Johnson Controls ME Series Скачать руководство пользователя страница 2

5724452-UIM-A-0619

2

Johnson Controls Ducted Systems

SAFETY REQUIREMENTS

Failure to carefully read and follow all instructions in this manual
can result in air handler malfunction, death, personal injury and/or
property damage.

This air handler must be installed in accordance with all national
and local building/safety codes and requirements, local plumbing
or wastewater codes, and other applicable codes. 

This air handler must be installed only in a location and position
specified in the “Unit Installation” section of this Instruction Man-
ual. 

The air handler is not to be used for temporary heating of build-
ings or structures under construction. 

Always install the air handler to operate within the air handler’s
intended maximum outlet air temperature. 

The unit rating plate displays the air handler model number. The
unit dimensions for the supply air plenum are provided in Figure 5
and Table 1 of this Instruction Manual. The plenum must be
installed according to the instructions. The return air duct attach-
ment is shown in Figure 1.

Clearance from combustible material is provided under “Clear-
ances” in the “Unit Installation” section. 

It is necessary to maintain clearances for servicing. Access must
be allowed for electric heaters and blower.

The unit rating plate and power supply must be verified to ensure
that the electrical characteristics match.

Air handler shall be installed so the electrical components are
protected from water. 

Installing and servicing heating/cooling equipment can be haz-
ardous due to the electrical components. Only trained and
licensed personnel should install, repair, or service heating/cool-
ing equipment. Unlicensed service personnel can perform basic
maintenance functions such as cleaning and replacing the air fil-
ters. When working on heating/cooling equipment, the precau-
tions in the manuals and on the labels attached to the unit and
other safety precautions must be observed as applicable.

These instructions cover minimum requirements and conform to
existing national standards and safety codes. In some instances
these instructions exceed certain local codes and ordinances,
especially those who have not kept up with changing residential
and non-HUD modular home construction practices. These
instructions are required as a minimum for a safe installation.

INSPECTION

As soon as a unit is received, it must be inspected for possible damage
during transit. If damage is evident, the extent of the damage must be
noted on the carrier’s freight bill. A separate request for inspection by
the carrier’s agent must be made in writing. Also, before installation the
unit must be checked for screws or bolts that may have loosened in
transit. There are no shipping or spacer brackets which need to be
removed.

It must be verified that all accessories such as heat kits and coils are
available. Installation of these accessories or field conversion of the unit
must be done before setting the unit in place or connecting any wiring,
duct work, or piping.

SECTION III: UNIT INSTALLATION

UNIT SIZING

The size of the unit must be based on an acceptable heat loss or
gain calculation for the structure. The ACCA – Manual J or other
approved methods may be used.

Only connect the air handler to a duct system which has an exter-
nal static pressure within the allowable range. 

Airflow must be within the minimum and maximum limits
approved for electric heat, indoor coils, and outdoor units.

When an air handler is installed so that supply ducts carry air cir-
culated by the air handler to areas outside the space containing
the air handler, the return air shall also be handled by duct(s)
sealed to the air handler casing and terminating in the space to
be cooled/heated. 

Refer to the unit rating plate for the air handler model number,
and then see the dimensions page of this instruction for supply air
plenum dimensions. The plenum must be installed according to
the instructions. 

The installer must check available supply power and verify that it
is within the normal operating voltage range for the unit. The
acceptable voltage range for these units is as follows:

 WARNING

Improper installation, adjustment, alteration, or maintenance may cre-
ate a condition where the operation of the product could cause per-
sonal injury or property damage. Refer to this manual for assistance,
or for additional information, consult a qualified contractor, installer, or
service agency.

 CAUTION

This product must be installed in strict compliance with the installation
instructions and any applicable local, state, and national codes
including, but not limited to building, electrical, and mechanical codes.

 CAUTION

These air handlers should be transported and handled in an upright,
upflow position. Failure to do so may result in unit damage and per-
sonal injury. Configuration conversions should be done at site of
installation.

!

!

!

 FIGURE 1:  

Return Air Duct Attachment

Entering Air Temperature Limits

Wet Bulb Temp.°F

Dry Bulb Temp. °F

Min.

Max.

Min.

Max.

57

72

65

95

Air Handler Voltage

Normal Operating 

1

 Voltage Range

1. Rated in accordance with ARI Standard 110, utilization range “A”.

208-230-1-60

187-253

S

IDE VIEW

RETURN AIR

DU

C

T

A

0

3

9

8-

001

Wh

en

 

atta

ch

ing

 

du

c

t

 wo

r

k w

it

h

s

c

re

w

s

 - k

ee

s

c

re

w

s

 w

it

h

in

 5/8”

o

f

 

sides

 

and

 b

a

ck o

f

 

air

 h

and

l

er

.

Содержание ME Series

Страница 1: ...ns These units may be located in a closet utility room attic crawl space or basement These versatile models may be used for cooling or heat pump operation with or without electric heat or indoor coil Top or side power and control wiring color coded leads for control wiring and electric heaters all combine to make the installation easy and minimize installation cost Electric heat kits are available...

Страница 2: ... for inspection by the carrier s agent must be made in writing Also before installation the unit must be checked for screws or bolts that may have loosened in transit There are no shipping or spacer brackets which need to be removed It must be verified that all accessories such as heat kits and coils are available Installation of these accessories or field conversion of the unit must be done befor...

Страница 3: ...casing may occur On these installations unit duct connections and other openings must be properly sealed and a wrap of 2 fiberglass insulation with vinyl vapor barrier must be used AIR HANDLER CONFIGURATION These air handler units are supplied ready to be installed in an upflow downflow horizontal right or horizontal left position Refer to Figure 2 The unit requires no conversion procedures AIR HA...

Страница 4: ...M INLET DIMENSIONS C D 12 3 16 19 1 8 B 20 1 2 21 1 2 TABLE 1 Dimensions ME MODELS Dimensions1 Wiring Knockout Dimensions1 A B C D E F Height Width Bottom Opening Top Opening Power Control ME08B 21 1 2 17 1 2 16 1 2 16 1 2 7 8 1 2 1 3 8 1 1 23 32 1 1 4 7 8 1 2 ME12B 21 1 2 17 1 2 16 1 2 16 1 2 ME12C 22 1 2 21 20 20 ME14D 22 1 2 24 1 2 23 1 2 23 1 2 ME16C 22 1 2 21 20 20 ME20D 22 1 2 24 1 2 23 1 2 ...

Страница 5: ...t be designed in accordance with the Air Conditioning Contractors of America ACCA Manual D HORIZONTAL SUSPENSION For suspension of these units in horizontal applications it is recom mended to use angle steel support brackets with threaded rods sup porting the units from the bottom at the locations shown in Figure 6 DUCT FLANGES Three duct flanges are provided to assist in positioning and attaching...

Страница 6: ...ired for Horizontal right hand airflow applica tion only Follow instructions with heater for modification SECTION VI LINE POWER CONNECTIONS Power may be brought into the unit through the supply air end of the unit top left when unit is vertical or the left side panel Use the hole appropriate to the unit s orientation in each installation to bring conduit from the disconnect The power lead conduit ...

Страница 7: ...eat kit connected to tap 5 for the heating speed and the Yellow cooling heat pump lead connected to tap 4 for the cooling heat pump heating speed Move the electric heat kit wire for the heating speed from tap 5 to the appropriate speed tap according to Table 4 If electric heat requires speed tap 5 the highest speed tap available for cooling heat pump heating is tap 4 The circulating blower Green t...

Страница 8: ...de or in Canada the Canadian Electrical Code and local codes to determine correct wire sizing TABLE 4 Minimum Fan Speed Electrical Heat with Heat Pump Heat Kit Models1 2 3 Nom kW 240 V Air Handler Models ME08B ME12B ME12C ME14D ME16C ME20D 6HK 0 1 6500206 2 4 kW Medium Low 2 Medium Low 2 Medium Low 2 Medium Low 2 Medium Low 2 Medium Low 2 6HK 0 1 6500506 4 8 kW Medium 3 Medium Low 2 Medium 3 Mediu...

Страница 9: ... following table DISTRIBUTION POWER NOMINAL VOLTAGE CONVERSION FACTOR 208 V 240 V 0 75 220 V 240 V 0 84 230 V 240 V 0 92 TABLE 7 Electric Heat Performance Data 208 230 1 60 and 208 230 3 60 Heater Models1 2 3 Nominal kW 240 V Total Heat4 kW Staging kW MBH W1 Only W1 W2 208 V 230 V 208 V 230 V 208 V 230 V 208 V 230 V 1PH 6HK 0 1 6500206 2 4 1 8 2 2 6 2 7 5 1 8 2 2 1 8 2 2 6HK 0 1 6500506 4 8 3 6 4 ...

Страница 10: ... 7 76 5 70 80 6HK 1 2 6501806 72 82 9 91 2 90 100 6HK 1 2 6502006 80 91 3 100 4 100 110 ME12C 6HK 0 1 6500206 10 15 6 16 7 20 20 6HK 0 1 6500506 20 26 4 28 7 30 30 6HK 0 1 6500806 32 39 6 43 3 40 45 6HK 0 1 6501006 40 48 0 52 6 50 60 6HK 1 2 6501306 52 61 2 67 3 70 70 6HK 1 2 6501506 60 69 7 76 5 70 80 6HK 1 2 6501806 72 82 9 91 2 90 100 6HK 1 2 6502006 80 91 3 100 4 100 110 ME14D 6HK 0 1 6500206 ...

Страница 11: ...vice must be HACR type circuit breaker or time delay fuse Refer to the latest edition of the National Electrical Code or in Canada the Canadian Electrical Code and local codes to determine correct wire sizing TABLE 10 Electrical Data for Single Source Power Supply 208 230 3 60 Air Handler Models Heater Models1 Heater Amps 240 V Field Wiring Min Circuit Ampacity MOP 2 208 V 230 V 208 V 230 V ME08B ...

Страница 12: ... High 5 923 892 862 833 797 743 688 Medium High 4 846 816 786 750 710 638 599 Medium 3 631 605 575 512 442 370 282 Medium Low 2 570 530 460 402 328 232 186 Low 1 477 448 372 292 203 157 24 CM30B High 5 937 905 877 841 798 748 704 Medium High 4 846 808 778 733 667 636 572 Medium 3 638 609 556 495 463 399 336 Medium Low 2 560 484 469 408 321 265 201 Low 1 481 448 390 328 252 166 92 ME12B CM18B High ...

Страница 13: ...124 1060 1008 954 889 827 755 ME20D CM36D High 5 2061 2021 1979 1938 1904 1865 1829 Medium High 4 1998 1949 1914 1879 1835 1797 1756 Medium 3 1769 1711 1677 1643 1603 1570 1530 Medium Low 2 1557 1508 1469 1439 1398 1355 1323 Low 1 1340 1291 1252 1216 1170 1132 1058 CM42D High 5 2032 1996 1959 1913 1890 1849 1820 Medium High 4 1974 1938 1892 1855 1824 1785 1754 Medium 3 1752 1706 1680 1633 1591 154...

Страница 14: ...s run the fan only to assure a dry coil Drill 2 holes one 12 away from the air handler in the supply air duct and on 12 away from the air handler in the return air duct before any elbows in the duct work Insert the pressure tips and read the pressure drop from the manometer See Table 12 to determine the airflow and make the necessary adjustments to keep the CFM within the airflow limitations of th...

Страница 15: ...AGE FIELD WIRING CONNECTIONS LEGEND LS LIMIT SWITCH SEQ SEQUENCER HE HEATING ELEMENT FL FUSIBLE LINK H SEQUENCER HEATER RLY RELAY AIR HANDLER WITH NO HEAT KIT WIRING DIAGRAM 5724441 UWD A 0219 1 2 3 4 5 6 1 2 3 4 5 6 L2 L1 HE2 LS FL RLY 2 RLY 1 RED WHT EQUIPMENT GROUND YEL BLK BLU YEL WHT BLU PRP BLU BLU HE1 LS FL WHT HEATER KITS 6HK 6500806 6HK 6501006 1 2 3 4 5 6 24V 240V COM 208V 1 2 3 4 5 6 1 ...

Страница 16: ...UE BLUE BLUE BLUE YELLOW YELLOW BLACK BLACK YELLOW YELLOW BLACK BLACK RED WHITE BLACK BLUE BLACK BLUE YELLOW BLACK YELLOW YELLOW BLUE BLACK BLUE BLACK YELLOW RLY 1 RLY 2 RLY 3 RLY 6 RLY 5 RLY 4 HE2 FL HE3 FL HE6 FL HE1 FL HE4 FL HE5 FL 5 4 3 2 6 1 WHITE BLUE PURPLE RED WHITE BLACK GND LS LS LS LS LS LS WHITE WHITE BLUE BLUE BLUE WHITE BROWN BROWN BLUE BLUE BROWN BLUE BROWN BLUE BLACK BLUE YELLOW B...

Страница 17: ... HE1 HE2 LS LS HE3 LS FL FL FL SEQ2 SEQ1 RED WHT EQUIPMENT GROUND BLK RED YEL BLK RED BLK BRN WHT BLU PRP BLU YEL BLU 1 2 3 4 5 6 RLY BLU BLU BLU YEL BLU YEL BRN 3 1 5 4 H H 3 1 5 4 H H Y2 OUT W1 OUT W2 OUT C R Y1 Y2 W O C R Y1 Y2 W E O G DEFROST CONTROL BOARD 2 STAGE HEAT PUMP 3 STAGE HEAT 2 STAGE COOL ROOM TERMMOSTAT NOTICE WIRING FOR BLOWER MOTOR MAY REQUIRE FIELD ADJUSTMENT DEPENDING ON MATCHU...

Страница 18: ...5724452 UIM A 0619 18 Johnson Controls Ducted Systems NOTES ...

Страница 19: ...dry bulb temperature Return air dry bulb temperature Temperature drop 1 2 3 4 5 Low Medium Low Medium Medium High High A B C D Outside air dry bulb temperature Return air wet bulb temperature Supply air wet bulb temperature Return static inches of water column Electrical Connections Inspection Complete all that apply Continued on next Page ECM X 13 PSC A B C D Low voltage value between R and C at ...

Страница 20: ...ting and correcting any problems Operate the unit through cooling cycles from the thermostat noting and correcting any problems Operate the unit through mechanical heating cycles from the thermostat noting and correcting any problems Operate the unit through emergency heating cycles from the thermostat noting and correcting any problems Job site has been cleaned indoor and outdoor debris removed f...

Отзывы: