background image

      

INSTALLATION GUIDE

 

Installing and Operating the NXT-INT-01 Intelligent Thermostat

 

Introduction

 

The  Intelligent Thermostat has a space 
temperature sensor, five user push buttons, 
and a 2 line x 8 character dot matrix LCD 
to show room temperature, time, outside air 
temperature, setpoint, and other optional 
parameters (depending upon the operation). 

NXT-INT-01 Intelligent Thermostat

 

OVERRIDE

*

ROOM/

OUTSIDE

72 ° F

RoomTemp

Figure 2 - Wiring connection for the Intelligent Thermostat

 

   www.johnsoncontrols.com 

LIT-TD-2006  11/2002

 

Literature Part # 24-9869-5  Rev. A

 

Figure 1 - NXT-INT-01 Intelligent Thermostat

 

Installation

 

The thermostat connects to the controllers 
via a 2-wire (#22 AWG, single twisted pair) 
cable.  The NexSys thermostat communica-
tions bus carries power and communica-
tions for the Intelligent thermostat. 

Wiring

 

WARNING - TO PREVENT ELECTRI-

CAL SHOCK OR DAMAGE TO THE

 

EQUIPMENT, YOU MUST DISCON-

NECT THE POWER SUPPLY TO THE

 

ELECTRONIC CONTROLLER

 

BEFORE YOU MAKE THE WIRING

 

CONNECTIONS.

 

All wiring is low voltage and should be in 
accordance with local regulations and the 
National Electrical Code. 
Use shielded cable only when it is required. 
Most applications do not require shielding 
and will benefit from unshielded cable. 
When using the optional shielded cable, 
ground only one end of the shield.   Low 
voltage control wiring should not be run in 
the same conduit as line voltage wiring or 
other conductors that supply highly- 
inductive loads (such as contactors, coils, 
motors, generators, etc.). 

CAUTION - MAKE ALL CONNEC-

TIONS AND CHECK ALL CONNEC-

TIONS BEFORE APPLYING

 

POWER.  IMPROPER WIRING MAY

 

CAUSE PERMANENT DAMAGE TO

 

THIS EQUIPMENT.

 

Wiring Recommendations

 

Unshielded

 

Stranded, 22AWG:  Belden #8442(2- 
wire), Belden #8444(4-wire) 
Plenum-rated, Stranded, 22AWG:  Belden 
#82442(2-wire), 82444(4-wire) 
Stranded, 18AWG:  Belden #8461(2- 
wire), Belden #8489(4-wire) 
Plenum-rated, Stranded, 18AWG:  Belden 
#87740(2-wire), 82489(4-wire) 

Shielded

 

Stranded:  Belden #8761 
Solid:  Belden #8450 
Plenum-rated, Stranded:  Belden 
#88761other equipment. 

To Wire the Intelligent Thermotat:

 

1

.  Connect the Red wire of  the stat’s pigtail 

to the STAT + terminal of  the controller. 

2

.  Connect the Black wire of  the stat’s 

pigtail to the controller’s STAT - terminal. 
Refer to Figure 2 below. 

Mounting

 

Mount the thermostat where it is exposed 
to normal air circulation and where it senses 
the average temperature of  the space being 
controlled (normally about 5 feet above the 
floor).  Do not mount it where it could be 
affected by heat or cold from windows, 
pipes, doors, lamps, sunlight, outside walls, 
or other sources. See Figure 3 for dimen-
sions. 

Figure 3 - Intelligent Thermostat dimensions

 

ST

-

ST+

NET

-

NET+

RED

BLACK

Electronic Systems USA, Inc.

OVERRIDE

*

ROOM/

OUTSIDE

72 ° F

RoomTemp