Product Overview
IP Requirements
12
IFI-WS Installation and Operation Manual – P/N LS10050-000JC-E:A 12/11/2014
1.6 IP Requirements
1.6.1 IP Port Settings
The following IP ports must be available to the IFI-WS:
1.6.2 Bandwidth Usage
The worst-case sustained bandwidth values are described below:
Table 1.2 IP Port Settings
Port
Type
Direction
Purpose
25
TCP
Out
SMTP
123
UDP
Both
SNTP
2004
TCP
N/A
(Internal) Workstation Plug-in Access
2014
TCP
Out
Connection to DACR Gateway
2017
TCP
Out
Connection to NFN Gateway
2029
TCP
Out
Workstation Output Appliances (Signs)
4016
TCP
In
Database Import/Export
Table 1.3 Bandwidth Usage
Worst Case Sustained
Bandwidth
No. Gateways
Bandwidth
Typical
200
3,360 Bytes/Sec
26,800 bits/Sec
0.027 Mb/Sec (Approx.)
Maximum
200
+ 50 Audio
617,580 Bytes/Sec
4,940,640 bits/sec
5 Mb/Sec (Approx.)