Technical Specifications  

M9203-AGx-2(Z) Series On/Off and Floating Point Control Electric Spring Return Actuator
 (Part 1 of 2 )

Power

Requirements

-AGx-2 Models

AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety 

Extra-Low Voltage (SELV) (Europe), 4.7 VA Running, 2.7 VA Holding Position
DC 24 V (DC 21.6 V to 28.8 V): Class 2 (North America) or SELV (Europe), 1.8 W 

Running, 1 W Holding Position
Minimum Transformer Size: 6 VA per Actuator

-AGx-2Z Models

AC 24 V (AC 19.2 V to 28.8 V) at 50/60 Hz: Class 2 (North America) or Safety 

Extra-Low Voltage (SELV) (Europe), 5.1 VA Running, 2.8 VA Holding Position 

DC 24 V (DC 19.2 V to 28.8 V): Class 2 (North America) or SELV (Europe), 1.9 W 

Running, 1.1 W Holding Position
Minimum Transformer Size: 6 VA per Actuator

Input Signal

-AGx-2(Z) Models

AC 19.2 to 28.8 V at 50/60 Hz or DC 24 V +20%/-10%
Class 2 (North America) or SELV (Europe)
Minimum Pulse Width: 500 msec

Control Input 

Impedance

-AGx-2(Z) Models

4,700 ohm

Auxiliary Switch

Rating

-xxB Models

One Single-Pole, Double-Throw (SPDT), Double-Insulated Switch with Silver 

Contacts:
AC 24 V, 50 VA Pilot Duty
AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty
AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty

Spring Return

Direction Is Selectable with Mounting Position of Actuator:
Actuator Face Labeled A Is Away from Damper or Valve: CCW Spring Return
Actuator Face Labeled B Is Away from Damper or Valve: CW Spring Return

Rated Torque

Power On

(Running)

27 lb·in. (3 N·m) All Operating Temperatures

Power Off

(Spring 

Returning)

27 lb·in. (3 N·m) All Operating Temperatures

Rotation Range

Maximum Full Stroke: 95°
Adjustable Stop: 35 to 95° Maximum Position

Rotation Time

for 90 Degrees of

Travel

Power On

(Running)

-AGx-2 Models

150 Seconds Constant for 0 to 27 lb·in. (3 N·m) Load, at All Operating Conditions

Power On

(Running)

-AGx-2Z Models

90 Seconds Constant for 0 to 27 lb·in. (3 N·m) Load, at All Operating Conditions

Power Off

(Spring 

Returning)

12 to 17 Seconds for 0 to 27 lb·in. (3 N·m) Load, at Room Temperature
16 Seconds Nominal at Full Rated Load
22 Seconds Maximum with 27 lb·in. (3 N·m) Load at -22°F (-30°C)

Life Cycles

60,000 Full Stroke Cycles with 27 lb·in. (3 N·m) Load
1,500,000 Repositions with 27 lb·in. (3 N·m) Load

Содержание M9203-AG-2 Series

Страница 1: ...the actuator No additional linkages or couplers are required Electrical connections are color coded and identified with numbers permanently marked on the actuator cable A tag on the actuator cable identifies the electrical connections and wiring details are included on the actuator housing IMPORTANT Use this M9203 AGx 2 Z Series On Off and Floating Point Electric Spring Return Actuator only to con...

Страница 2: ... this M9203 AGx 2 Z Series On Off and Floating Point Electric Spring Return Actuator in or near environments where corrosive substances or vapors could be present Exposure of the electric actuator to corrosive environments may damage the internal components of the device and will void the warranty Figure 1 M9203 AGx 2 Series On Off and Floating Point Electric Spring Return Actuator Dimensions in m...

Страница 3: ...9000 560 Ball Valve Linkage Kit for applying M9104 M9203 and M9208 Series Electric Actuators to VG1000 Series Valves quantity 1 M9000 561 Thermal Barrier Kit for M9000 560 Ball Valve Linkage Extends M VA 9104 M VA 9203 M VA 9208 and M VA 9308 9310 Series Electric Actuators applications to include low pressure steam quantity 1 M9000 604 Replacement Anti Rotation Bracket Kit for M9203 M9208 M9220 an...

Страница 4: ... to the damper If the damper shaft extends less than 0 79 in 20 mm a shaft extension is required to mount the actuator To change the coupler s position see Figure 4 and proceed as follows 1 Mount the coupler on either Side A or Side B of the actuator as determined by the shaft length 2 Snap the locking clip securely into the coupler retention groove to retain the coupler Mounting the Actuator To m...

Страница 5: ... coupler side of the actuator to reduce the rotation range Attaching the stroke limiting stop in the furthest mounting position reduces the rotation range of the actuator by 5 Each progressive mounting position reduces the rotation range an additional 5 1 Check that the damper blade is visible or its position is permanently marked on the end of the damper shaft as illustrated in Figure 7 2 Positio...

Страница 6: ...ltage can cause electric shock and may result in severe personal injury or death AVERTISSEMENT Risque de décharge électrique Débrancher ou isoler toute alimentation avant de réaliser un branchement électrique Plusieurs isolations et débranchements sont peut être nécessaires pour couper entièrement l alimentation de l équipement Tout contact avec des composants conducteurs de tensions dangereuses r...

Страница 7: ... can be switched by the user to Reverse Acting RA mode CAUTION Risk of Property Damage Insulate and secure each unused wire lead before applying power to the actuator Failure to insulate and secure each unused wire lead may result in property damage MISE EN GARDE Risque de dégâts matériels Isoler et protéger chaque fil non utilisé avant de mettre l actuator sous tension Le non respect de cette obl...

Страница 8: ... and apply power to the actuator The actuator moves to the fully open position and holds while power is applied 4 Observe the switch point If required repeat Step 1 through Step 3 Repair Information A number of replacement parts are available see Table 1 for more details If an M9203 AGx 2 Z Series On Off and Floating Point Control Electric Spring Return Actuator fails to operate within its specifi...

Страница 9: ...ole Double Throw SPDT Double Insulated Switch with Silver Contacts AC 24 V 50 VA Pilot Duty AC 120 V 5 8 A Resistive 1 4 hp 275 VA Pilot Duty AC 240 V 5 0 A Resistive 1 4 hp 275 VA Pilot Duty Spring Return Direction Is Selectable with Mounting Position of Actuator Actuator Face Labeled A Is Away from Damper or Valve CCW Spring Return Actuator Face Labeled B Is Away from Damper or Valve CW Spring R...

Страница 10: ...tandard Operating 22 to 140 F 30 to 60 C 90 RH Maximum Noncondensing Storage 40 to 185 F 40 to 85 C 95 RH Maximum Noncondensing Dimensions 6 38 x 3 23 x 2 26 in 162 x 82 x 57 5 mm Compliance United States UL Listed CCN XAPX File E27734 to UL 60730 1A 2003 08 Ed 3 1 Automatic Electrical Controls for Household and Similar Use and UL 60730 2 14 2002 02 Ed 1 Part 2 Particular Requirements for Electric...

Страница 11: ...t warranty This product is covered by a limited warranty details of which can be found at www johnsoncontrols com buildingswarranty Patents Patents http jcipat com Single point of contact APAC Europe NA SA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MIC...

Отзывы: