![Johnson Controls LSWU025 Скачать руководство пользователя страница 172](http://html.mh-extra.com/html/johnson-controls/lswu025/lswu025_manual_2023363172.webp)
JOHNSON CONTROLS
172
FORM 145.05-NOM7
ISSUE DATE: 10/31/2019
SECTION 6 – USER INTERFACE CONTROL CENTER
TABLE 42 -
BACNET MS/TP, MODBUS, BACNET IP
BACNET
NAME
USER INTERFACE
NAME
READ/
WRITE
BACNET
OBJECT
TYPE AND
INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
ACT _DSP_
SP
Duct Static Setpoint
R
AI01
514
A Derived Value the Duct Static is Controlled
to ("WG)
ACT_MIN_
POS
Active Minimum
Position
R
AI03
516
A Derived Value the Damper is Controlled to
for Minimum Ventilation Air (%)
ACT_SAT_
SP
Supply Air Setp
R
AI04
517
A Derived Value the Supply Air Temperature
is Controlled to (F)
ACT_SLAB_
CTL
Active Slab Control
R/W
AI5
1102
Allows the Active Slab Control Feature to be
Turned On and Off on FlexSys Units (0 = Off
/ 1 = On)
ALARM
Alarm
R
BI02
1283
Gives the Status of the Alarm (NFL - No
Fault; FLT - Faulted)
AMORN_
WA_ACT
Adapt Morn Warm Up
Active
R
BI01
1282
Identifies when Adaptive Morning Warm Up
is Active (Off / On)
AV_PRS_A_
SUC
Avg Press Suction A
R
AI5
518
Gives the Average Suction Pressure for the
System A Unloading Compressor
AV_PRS_DIS
Avg Press Discharge A
R
AI2
515
Gives the Average Discharge Pressure for
the System A Unloading Compressor
BYPASS_
DAMPER
Bypass Damper
R
AI06
519
Actual Bypass Damper Position (%)
BYP_VALV_
POS
Bypass Valve Position
R
AI64
577
The Analog Output from the Control to the
Bypass Valve
COMFORT_
VENT
Comfort Ventilation
R/W
AI2
1103
Gives the Status of the Comfort Vent Option
and Allows it to be Turned On and Off (0 =
Off; 1 = On)
COMP_A
Compressor A
R
BI03
1284
Status of Compressor A, (On/Off)
COMP_B
Compressor B
R
BI04
1285
Status of Compressor B, (On/Off)
COMP_C
Compressor C
R
BI05
1286
Status of Compressor C, (On/Off)
COMP_D
Compressor D
R
BI06
1287
Status of Compressor D, (On/Off)
COMP_E
Compressor E
R
BI07
1288
Status of Compressor E, (On/Off)
COMP_F
Compressor F
R
BI08
1289
Status of Compressor F, (On/Off)
COMP_A_
LOAD
Compressor A Load
R
AI15
528
Gives the Status of the Unloading Compres-
sor in %.
COMP_A_
OPER
Compressor 1A Oper
Hrs
R
AI09
522
The Number of Hours Compressor A has
been in Operation (Hour)
COMP_B_
OPER
Compressor 1B Oper
Hrs
R
AI10
523
The Number of Hours Compressor B has
been in Operation (Hour)
COMP_C_
OPER
Compressor 2A Oper
Hrs
R
AI11
524
The Number of Hours Compressor C has
been in Operation (Hour)
COMP_D_
OPER
Compressor 2B Oper
Hrs
R
AI12
525
The Number of Hours Compressor D has
been in Operation (Hour)
COMP_E_
OPER
Compressor 3A Oper
Hrs
R
AI13
526
The Number of Hours Compressor E has
been in Operation (Hour)
COMP_F_
OPER
Compressor 3B Oper
Hrs
R
AI14
527
The Number of Hours Compressor F has
been in Operation (Hour)