User Manual: NEO System
27
Rev.0.3
3.2.5 Emergency State Log
The system has a log that records the operations or indications made during the Emergency
state. The emergency state log will be displayed on the screen automatically when the
equipment / system is being remotely activated. It will show the log for one hour after the last
entry occurred in the log. A whole year's log will be accessible through the configuration
application.
Once the log has been checked, press the “ACK" button and the log will automatically stop
being displayed. You can access the record again by pressing the “EMERGENCY LOG" button
in the EMG state. A list of records will be showed in chronological order from newest to oldest
operations and indications that have occurred. To exit the emergency state log, press the
"BACK" button.
To view all issued logs, use the scroll control up and down to scroll the window. You can see an
overview of all logs in Appendix B: Content of logs.
3.2.6 Voice Evacuation Zone Volume Adjustment
The equipment/system has an independent adjustment of the volumes of voice evacuation
zones. If this setting is not defined, the volume in this state will be the same as configured in the
paging mode (see 3.5.1).
To set the volume, adjust the volume through the configuration application or according to 3.5.1.
Once the setting has been made, use the configuration application to memorize it as the default
volume for the emergency state.
3.3 Failure
3.3.1 Failure State Log
The system has a log of detected failures. This log will be automatically displayed on the screen
when the equipment / system is in this state for five minutes since the last entry occurred in the
log. A whole year's log will be accessible through the configuration application.
Once the log has been checked, press the "ACK" button and the log will stop displaying
automatically. It can be viewed again by pressing the shortcut button to the fault state "FLT", a
list will show the operations and indications that have occurred, in chronological order from
newest to oldest. To exit the emergency state log, press the "BACK" button.
To view all logs, use the scroll control to scroll up and down the window. You can see an
overview of all logs in Appendix B: Content of logs.
3.3.2 Reset Failure’s State
To reset the failure's state, press the "RESET" button, the display will show a user control
access level 2 (see 2.3). To return, press the "BACK" button. Upon successful completion of the
control access, all faults will be reset.