104
IFC-3030 Programming Manual —
P/N 52025:C 08/05/2005
Releasing Applications
Abort Switches
How to Program a Second Shot Switch
The following contains information needed to program a Second Shot switch for a monitor module
.
NOTE:
The Second Shot switch can only be used with the MAN REL DELAY Type Code
Description
A monitor module—connected to a UL-listed manual station (such as the NBG-12LRA)—used as
for a second release of agents. A Second Shot switch overrides a Delay Timer programmed to the
same Releasing Zone.
Program
Select a monitor module for the manual release function. While programming the module (refer to
“Module Point” on page 43 for instructions)
1.
Select the
SECOND
SHOT
Type Code.
2.
Enter the number of the desired releasing zone into the module’s zone map. The releasing
zone must be fully programmed (refer to “Releasing Zone” on page 51).
Example
A programming example of a monitor module programmed as a MAN REL DELAY switch for the first shot and a
SECOND SHOT switch for the second shot.
Figure B.12 Monitor Module Configured as a Second Shot Switch
With two monitor modules configured as shown above, program releasing zone ZR05 for the
following releasing selections: Delay Time = 15, Abort Switch = ULI, Cross Zone = Y, Soak Time
= 30
ZR05 can be activated in one of two ways, as described in the examples given below.
Example 1: If the detector initiates the alarm, ZR05 activates. Releasing begins after the delay
timer has expired (15 seconds). Releasing will continue for the soak timer duration (30 seconds).
The Second Shot switch can then be activated, and will remain activated for as long as the switch
is held on. Second Shot releasing will end when the switch is no longer held on (behaving like a
tracking function).
Example 2: If the NBG-12LRA (Type Code
MAN REL DELAY
) lever is pulled, the delay timer
begins its 15 second countdown. Releasing will begin after the delay timer has expired, and will
continue for the soak timer duration (30 seconds). The Second Shot switch can then be activated,
and will remain activated for as long as the switch is held on. Second Shot releasing will end when
the switch is no longer held on (behaving like a tracking function).
NBG-12LRA station with
Manual Release lever
ZR05
Detector
Monitor
Module
Monitor
Module
Type Code
MAN
REL
DELAY
SYSTEM
N ORMAL
SYSTEM
ACT IVATED
Type Code
SECOND
SHOT
Second
Shot
Switch
SLC
output
module
SLC
output
module
Содержание IFC-3030
Страница 8: ...Table of Contents 8 IFC 3030 Programming Manual P N 52025 C 08 05 2005...
Страница 64: ...64 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Program Autoprogram Menu...
Страница 78: ...78 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Alter Status Control On Off Point Select...
Страница 84: ...84 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Service Screens Application Corrupt Screen...
Страница 87: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 87 Screens Overview Menu Hierarchy...
Страница 88: ...88 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Menu Hierarchy Screens Overview...
Страница 130: ...130 IFC 3030 Programming Manual P N 52025 C 08 05 2005 CBE Zones and Equations Equations...
Страница 138: ...138 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Type Codes FlashScan Codes...
Страница 146: ...146 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Glossary...
Страница 154: ...154 IFC 3030 Programming Manual P N 52025 C 08 05 2005 Z Z Index...
Страница 155: ...IFC 3030 Programming Manual P N 52025 C 08 05 2005 155...
Страница 156: ...Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53201 www johnsoncontrols com Release C Printed in U S A...