IOM4710 Input/Output Module Installation Instructions

2

Mount the IOM controller on an even surface 
whenever possible.

Use shims or washers to mount the unit securely 
on the mounting surface.

Mount the IOM controller in areas free of corrosive 
vapors and observe the environmental limitations 
listed in the 

Technical Specifications

 section. 

Do not mount the IOM controller on surfaces that 
are prone to vibration, such as duct work, or in 
areas where electromagnetic emissions from other 
devices or wiring can interfere with IOM controller 
communication.

Allow sufficient space for cable and wire 
connections (minimum of 51 mm [2 in.] in each 
direction).

On panel or enclosure mount applications, observe the 
following guidelines:

Do not install the IOM controller in an airtight 
enclosure.

Mount the IOM controller so that the enclosure wall 
or the transformer does not obstruct ventilation of 
or radiate heat into the IOM controller housing. 

Wall Mount Applications

Use the holes in the mounting clips for wall mount 
applications.

To mount the IOM controller on a wall or other vertical 
surface:

1.

Ensure that the bottom mounting clip(s) are pulled 
outward and snapped firmly into the extended 
position and that the top clip is securely installed 
(Figure 2).  

Figure 1: IOM4710 Controller Physical Features and Wiring Terminals

FAULT

POWER

ON

ADDRESS

ADDRESS Ø = ALL OFF

CO

M

HO

T

OU

T

 4

OC

OM

 4

OU

T

 5

OC

O

M

 5

OU

T

 6

OC

OM

 6

OU

T

 7

OC

O

M

 7

OU

T

 2

OC

OM

 2

OU

T

 1

OC

OM

 1

OU

T

 3

OC

OM

 3

OU

T

 8

OC

OM

 8

OU

T

 9

OC

OM

 9

UNIVERSAL

+

15V

IN

1

IC

O

M

1

IN

2

IC

O

M

2

+

15V

IN

3

IC

O

M

3

IN

4

IC

O

M

4

+

15V

IN

5

IC

O

M

5

IN

6

IC

O

M

6

IN

7

IC

O

M

7

IN

8

IC

O

M

8

BINARY

EOL

O
N

Status

LEDs

Device

Address

DIP

Switches

EOL

Switch

FI

G

:I

O

M

4

7

1

0_

cv

r

+

-

CO

M

+

-

CO

M

15

V

SA

PW

R

FC

SA

Binary

Outputs

Configurable

Outputs

Analog

Outputs

24 VAC

Power Terminal

Universal

Inputs

Binary

Inputs

SA/FC Bus

Terminals

SA/FC Bus

Port

Содержание IOM4710

Страница 1: ...dels that are UL Listed UUKL 864 Listed Smoke Control Equipment See Repair Information on page 10 for UUKL 864 Listed IOM4710 models For Metasys system smoke control applications you must refer to the...

Страница 2: ...the enclosure wall or the transformer does not obstruct ventilation of or radiate heat into the IOM controller housing Wall Mount Applications Use the holes in the mounting clips for wall mount applic...

Страница 3: ...hinge tabs cover onto the top of the hinge slots base See Figure 5 Note Do not fully insert the tabs into the slots If the tabs are fully inserted into the slots the cover hinge may not allow the cov...

Страница 4: ...troller before finishing wiring and checking all wiring connections Short circuits or improperly connected wires may result in permanent damage to the equipment IMPORTANT User copper conductors only M...

Страница 5: ...4 20 mA input signal Internal 100 ohm load Impedence enabled disabled by jumper B Analog Input Resistive Mode Accepts 0 600k ohm input signal Internal 12 V 15k ohm Pullup RTD 1k Nickel Johnson Contro...

Страница 6: ...n activated 30 VAC maximum output voltage 40 mA minimum load current 0 5 A maximum output current or 1 3 A at 25 duty cycle or Maximum 6 cycles per hour with M9220 BGx 3 C OCOM n The signal common for...

Страница 7: ...on network RJ 12 6 position modular connector 30 5 m 100 ft maximum length phone cord SA Bus1 2 COM Provides SA Bus communication network Daisy chained 366 m 1 200 ft maximum length 0 6 to 1 5 mm 18 t...

Страница 8: ...ons Table 2 Wire Gauge and Length Guidelines Guideline Cable Size Maximum Length Assumptions A 1 5 mm 18 AWG 457 2 m 1 500 ft 100 mV maximum voltage drop 0 8 mm 20 AWG 297 2 m 975 ft 0 6 mm 22 AWG 182...

Страница 9: ...the Binary Outputs and power must come from one or more external sources Do not wire the load directly to the OUTx and COMx terminals Wire one side of the load to the source and the other side of the...

Страница 10: ...Steady Power is supplied by primary voltage Fault Red Off Steady Blink 2 Hz Download or startup in progress not ready for normal operation Off Steady No faults On Steady Device fault or no application...

Страница 11: ...olution and 200 mV in 0 10 VDC applications Mounting On flat surface with screws on three mounting clips or a single 35 mm DIN rail Dimensions Height x Width x Depth 180 x 127 x 58 7 1 16 x 5 x 2 1 4...

Страница 12: ...odule Installation Instructions 12 Metasys and Johnson Controls are registered trademarks of Johnson Controls Inc All other marks herein are the marks of their respective owners 2010 Johnson Controls...

Отзывы: