User Manual: NEO System
57
Rev.0.3
10 Appendix C: Cabling section for speaker lines.
The table below reflects the maximum desirable distance for 100V speaker lines. The type of
cable that is used for the calculations is a two-wire type with copper conductor. The values
shown may be used as a guide for planning, being the responsibility of the installer who will
make the appropriate final calculations for each case.
The table shows the output power of typical amplification channels, constant voltage 100V in
effective watts (rms) are expressed. The maximum length for 70V lines is half of what is
reflected in the table.
Section
Maximum length with 5% of loss of power
AWG
ømm
mm
2
60Wrms
120Wrms
240Wrms
480Wrms
960Wrms
6
4.11
13.3
3260
1630
810
405
200
7
3.67
10.6
2600
1300
645
320
160
8
3.26
8.35
2050
1025
510
255
130
9
2.91
6.62
1625
810
405
200
100
10
2.59
5.27
1300
645
320
160
80
11
2.3
4.15
1020
510
255
130
65
12
2.05
3.31
810
405
200
100
50
13
1.83
2.63
645
320
160
80
40
14
1.63
2.08
510
255
130
65
35
15
1.45
1.65
405
200
100
50
25
16
1.29
1.31
320
160
80
40
20
17
1.15
1.04
255
130
65
35
15
18
1.02
0.82
200
100
50
25
13
Table 23 - Section of Cabling for Lines of 100V
Notes
•
AWG (American Wire Gauge): American Wire Gauge. Classification according to USA
standard diameters.
•
ømm cable diameter in millimeters
•
mm
2
: Cross-sectional area in square millimeters cable