IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
105
Abort Switches
Releasing Applications
How to Program a Release End Bell Circuit
The following contains information needed to program a Release End Bell circuit for an SLC or
Panel Circuit output module
.
NOTE:
A releasing circuit with this Type Code requires the following selections: a Releasing
Zone; an output circuit mapped to the same Releasing Zone; Switch Inhibit; Non-Silenceable; No
Walk Test.
Description
An SLC or panel circuit output module to activate an audible or visual device
when releasing devices shut off. Multiple outputs with the
REL
END
BELL
Type
Code can also be mapped to the same Releasing Zone. When all the Releasing
Zone functions are complete, all outputs with the
REL
END
BELL
Type Code
activate at the same time. A
REL
END
BELL
circuit remains on until the system is
reset.
Program
Select an SLC or panel circuit output module to use as a Release End Bell circuit.
While programming the point (refer to the Point Programming section of this
manual for instructions),
1.
Select the
REL
END
BELL
Type Code,
2.
Enter the number of the desired releasing zone into the module’s zone map.
The releasing zone must be fully programmed (refer to “Releasing Zone” on
page 51).
Example
A programming example of a control module programmed as a Release End Bell for
Releasing Zone ZR05.
Figure B.13 Output Module Configured as a Release End Bell Circuit
Type Code
REL
END
BELL
Type Code
RELEASE
CKT
Type Code
RELEASE
CKT
Type Code
REL
AUDIBLE
For example, a module programmed with the
REL
END
BELL
Type Code activates when all releasing functions, such as the
releasing functions programmed for ZR05, shut off.
Output
module
Output
module
ZR05
Monitor
Module
Detector
Detector
Detector
SLC
output
module
SLC
output
module
Содержание IFC-3030
Страница 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Страница 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Страница 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Страница 84: ...84 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Service Screens Application Corrupt Screen...
Страница 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Страница 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Страница 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Страница 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Страница 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Страница 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Страница 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...
Страница 156: ...Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53201 www johnsoncontrols com Release C Printed in U S A...