System Security
Product Overview
15
IFI-WS Installation and Operation Manual – P/N LS10050-000JC-E:A 12/11/2014
1.8 System Security
1.8.1 Software Security
Workstation software security is as follows:
•
Secure Windows (Control/Command Key Lockouts)
- This type of lockout disables the
workstation’s keyboard keys that are used to access Windows programs that are not part of the
workstation software applications. For example, keyboard key combinations can be used to
shut-down or restart the workstation and for switching between software applications. The PC
Monitor’s Secure Windows selection disables those types of operations.
•
User Security Options
- User accounts can be created with differing levels of access to the
Intelligent Fire Integrator system. The user’s security option choice determines which functions are
visible or selectable. For example, some user accounts may not have permission to exit the
workstation software application. Refer to the
Intelligent Fire Integrator
Configuration Tool
Installation & Operation Manual
(P/N 53380)
for additional information.
1.8.2 UL 2572 Security Levels
The IFI-WS meets the UL 2572 security levels stated below:
1.9 Field Programmable Settings
Table 1.4 Security Levels
Level Type
Level
Communication Security
1
Stored Data Security
0
Access Control Security
2
Physical Security
1
Audit Control Security
0
Table 1.5 UL 864 Field-programmable Settings
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard
for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to
specific values or not used at all as indicated below.
Program feature or option
Permitted in UL 864 (Y/N)
Possible Settings
Settings permitted in UL 864
Remote resetting and
silencing of a fire alarm
control unit from other than
the protected premises
(ref: NFPA 72-2007
6.8.2.8)
No
Security Levels
• Administrator
• User with Point Control
• User with Client Control
• Default User
Controlling Fire Panels
over Ethernet connection
No