Fig. 5: Session menu
Password
When you want to change a parameter you must enter a four digit password.
In UniSAB III there are 4 password levels:
•
Monitoring
(no password) - monitoring access only
•
User
- access to change set points linked to normal operation
•
Superuser
- access to change configuration and critical set points
•
Supervisor
- Johnson Controls Denmark supervisor level
Switch between the password levels with
and
. Choose the appropriate level with
and enter the
four digit password using the arrow keys. When you have entered the four digits, press
and then
/OK.
If the password is accepted you will return to the picture where you wanted to change a parameter and
may change the parameter value with the
and
keys.
In subsection
, you will find a detailed example of how to change a parameter,
e.g. a limit value.
You can always log into UniSAB III even if you are not prompted for a password. Simply choose
Current
user
in the
Password
picture in the
Session
menu.
In the
Password
menu you can inactivate an open password like this: Choose
Current user
in the
Pass-
word
picture. The password “Lock” in the
info bar
will close and the password access will be
terminated.