5370597-JIM-D-1019
Johnson Controls Ducted Systems
31
If the demand for cooling from the space/return is satisfied, the
economizer output will modulate to minimum position and the
compressor outputs will be de-energized as long as their
minimum run timers have expired.
Power Exhaust
Setpoints
a. Economizer Enable ON
b. Power Exhaust Enable ON
c. Modulating Power Exhaust OFF
d. Exhaust VFD Installed OFF
e. Building Pressure Sensor Enabled OFF
f. Econo Damper Position For Exh Fan ON Percent
g. Econo Damper Position For Exh Fan OFF Percent
Inputs
No inputs are present for non-modulating power exhaust.
Outputs
a. 2-10 VDC from ECON on Economizer Expansion module
b. 24 VAC from EX-FAN to energize exhaust fan on
Economizer Expansion module
Operation
Operation details include:
a. Compares economizer output to the Economizer Damper
Position For Exhaust Fan On and OFF.
b. Energizes exhaust fan when economizer output is above
Economizer Damper Position For Exhaust Fan On.
c. De-energizes exhaust fan when economizer output is
below the Economizer Damper Position for Exhaust Fan
OFF