background image

IFC-200 Technical Manual

444

Hardware Installation Section

Technical Bulletin

Issue Date

1293

©

1993 Johnson Controls, Inc.

1

Order No. 444-040

IFC-200 Hardware Installation Procedures

Hardware Installation Procedures

Page

5

General

5

-

Backbox Mounting

5

Power Supplies

6

-

DC Power Output Connections

7

-

AC Power Connections

7

-

Battery Power

7

Output Circuits

8

-

Indicating Appliance Circuits

8

-

Releasing Circuits

8

Standard Relays

9

Remote Printers

9

-

Installation

10

-

Printer Configuration

10

-

PRN-3 Setup Paper Feed Advance

11

-

Keltron Printer Option

12

CRT-1 Configuration

12

-

Function Key Programming

14

Wiring the Signaling Line Circuit

14

-

Isolator Modules

14

-

Monitor Modules

15

-

Control Modules

15

-

Intelligent Detectors

15

-

Device Capacity

15

-

SLC Resistance Measurement

16

-

Isolator Module Operation

20

-

SLC Shield Termination

21

Содержание IFC-200

Страница 1: ...ections 7 Battery Power 7 Output Circuits 8 Indicating Appliance Circuits 8 Releasing Circuits 8 Standard Relays 9 Remote Printers 9 Installation 10 Printer Configuration 10 PRN 3 Setup Paper Feed Adv...

Страница 2: ...ircuit 25 NFPA Style D Initiating Device Circuit 26 Control Module 30 SLC Connections 30 NFPA Style Y Indicating Appliance Circuit 30 NFPA Style Z Indicating Appliance Circuit 30 Indicating Appliance...

Страница 3: ...ocedures 3 Supply Calculations Page 43 AC Branch Circuit 43 Main Power Supply 43 Smoke Detectors 43 Standby Current Load on Batteries 45 Four Wire Detectors 45 Alarm Current Load on Batteries 45 Calcu...

Страница 4: ...4 Hardware Installation IFC 200 Hardware Installation Procedures...

Страница 5: ...The area should be readily accessible with sufficient room to easily install and maintain the panel 3 Locate the top of the cabinet approximately five feet above the floor with the hinge mounting on t...

Страница 6: ...les from the side of the cabinet Do not insert wiring from the back of the cabinet Note the entry locations of primary 120 VAC power and low voltage wiring above CAUTION Damage may occur when removing...

Страница 7: ...0 VAC 50 60 Hz 3 0 amps Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code NEC and or local codes Use 14 AWG or larger wire with 600 volt rating AC Po...

Страница 8: ...t for RELEASE CKT See the Releasing Applications section of the IFC 200 Applications Technical Bulletin in this manual for more information including a list of compatible solenoid valves T B 2 B B B B...

Страница 9: ...elay Connections The PRN 3 Remote Printer provides a hardcopy printout of all status changes within the system and time stamps the printout with the current time of day and date The PRN 3 provides 80...

Страница 10: ...ed for connection to the printer s RS 232 port Refer to the documentation supplied with the PRN 3 for instructions on the printer s menu controls Set the printer s options as listed in Table 1 Table 1...

Страница 11: ...this happens the printer needs to be configured by adding a one inch printer advance selection to the printer s internal setup This selection advances the paper up one inch if the printer does not re...

Страница 12: ...e Set key 13 Press Local Note Current shipments of the PRN 3 have been modified to include this software selection The IFC 200 may also be used with a Keltron printer For more information or to order...

Страница 13: ...hout a keyboard SET 3 DATA BIT 7 BIT8 0 PARITY ON PARITY BIT EVEN STOP BIT 1 EMULATION T101 SET 4 CURSOR UL CURSOR BLINK HERE IS TIME OFF FREQ 60 Note To change the HERE IS parameter press the Enter k...

Страница 14: ...ogramming function keys use the Enter key located on the number pad The IFC 200 communicates with intelligent and addressable initiating monitor and control devices through a Signaling Line Circuit SL...

Страница 15: ...lations section of this document and the installation drawings supplied with each device for rating and specification information Table 3 Communications SLC Performance Fault Condition Single Open on...

Страница 16: ...LC to the end of that particular branch as shown in Figure 8 The total DC resistance from panel to branch end cannot exceed 40 ohms 2 Repeat this procedure for all remaining branches Add the lengths o...

Страница 17: ...r cannot exceed 40 ohms Measure the loop pair by completing the following steps 1 Disconnect Loop Out and Return at the control panel 2 Short the two leads of Loop Return 3 Meter Loop Out as shown in...

Страница 18: ...tectors B501BJ Base 1 2 3 4 9 8 7 6 5 ION PHOTO THERM Lo op Add re ss T ype 2 3 1 M500MJ 1 2 3 4 9 8 7 6 5 M500XJ 1 2 3 4 9 8 7 6 5 1 2 3 4 9 8 7 6 5 M500XJ Note M500XJ devices not reguired to meet NF...

Страница 19: ...ectors B501BJ Base 1 2 3 4 9 8 7 6 5 ION PHOTO THERM Loop Address Type 2 3 1 M500MJ 1 2 3 4 9 8 7 6 5 M500XJ 1 2 3 4 9 8 7 6 5 1 2 3 4 9 8 7 6 5 M500XJ Note M500XJ devices not required to meet NFPA St...

Страница 20: ...ea the M500XJ on either end of that section of the SLC will open the SLC thus allowing the other addressable devices on the SLC to continue to communicate For example a fault on Area 2 will not affect...

Страница 21: ...ination in No Conduit Shield Termination in Full Conduit Figure 14 The shield drain wire must be connected to the negative side of the loop Do not allow the shield drain wire or the shield foil to tou...

Страница 22: ...mination point of the conduit run such as a single gang box as illustrated above The conduit cannot be longer than 20 feet If the partial conduit system exceeds 20 feet terminate the SLC shield drain...

Страница 23: ...meeting NFPA Style 7 requirements Note During a fault condition the IFC 200 registers a trouble condition for each zone mapped to the isolated SLC branch Continuation of the SLC T Tapped Branch off t...

Страница 24: ...and 8 The M500MJ includes a magnetic test switch located near the center front of the module Activation of this switch causes an open circuit indication for the indicating appliance circuit The M501MJ...

Страница 25: ...ch for testing the module s electronics and connections to the control panel The M502MJ circuit can be wired as an NFPA Style B or NFPA Style D IDC Initiating Device Circuit The M502MJ occupies one mo...

Страница 26: ...ect the Style D IDC to M502MJ terminals 6 and 9 then 7 and 8 2 Do not loop wire under terminals Break wire run to provide supervision of connections 3 Power to the M502MJ must be externally switched t...

Страница 27: ...Device on SLC SLC Out TB1 TB2 B B B B B B B B NO C NO NC C NO NC C TB3 TB4 TB5 TB6 TX REF RX REF OUT OUT IN IN A B B A B A 24V TB1 5 24V TB1 6 SLC TB6 3 SLC TB6 5 A77 716B Power Supervision Relay End...

Страница 28: ...J IFC 200 To Next Device on SLC SLC Out TB1 TB2 B B B B B B B B NO C NO NC C NO NC C TB3 TB4 TB5 TB6 TX REF RX REF OUT OUT IN IN A B B A B A 24V TB1 5 24V TB1 6 SLC TB6 3 SLC TB6 5 Power Supervision R...

Страница 29: ...Detectors To Next Device On SLC IFC 200 Observe Polarity SLC Figure 20 NFPA Style B Initiating Device Circuit Two Wire T B 1 T B 2 T B 3 B B B B B B B B N C C NO N C C NO N C C 3 9 K ELR resistor mus...

Страница 30: ...device by a 47K 1 2 watt ELR part number R 47K 1 Connect polarized alarm indicating appliances to a single two wire circuit 2 Connect the circuit to M510CJ terminals 6 and 7 See Figure 24 This circui...

Страница 31: ...6 3 SLC TB6 5 Break Off Tabs M510CJ To Next Device on SLC Common Contact Normally Closed Contact 1 2 3 4 5 6 IFC 200 Normally Open Contact FIG2 16 Figure 23 M510CJ Control Module Form C Relay To confi...

Страница 32: ...TB2 B B B B B B B B N O C N O N C C N O N C C TB3 TB4 TB5 TB6 TX REF RX REF OUT OUT IN IN A B B A B A 24V TB1 5 24V TB1 6 SLC TB6 3 SLC TB6 5 CAUTION Do not loop wiring under any terminals Break wire...

Страница 33: ...24V TB1 6 SLC TB6 3 SLC TB6 5 CAUTION Do not loop wiring under any terminals Break wire run to maintain supervision A77 716B Power Supervision Relay 24 VDC Indicating A ppliances 1 2 3 4 9 8 7 6 5 UL...

Страница 34: ...ctory preset with address 00 Set the SLC address for the pull station by using a screwdriver to turn the rotary address switches on the back of the unit to the appropriate settings A D D R ES S LO O P...

Страница 35: ...ator connect the RA 400Z positive terminal to B501BJ terminal 3 and the negative terminal to B50BH terminal 1 3 Before installing the appropriate intelligent detector head set the detector s SLC addre...

Страница 36: ...provided into the holes located on the right side edge of the main board 2 Carefully align the pins on the main board with the connector on the option board 3 Press firmly on the option board until it...

Страница 37: ...Trouble M unicipal Box TBL Jum per D isconnect LED D isconnect Sw itch Figure 30 4XTM Transmitter Module Polarities Shown in Activated Positions 1 Push the disconnect switch down to prevent unwanted a...

Страница 38: ...Figure 31 RTM 8 Relay Transmitter Module Table 4 Relay Transmitter Module RTM 8 Specifications Zone Relay Contact Ratings Max Switched Power Switched Current Max Switched Voltage UL Rating Contact Mat...

Страница 39: ...line to terminal 1 on the NR45 24 and the primary Neutral line to terminal 2 All connections between the IFC 200 and the NR45 24 must be made in conduit within 20 ft using 14 AWG wire Do not route 120...

Страница 40: ...lso check the electrolyte level in wet cells at least every 90 days In a wet cells add only distilled water as required Overload protection is provided by means of fuses Installation WARNING Fire Haza...

Страница 41: ...ing FIG2 25 1 2 3 6 5 4 7 8 9 0 ABC DE F GHI JKL MNO PRS TUV WXY Q Z ENTER DET MOD 1 2 3 4 NR45 24 GC12550 12 VDC 55 AH Battery GC12550 12 VDC 55 AH Battery 120 VAC 50 60 H z Prim ary Power Source Hot...

Страница 42: ...42 Hardware Installation IFC 200 Hardware Installation Procedures...

Страница 43: ...supplied to the system Table 5 AC Branch Circuit Requirements 120 VAC Device Type Number of Devices Current Draw amps Total Current per Device IFC 200 1 X 3 0 3 0 NR 45 24 Charger X 1 0 Sum Column for...

Страница 44: ...nd 6 are resettable smoke detector power Current limitations TB 1 Terminals 1 and 2 1 0 amp TB 1 Terminals 3 and 4 0 5 amp TB 1 Terminals 5 and 6 0 5 amp Terminals 3 and 4 combined with Terminals 5 an...

Страница 45: ...nts of the secondary power source during alarm conditions The total obtained in Table 9 will be used in Table 10 to determine the size of the batteries needed to support five minutes of alarm operatio...

Страница 46: ...72 Auxiliary and 72 Remote Station require 60 hours of standby power followed by five minutes in alarm Batteries installed in a system powered by a generator need to provide at least four hours of st...

Страница 47: ...r length of Style 6 and 7 loops 40 ohms per branch maximum for Style 4 loops 10 000 8 000 4 875 3 225 Belden 9583 12 AWG Belden 9581 14 AWG Belden 9575 16 AWG Belden 9574 18 AWG Untwisted unshielded w...

Страница 48: ...48 Hardware Installation IFC 200 Hardware Installation Procedures Notes Controls Group FAN 444 507 E Michigan Street IFC 200 Technical Manual P O Box 423 Printed in U S A Milwaukee WI 53201...