User Manual: NEO System
8
Rev.0.3
d)
DIS: “Disarmed” / “Disabled” - Amber
Active (on) when any zone from the voice alarm zones is disabled.
e)
PA: “Public Address” - White
Active when the equipment is not in a state of emergency.
2.1.2 Channel Status Indicators
The channel status indicators show the channel operating state or condition at all times.
f) EMG: “Emergency” - Red
Active (on) when the equipment is in a state of emergency operation (voice alarm) or by
manual or automatic activation from the CIE, in any of the voice alarm zones. When the
system is in a state of emergency and it is broadcasting a spoken voice, either through the
emergency microphone or by a pre-recorded evacuation message, the indicator light will
flash.
g)
FLT/DIS: “Fault/Disarmed” - Amber
Active (on) when the voice evacuation channel is turned off.
Active (flashing) when a fault is detected on a voice evacuation channel. This indicator is
activated automatically upon detection of failure of any supervised functions in the
channel. If none of the indicators of general supervised function is on, it will indicate a fault
in the speaker's line. Restart the fault condition.
h)
SIGNAL: “Signal” - Green
Active (on) when an amplifier channel output signal from the corresponding voice
evacuation zone has been detected. The minimum level at which the indicator will light is:
-50dB.
2.1.3 Supervised Function Indicators
Supervised Functions indicators show the faults that affect the general system functions.
i) CIE: “CIE” / “ECI”
Active (on) when a failure occurs in the transmission line between the CIE and the system.
Reset fault condition. If the faults persists, see chapter
5.2. for its resolution. Amber
colour.
j) PROTECT: “Protection”
Active (on) when any of the system protection devices are active. Restart the fault
condition. Reset fault condition. If the fault persists, see chapter 5.3
Amber colour.
k)
POWER: “Power” / “Supply”
Active (on) when there is a power failure in the system. It may be due to a failure at the
main power supply or at the emergency power supply. Reset fault condition. If the fault
persists, see chapter 5.4
for its resolution. Amber colour.