Maestro Software
58
Unit #3 HVAC
Setup
Status
Setpoints
Night setpoints
Zone #1
Prev
Next
Undo
2
Differential:
2
Delay[Min]:
5
Deadband:
2
Delay[Min]:
Cool if outside temp. <
65
Reclaim during dehum
Deh. if inside temp. <
Cooling Setpoints
72
Setpoint:
Dehum. Setpoints
65
Setpoint:
Lockouts
75
Aux. if outside temp. >
2
Differential:
2
Delay[Min]:
Reclaim Setpoints
68
Setpoint:
2
Differential:
2
Delay[Min]:
Auxiliary Setpoints
66
Setpoint:
10
Delay [Min]
High:
10
78
Setpt.
64
Low:
Alarm Setpoints
45
Cooling Setpoints:
defines the target temperature
at which the cooling output
ends the cooling cycle.
is the total
differential between stages -
the interstage differential
between is this total differential
divided by the number of
stages. See example below.
is the minimum time (in
minutes) between successive
stages.
Setpoint
Differential
Delay
Reclaim Setpoints:
This section
defines when and how heating will
be controlled.
defines the
temperature at which heating (heat
reclaim) will begin.
Setpoint
Differential
Delay
is the
total differential between heating
stages - the differential between
successive stages of heat is the total
differential divided by the number of
stages.
is the minimum time
(in minutes) between successive
heating stages.
Dehum. Setpoints:
defines the target humidity at
which the
ends
dehumidification.
defines the
differential (in % RH) between
setpoint and the point at which
the output starts
dehumidification.
is the
amount of time
.
Setpoint
Deadband
Delay
output
that the output
delays before starting
dehumidification after the
dehumidification start RH
(setpoint plus deadband) has
been reached
Auxiliary Setpoints:
Setpoint
Differential
Delay
defines the temperature at which
auxiliary heat may be used.
is the temperature
between the first stage of auxiliary
heat and the second stage of
auxiliary heat.
is the
minimum time (in minutes) between
successive auxiliary heat stages.
Lockouts:
This area defines
the outside air temperature at
which the auxiliary heat,
cooling, and dehumidification
are locked out (the outputs are
not allowed to energize). If the
box has
a check mark, the heat reclaim
will operate while
dehumidification is on.
reclaim during dehum
Alarm Setpoints:
This
defines the high and low
temperatures and time
delays at which the
temperature alarms for this
zone are activated.
Figure 54: HVAC Setpoint Parameters
Содержание PENN ACT2
Страница 16: ...Maestro Software 16 ...
Страница 30: ...Maestro Software 30 ...
Страница 38: ...Maestro Software 38 3 Click the unit you wish to view Figure 32 Select Unit Dialog 4 Click the OK button ...
Страница 90: ...Maestro Software 90 ...
Страница 102: ...Maestro Software 102 ...
Страница 104: ...Maestro Software 104 ...