40
IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
Program
Point Program
ACCEPT:
Press to save entries made on this screen and return to the Detector Point Programming
screen.
Detector Point Programming (2)
Press the
MORE
soft key on the Detector Point Programming screen to display this screen.
Figure 3.26 More Detector Point Programming (2) Screen
Soft Keys
CUSTOM
ACTION
MESSAGE:
Displays the custom action message number (a value of one
through 100). The default value is 0 (no message). Press this soft key to progress to the Custom
Action Message screen (Figure 3.27) to view the message or to choose a different message for
viewing when this point activates. (To create a new custom action message, refer to “Custom
Action Message” on page 35.)
ALARM
VERIFICATION:
Press this key to determine the device’s participation in Alarm
Verification. Choosing Yes will set the device participation to the values entered at the Panel
Timers screen (Figure 3.8).
LOCAL
MODE:
Press to toggle between Local Mode (
ON
) or no Local Mode (
OFF
). When there is
a communication loss between the panel and its LCM/LEMs, SLC devices that have been selected
for Local Mode participation (
ON
) will continue to function across all the panel’s SLCs in a limited
manner as follows: input points will activate output points of the same Type Code point type
designations. For example, SLC inputs with“fire” point types will activate SLC outputs with“fire”
point types. Refer to Appendix G, “Type Codes”, on page 133 for type code point types. All SLC
detector types can participate in local mode.
NOTE:
The panel setting
LCM
LOCAL
MODE
must be set to Yes for local mode to work at the
device level.
SENSITIVITY:
Press to proceed to the Detector Sensitivity screen.
WEEKLY
OCCUPANCY
SCHEDULE:
To choose an existing weekly occupancy schedule, press this
soft key to proceed to the Detector Occupancy Schedule screen. Refer to “Weekly Occupancy
Schedule” on page 31 for information on how to set up a schedule.
MULTI-DETECTOR:
This detector can be linked with up to two detectors at other addresses on
the same loop in cooperative multi-detector sensing if entries are made in these fields. The
detectors need not be sequential in their addresses. Refer to the section on Cooperative Multi-
Detector Sensing in Appendix D, “AWACS™ Applications” for a description of this function.
MORE:
Press this soft key to progress to the next detector point programming screen.
D E T E C T O R P O I N T P R O G R A M M I N G
L 0 3 D 1 2 3
C U S T O M A C T I O N M E S S A G E : 0 1 0
A L A R M V E R I F I C A T I O N : O F F
S E N S I T I V I T Y
L O C A L M O D E : O F F
M O R E
W E E K L Y O C C U P A N C Y S C H E D U L E : 1 0
A C C E P T
M U L T I - D E T E C T O R : D 1 0 0 , D 1 0 5
B A C K
Содержание IFC-3030
Страница 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Страница 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Страница 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Страница 84: ...84 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Service Screens Application Corrupt Screen...
Страница 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Страница 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Страница 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Страница 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Страница 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Страница 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Страница 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...
Страница 156: ...Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53201 www johnsoncontrols com Release C Printed in U S A...