background image

M9220-GGx-3 Proportional Electric Spring Return Actuators Installation 

Guide

1

Applications 

The M9220-GGx-3 Proportional Electric Actuators are 
direct-mount, spring return electric actuators that 
operate on AC/DC 24V power. These bidirectional 
actuators do not require a damper linkage, and are 
easily installed on dampers with 1/2 to 3/4 in. or 12 to 
19 mm round shafts, or 3/8 and 1/2 in. or 
10, 12, and 14 mm square shafts using the standard 
shaft clamp included with the actuator. An optional 
M9220-600 Jackshaft Coupler Kit is available for 
3/4 to 1-1/16 in. or 19 to 27 mm round shafts, or 
5/8 and 3/4 in. or 16, 18, and 19 mm square shafts.

A single M9220-GGx-3 Series Proportional Electric 
Spring Return Actuator provides a running and spring 
return torque of 177 lb·in (20 N·m). Two or three like 
models mounted in tandem deliver twice or triple the 
torque (354 lb·in [40 N·m] or 531 lb·in [60 N·m]). 
Integral line voltage auxiliary switches are available on 
the GGC models to indicate end-stop position or to 
perform switching functions within the selected rotation 
range.  

IMPORTANT:

Use this M9220-GGx-3 Proportional 

Electric Spring Return Actuator only to control 
equipment under normal operating conditions. 
Where failure or malfunction of the electric actuator 
could lead to personal injury or property damage to 
the controlled equipment or other property, 
additional precautions must be designed into the 
control system. Incorporate and maintain other 
devices, such as supervisory or alarm systems or 
safety or limit controls, intended to warn of or protect 
against failure or malfunction of the electric actuator.

IMPORTANT: 

Utiliser ce M9220-GGx-3 Proportional 

Electric Spring Return Actuator uniquement pour 
commander des équipements dans des conditions 
normales de fonctionnement. Lorsqu'une défaillance 
ou un dysfonctionnement du electric actuator risque 
de provoquer des blessures ou d'endommager 
l'équipement contrôlé ou un autre équipement, la 
conception du système de contrôle doit intégrer des 
dispositifs de protection supplémentaires. Veiller 
dans ce cas à intégrer de façon permanente 
d'autres dispositifs, tels que des systèmes de 
supervision ou d'alarme, ou des dispositifs de 
sécurité ou de limitation, ayant une fonction 
d'avertissement ou de protection en cas de 
défaillance ou de dysfonctionnement du electric 
actuator.

M9220-GGx-3 Proportional Electric Spring Return 
Actuators

Installation Guide

Part No. 34-636-1697, Rev. L

Issued November 2019

*346361697L*

34-636-1697, Rev. L

Содержание M9220-GG-3 Series

Страница 1: ... only to control equipment under normal operating conditions Where failure or malfunction of the electric actuator could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of or...

Страница 2: ...s the electrical connections and wiring details are also included on the actuator housing Parts Included Proportional electric spring return actuator with coupler Anti rotation bracket Manual override crank Two M3 x 9 5 mm self drilling sheet metal mounting screws Two No 10 32 x 9 16 in thread forming conduit screws Special Tools Needed Torque wrench with 3 8 in 10 mm socket Digital voltmeter Flat...

Страница 3: ...ions Figure 1 M9220 GGx 3 Proportional Electric Spring Return Actuator Dimensions in mm A 4 102 10 5 16 262 2 3 16 56 FIG M9210_9220_dimen 1 3 4 44 1 8 3 3 3 16 81 3 4 19 2 3 16 56 1 25 2 51 1 19 32 40 1 1 16 27 1 4 6 5 Mounting Hole 6 Locations 1 19 32 40 1 19 32 40 6 15 16 176 10 254 ...

Страница 4: ...ity 1 M9000 320 Weather Shield Enclosure NEMA 3R enclosure for protecting a single M9210 20 actuator from rain sleet or snow quantity 1 M9000 400 Jackshaft Linkage Kit Open ended design enables clamping onto a jackshaft without requiring access to the ends of the jackshaft quantity 1 M9000 519 Valve linkage for mounting M9220 actuator to 2 1 2 to 6 in flanged ball valves M9000 604 Replacement Anti...

Страница 5: ...W Removable Coupler The coupler may be installed on either side of the output hub If the damper shaft is less than 3 19 32 in 91 mm long insert the coupler in the face of the actuator closest to the damper If the damper shaft is shorter than 1 5 32 in 29 mm long a shaft extension is required to mount the actuator Figure 2 Side A of Actuator A 90 5 10 20 30 40 50 60 70 80 Manual Override Pointer Sh...

Страница 6: ...e direction to lock the actuator hub in place Note To unlock the actuator hub rotate the manual override crank in the direction indicated by the arrow on the label The actuator hub automatically unlocks when power is applied to the actuator and returns the actuator to normal drive and spring return operation Mounting the Actuator To mount the actuator proceed as follows 1 See the dimensions in Fig...

Страница 7: ...n unused mounting hole 10 Apply power long enough for the actuator to travel a full stroke and verify that the actuator rotates freely throughout the range Note If electric power is not available complete this verification by reinserting the manual override crank and turning it in the direction indicated to rotate the coupler to the fully open position Rotation Range Using Optional M9220 603 Adjus...

Страница 8: ...tween 5 to 90 causes the output hub to stop motion and hold its position until power is removed Rotation is mechanically limited to the 5 and 90 positions by integral end stops Optional end stops are available to limit the output hub travel An anti rotation bracket prevents rotational movement of the actuator body See Figure 9 Figure 10 and Figure 11 for proper wiring of the M9220 GGx 3 Proportion...

Страница 9: ... V Figure 11 M9220 GGx 3 Control Wiring Diagram Overrides 1 2 3 4 Y COM U BLK RED GRY ORN Override to MIN position AC 24 V DC 0 2 10 V DC 0 2 10 V A A Open MIN Position A Closed Normal Operation 1 2 3 4 Y COM U BLK RED GRY ORN Override to MAX position AC 24 V DC 0 2 10 V DC 0 2 10 V C B Closed MAX Position C Closed Normal Operation B 1 2 3 4 COM U BLK RED GRY ORN Override to MIN MID MAX positions ...

Страница 10: ...ion range The actuator stores the reduced rotation range in nonvolatile memory retains data when power is lost or removed To calibrate the control input range proceed as follows 1 With power off move the mode selection switch to the CAL position Figure 13 Then energize the actuator The actuator automatically rotates until the end stops are found and proportionally reconfigures the control input ra...

Страница 11: ...nning Power x 1 5 Only one of the actuators can be configured as the master Set the selector switch to the master position Figure 15 The other GGx actuator s must be configured as subordinate s by setting the tandem selector switch to the subordinate position The master can accept DC 0 10 V or DC 2 10 V or 4 20 mA command signals based on the master s switch settings and or external resistor The m...

Страница 12: ...liary Switch No 1 is 11 closing and the nominal factory setting for Auxiliary Switch No 2 is 81 opening relative to a 0 to 90 rotation range See the Technical Specifications table for the auxiliary switch ratings The switch point of Auxiliary Switch No 1 is fixed The switch point of Auxiliary Switch No 2 is independently and continuously adjustable from 25 to 95 See Figure 17 and use the method in...

Страница 13: ...lly open position and holds while power is applied 4 Observe the switch point If required repeat Steps 2 and 3 Repairs and Replacement A number of replacement parts are available see Table 1 for more details If the M9220 GGx 3 Proportional Electric Spring Return Actuator fails to operate within its specifications replace the unit For a replacement electric actuator contact the nearest Johnson Cont...

Страница 14: ...ction is selectable with mounting position of actuator Side A actuator face away from damper for CCW spring return Side B actuator face away from damper for CW spring return Running and Spring Return Torque 177 lb in 20 N m for a single actuator 354 lb in 40 N m for two like models mounted in tandem 531 lb in 60 N m for three like models mounted in tandem Rotation Range Adjustable from 30 to 90 CW...

Страница 15: ...isted CCN XAPX7 File E27734 to CAN CSA E60730 1 Automatic Controls for Household and Similar Use and CAN CSA E60730 2 14 Part 2 Particular Requirements for Electric Actuators Models All Europe CE Mark Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive and Low Voltage Directive Australia and New Zealand RCM...

Страница 16: ... johnsoncon Technical support Region Group Contact information North America Product Technical Support 1 800 275 5676 Option 2 Product Technical Support then Option 1 HVAC psotechsupport jci com Option 2 FX and Metasys Option 3 PENN Controls Refrigeration refrig techsupport jci com Field Support Center CGFieldSupportCenter jci com 1 800 524 1330 Applied DX Technical Support applieddxtechsupport jc...