Johnson Controls IOM3731-0A Скачать руководство пользователя страница 10

Setup and Adjustments

Setting the device address

Metasys

 expansion modules are master devices

on MS/TP (SA or FC) buses. Before operating an

expansion module on a bus, you

 must

 set a valid

and unique device address for each expansion

module on the bus. You set an expansion module's

device address by setting the positions of the

switches on the DIP switch block at the top of the

expansion module . Device addresses 4 through

127 are the valid addresses for these expansion

modules.

The DIP switch block has eight switches numbered

128, 64, 32, 16, 8, 4, 2, and 1. Switches 64 through 1

are device address switches. Switch 128 must be set

to off for all hard-wired SA and FC bus applications.

Switch 128 must be set to OFF for all hard-wired SA

and FC Bus applications

Figure 9: Device address DIP switch block set to

address 21

Note: 

 

Metasys

 controllers ship with switch 128

ON and the remaining address switches OFF

rendering the controllers wired subordinate

devices, which do not operate on MS/TP buses,

but do not interfere with bus operation. Set

a valid and unique device address on the

expansion module before applying power to

the expansion module on the bus.

To set the device addresses on 

Metasys

expansion modules, complete the following

steps:

1. Set 

all

 of the switches on the address DIP

switch block (128 through 1) to OFF.

2. Set one or more of the seven address switches

(64 though 1) to ON, so that the sum of the

switch numbers set to ON equals the intended

device address, and ensure that switch 128

remains set to OFF.

Note: 

To do this, set the highest number switch

that is less than or equal to the intended device

address to ON. Then continue setting lower

numbered switches until the total equals the

intended address. For example, if the intended

device address is 21, set switches 16, 4, and 1 to

ON (16+4+1= 21) and all other switches to OFF.

3. Set a unique and sequential device address for

each of the expansion modules connected on

the SA or FC bus starting with device address 4.

Note: 

 To ensure the best bus performance,

set sequential device addresses with no gaps

in the device address range (4, 5, 6, 7, 8, 9, and

so on). The expansion modules do 

not

 need

to be physically connected on the bus in their

numerical device address order.

4. Write each expansion module's device address

on the white label below the DIP switch block

on the expansion module's cover.

The following table describes the FC bus and SA bus

device addresses for Johnson Controls MS/TP com-

munications bus applications.

Table 6: SA/FC bus device address descriptions

Device Address Use on Descriptions

0

(Switch 128 Off)

Reserved for FC Bus Supervisory Controller (not

for use on controllers or expansion modules).

1-3

(Switch 128 Off)

Reserved for peripheral devices (not for use on

controllers or expansion modules).

4-127

(Switch 128 Off)

Used for MSTP master devices (controllers and

expansion modules) that are hardwired to an

SA bus or FC bus.

Removing the expansion module
cover

Important: 

Electrostatic discharge can damage

expansion module components. Use proper

electrostatic discharge precautions during

installation, setup, and servicing to avoid

damaging the expansion module.

Important: 

Disconnect all power sources to

the expansion module before removing the

cover and changing the position of any jumper

or the EOL switch on the expansion module.

Failure to disconnect power before changing

a jumper or EOL switch position can result in

damage to the expansion module and void any

warranties.

IOM3731-0A Expansion Input/Output Installation Guide

10

Содержание IOM3731-0A

Страница 1: ...easonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area may cause harmful interference in which case...

Страница 2: ...nsion module Ensure the mounting surface can support the expansion module DIN rail and any user supplied enclosure Mount the expansion module horizontally on 35 mm 1 4 in DIN rail whenever possible Mount the expansion module in the proper mounting position Figure 2 Mount the expansion module on a hard even surface whenever possible in wall mount applications Use shims or washers to mount the expan...

Страница 3: ...om mounting clips inward up to secure the controller on the DIN rail To remove the controller from the DIN rail pull the bottom mounting clips out to the extended position and carefully lift the controller off the DIN rail Wall mount applications To mount the controller directly on a wall or other flat vertical surface complete the following steps 1 Pull the two bottom mounting clips outward and e...

Страница 4: ...mportant Electrostatic discharge can damage controller components Use proper electrostatic discharge precautions during installation setup and servicing to avoid damaging the controller For detailed information on configuring and wiring an MS TP Bus FC bus and SA bus refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 Terminal blocks and bus ports See Figure 1 for terminal block ...

Страница 5: ...nding on which bus the expansion module is operating on The SA FC bus port is connected internally to the SA FC bus terminal block See for more information The SA FC bus port pin assignment is shown in Figure 6 Figure 6 Pin number assignments for sensor SA bus and FC bus ports on expansion modules Supply power terminal block The 24 VAC supply power terminal block is a gray removable 3 terminal plu...

Страница 6: ...ro Series Wireless Field Bus System Product Bulletin LIT 12012320 For more information on the ZFR 1800 Wireless Field Bus system refer to the ZFR1800 Series Wireless Field Bus System Product Bulletin LIT 12011336 Terminal Wiring Guidelines Functions Ratings and Requirements Input and output wiring guidelines The following table provides information and guidelines about the functions ratings and re...

Страница 7: ...es for low voltage 30 V inputs and outputs Guideline Wire size Gauge and type Maximum cable length and type Assumptions 1 0 mm 18 AWG stranded copper 457 m 1 500 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wire 0 6 mm 22 AWG stranded copper 183 m 600 ft twisted wire A 0 5 mm 24 AWG stranded copper 107 m 350 ft twisted wire 100 mV maximum voltage drop Depending on cable and t...

Страница 8: ...size and cable length requirements for the SA and FC buses Table 4 Communications bus and supply power terminal blocks functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements Recommended cable type FC or SA Bus Communications COM Signal Reference Common for FC or SA Bus communications FC BUS or SA BUS SHLD or SAPWR SHLD on FC Bus...

Страница 9: ...Table 5 Termination details Type of device Type of Input Output Termination diagrams Dry Contact Binary Input BI Incremental Control to Actuator Switch Low Externally Sourced BO 24 VAC Binary Output Switch Low Externally Sourced BO 24 VAC Binary Output Switch High Externally Sourced BO Incremental Control to Actuator Switch High Externally Sourced BO IOM3731 0A Expansion Input Output Installation ...

Страница 10: ...r numbered switches until the total equals the intended address For example if the intended device address is 21 set switches 16 4 and 1 to ON 16 4 1 21 and all other switches to OFF 3 Set a unique and sequential device address for each of the expansion modules connected on the SA or FC bus starting with device address 4 Note To ensure the best bus performance set sequential device addresses with ...

Страница 11: ... the controller is not a terminating device on the bus set the EOL switch to Off When a controller is connected to power with its EOL switch set to ON the amber EOL LED on the controller cover is lit Commissioning You commission expansion modules with the Controller Configuration Tool CCT software using NxE Passthru Bluetooth with BTCVT through Mobile Access Portal MAP Gateway at version 4 2 or ab...

Страница 12: ... AS XFR050 0 Power Transformer Class 2 24 VAC 50 VA Maximum Output no enclosure AP TBK4SA 0 Replacement SA Bus Terminal Blocks 4 Position Brown Bulk Pack of 10 AP TBK4FC 0 Replacement FC Bus Terminal Blocks 4 Position Blue Bulk Pack of 10 AP TBK3PW 0 Replacement Power Terminal Blocks 3 Position Gray Bulk Pack of 10 WNC1800 ZFR182x Pro Wireless field Bus System This system is used for installations...

Страница 13: ...er 4 Wire and 3 Wire Pluggable Screw Terminal Blocks Mounting Horizontal on single 35 mm DIN rail mount preferred or screw mount on flat surface with three integral mounting clips on expansion module Housing Enclosure material ABS and polycarbonate UL94 5VB self extinguishing plenum rated Protection Class IP20 IEC529 Dimensions Height x Width x Depth 150 mm x 164 mm x 53 mm 5 7 8 in x 6 1 2 in x 2...

Страница 14: ...SON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA For more contact information refer to www johnsoncontrols com locations 2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com ...

Отзывы: