Johnson Controls NS Series Скачать руководство пользователя страница 1

Vertical Wallbox-Mounted or Surface-Mounted

NS Series Network Sensors with LCD Installation

Guide

Applications

The vertical wallbox-mounted or surface-mounted

NS Series Network Sensor with LCD is an electronic

zone sensor designed to function directly with Johnson

Controls

®

 BACnet

®

 Master-Slave/Token-Passing (MS/TP)

digital controllers in HVAC systems. Models in this series

monitor the temperature setpoint, zone temperature, and

humidity, and transmit this data to a field controller on the

Sensor Actuator (SA) Bus.
All models except the NS-BTF Series feature either

a temperature setpoint adjustment dial or setpoint

adjustment buttons. They also feature a °F/°C pushbutton

and an LCD designed to make adjusting the temperature

setpoint and viewing the zone temperature easier. A

warmer/cooler dial is included on NS-BTF Series models

for minor temperature adjustments from the setpoint.
Some models also allow occupants to view the Relative

Humidity (RH) of the zone; these models include a

pushbutton to toggle between temperature and RH on the

display. These models also have the capability to set the

default display to either temperature or RH.
A °F/°C pushbutton is available on all models to provide

temperature scale options for display. A fan mode

pushbutton is also included on some models to select

the desired fan speed (AUTO-OFF-low-medium-high). An

occupancy override function is featured on all models,

which allows you to signal the controller that the space

is occupied, to request an override of time-of-day

scheduling. Rotating the setpoint dial or pressing either

setpoint adjustment button signals occupancy. See

Temperature Setpoint Adjustment/Occupancy Override

 for

more information.
Select models in this series also provide Variable Air

Volume (VAV) balancing functionality. These models look

like and perform similarly to the other network sensors

but have the added capability of serving as a tool to

balance a VAV box.
Depending on the model chosen, you can terminate the

wires connecting the network sensor to the controller

using either a modular jack or screw terminal block,

offering wiring flexibility.

Note: 

Models featuring a modular jack are not

intended for installations where daisy chaining to the

MS/TP Bus is required.

All models include an SA Bus access port for connecting

accessories to access the SA Bus. This feature allows a

technician to commission or service the controller through

the network sensor.

Note: 

Since some NS Series Network Sensor features

are not supported in previous releases of 

Metasys

®

or Facility Explorer system software, we recommend

that you keep the system software up to date.

Important: 

The NS Series Network Sensor is

intended to provide an input to equipment under

normal operating conditions. Where failure or

malfunction of the network sensor could lead

to personal injury or property damage to the

controlled equipment or other property, additional

precautions must be designed into the control

system. Incorporate and maintain other devices,

such as supervisory or alarm systems or safety or

limit controls, intended to warn of or protect against

failure or malfunction of the network sensor.

Important: 

Le NS Series Network Sensor est

destiné à transmettre des données entrantes à

un équipement dans des conditions normales

de fonctionnement. Lorsqu'une défaillance ou

un dysfonctionnement du network sensor risque

de provoquer des blessures ou d'endommager

l'équipement contrôlé ou un autre équipement, la

conception du système de contrôle doit intégrer des

dispositifs de protection supplémentaires. Veiller

dans ce cas à intégrer de façon permanente d'autres

dispositifs, tels que des systèmes de supervision

ou d'alarme, ou des dispositifs de sécurité ou de

limitation, ayant une fonction d'avertissement

ou de protection en cas de défaillance ou de

dysfonctionnement du network sensor. Approved

March 14, 2003.

North American emissions compliance

United States

This equipment has been tested and found to comply with

the limits for a Class A digital device pursuant to Part 15

of the FCC Rules. These limits are designed to provide

reasonable protection against harmful interference when

this equipment is operated in a commercial environment.

This equipment generates, uses, and can radiate radio

frequency energy and, if not installed and used in

accordance with the instruction manual, may cause

harmful interference to radio communications. Operation

of this equipment in a residential area may cause harmful

interference, in which case the users will be required to

correct the interference at their own expense.

Warning (Part 15.21)

Changes or modifications not expressly approved by the

party responsible for compliance could void the user’s

authority to operate the equipment.

Canada

This Class (A) digital apparatus meets all the requirements

of the Canadian Interference-Causing Equipment

Regulations.
Cet appareil numérique de la Classe (A) respecte toutes

les exigences du Règlement sur le matériel brouilleur du

Canada.

*241009425P*

Part No. 24-10094-25   Rev. P

2021-03-31

NS-BHB700x-0, NS-BHM710x-x, NS-BHR710x-0,

NS-BPB700x-0, NS-BTB700x-x, NS-BTF700x-0, NS-

BTJ700x-x, NS-BTK700x-x, NS-BTV700x-0

Содержание NS Series

Страница 1: ...r features are not supported in previous releases of Metasys or Facility Explorer system software we recommend that you keep the system software up to date Important The NS Series Network Sensor is intended to provide an input to equipment under normal operating conditions Where failure or malfunction of the network sensor could lead to personal injury or property damage to the controlled equipmen...

Страница 2: ...djustment Tool to loosen the security screw on the top of the unit 2 Insert a coin into the slot next to the security screw location then carefully pry the top edge of the sensor assembly away from its mounting base and remove Important Do not remove the Printed Circuit Board PCB Removing the PCB voids the product warranty 3 For vertical wallbox mounted installations proceed to Step 4 For surface ...

Страница 3: ...f the network sensor assembly and rotate the assembly onto its mounting base Note On models featuring a screw terminal block be certain that the terminal block pins align with the holes in the terminal block 11 Use a 1 16 in 1 5 mm Allen wrench or Johnson Controls T 4000 119 Allen Head Adjustment Tool to tighten the security screw and fasten the network sensor assembly to the mounting base Note Do...

Страница 4: ... defaults to temperature 5 seconds after the RH pushbutton is released The NS BHR710x 0 models also have the capability to set the default display to either temperature or RH Follow this procedure to change the default display on these models 1 If the display backlight is off press and release the RH pushbutton to illuminate the backlight If the display backlight is already on proceed to Step 2 2 ...

Страница 5: ...ity Sensor Type Thin Film Capacitive Sensor Temperature Resolution 0 5F 0 5C NS Series Network Zone Sensor 1 0F 0 6C Temperature Accuracy Temperature Element Only 0 35F at 70 F 0 19C at 21 C NS BPB700x x Models 2 RH for 20 to 80 RH at 50 F to 95 F 10 C to 35 C 4 RH for 10 to 20 and 80 to 90 RH at 50 F to 95 F 10 C to 35 C Humidity Element Accuracy NS BHx7x0x x Models 3 RH for 20 to 80 RH at 77 F 2...

Страница 6: ...oncontrols com buildingswarranty Software terms Use of the software that is in or constitutes this product or access to the cloud or hosted services applicable to this product if any is subject to applicable end user license open source software information and other terms set forth at www johnsoncontrols com techterms Your use of this product constitutes an agreement to such terms Patents Patents...

Отзывы: