IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
73
Walk Test
Alter Status
4.6.2 Walk Test Loops Parameters
This screen appears when
LOOPS
is chosen as a parameter at the Walk Test Menu.
Figure 4.10 Walk Test Loops Programming Screen
The chosen settings are displayed (
BASIC,
AUDIBLE
in Figure 4.10), and installed loops will
display with a participation field. The up and down arrow keys on the keypad navigate through the
fields. Choose
YES
for participation,
NO
for no participation, using the
NEXT SELECTION
(+)/
PREVIOUS SELECTION
(-) keys on the keypad.
Soft Keys
START TEST:
Press to begin Walk Test using the chosen parameters. Once Walk Test has begun,
this soft key becomes
ABORT
, and can be pressed at any time to exit Walk Test.
NEXT
TEST:
This key appears for Advanced Walk Tests when the panel parameter is chosen at the
Walk Test Menu Screen. Refer to Figure 4.13 for the location of this key. Press it to progress from
one activation to the next, latching the new point and releasing the latch on the previous point.
4.6.3 Advanced Walk Test Activation
Figure 4.11 Walk Test Devices Programming Screen
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A
F R I S E P 2 4 , 2 0 0 4
W A L K T E S T
S E T T I N G S : B A S I C , A U D I B L E , L O O P S
L 1 : N O
L 2 : N O
L 3 : Y E S
L 4 : N O
L 5 : N O
L 6 : Y E S
L 7 : N O
L 8 : N O
L 9 : Y E S
L 1 0 : N O
S T A R T T E S T
B A C K
Once the
START TEST
soft key has
been pressed and the test begun, this
message changes to
ABORT
L A K E V I E W G E N E R A L H O S P I T A L
S Y S T E M N O R M A L
1 0 : 2 2 : 3 4 A
F R I S E P 2 4 , 2 0 0 4
W A L K T E S T S E L E C T
S E T T I N G S : B A S I C , A U D I B L E , D E V I C E S
D E V I C E : L 0 1 D 0 0 5
N E X T P O I N T
A C C E P T
P R E V I O U S P O I N T
B A C K
Содержание IFC-3030
Страница 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Страница 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Страница 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Страница 84: ...84 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Service Screens Application Corrupt Screen...
Страница 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Страница 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Страница 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Страница 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Страница 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Страница 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Страница 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...
Страница 156: ...Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53201 www johnsoncontrols com Release C Printed in U S A...