Section 5: Programming
201-231 – Zone Follower (Zones 1-248)
This output type is assigned to a group of zones and is normally activated, but deactivates when a zone is tripped. Zones are
assigned to this output in the following groups:
Zone Group
Zones
Zone Group
Zones
001
1-8
017
129-136
002
9-16
018
137-144
003
17-24
019
145-152
004
25-32
020
153-160
005
33-40
021
161-168
006
41-48
022
169-176
007
49-56
023
177-184
008
57-64
024
185-192
009
65-72
025
193-200
010
73-80
026
201-208
011
81-88
027
209-216
012
89-96
028
217-224
013
97-104
029
225-232
014
105-112
030
233-240
015
113-120
031
241-248
016
121-128
If multiple zones are enabled, any active zone in that group triggers the output. The PGM will not activate again until all
zones are restored.
[010] PGM Attributes
The following options are used to program the operating characteristics of the main bell and PGM outputs.
[000] Main Bell Mask
This programming section is used to configure the types of audible alarms that trigger the main bell output on the alarm con-
troller. All options are selected by default.
Fire Alarm
ON: Fire alarm ([F] key, Fire zones) activates the main siren.
OFF: Fire alarm does not activate the main siren.
CO Alarm
ON: CO alarm activates the main siren.
OFF: CO alarm does not activate the main siren.
Burglary Alarm
ON: Burglary alarm (Delay, Instant, Interior, Stay/Away, Night, Interior Delay, Instant Stay/Away, Day, 24-hour Burglary) activ-
ates the main siren.
OFF: Burglary alarm does not activate the main siren.
24-Hour Flood Alarm
ON: Main bell activates in the event of a 24-Hour Flood alarm.
OFF: Main bell does not activate in the event of a 24-Hour Flood alarm.
Bell Squawks
ON: Squawks activate the main siren. Bell squawks must be enabled to use the following options:
- 92 -