Instant
Commonly used for perimeter doors and windows, this zone type follows the exit delay. The alarm
is triggered instantly if the zone is tripped after the exit delay expires.
–
Interior
Commonly assigned to interior motion sensors near a point of entry, such as a foyer or hallway,
that must be accessed to reach the keypad. The alarm is activated if the system is armed and a
delay type zone (e.g., front door) is not tripped first, or if the entry/exit timer expires before the
alarm is disarmed. Otherwise, the zone is instant if tripped.
–
Interior Stay/Away
Similar to Interior zone type except that the system bypasses the zone when armed in Stay mode.
Commonly used to activate perimeter zones while permitting free movement throughout the
interior.
–
Delay Stay/Away
Similar to delay 1 except that the zone is bypassed when armed in Stay mode. Commonly used with
motion detectors that cover an entry point.
–
Delayed 24-Hour Fire
This zone is used with smoke detectors and functions similar to the standard fire zone, except
the communicator delays the alarm memory and transmission by 30 seconds. If the alarm is
acknowledged by pressing any key, the siren is silenced and the transmission aborted. If the smoke
detector is not restored after the alarm has been acknowledged, the siren output activates after 90
seconds and another 30-second delay starts. A code is required to silence the alarm. A tamper or
fault causes a fire trouble to log and transmit.
Note:
The supervision options (NC, EOL, DEOL) do not affect the functionality of this zone. The
restored state of this zone type is 5k6, the alarm state is short and the trouble state is open.
–
Standard 24-Hour Fire
This zone is used with smoke detectors. The siren sounds instantly when the smoke detector is
activated. If enabled, the communicator immediately transmits the alarm to the monitoring station.
A tamper or fault of this zone type causes a fire trouble to log and transmit.
Note:
The supervision options (NC, EOL, DEOL) do not affect the functionality of this zone. The
restored state of this zone type is 5.6k, the alarm state is short and the trouble state is open.
–
Instant Stay/Away
Commonly assigned to interior motion sensors. This zone type is bypassed when armed in Stay
mode, but functions like an Instant zone [003] when armed in Away mode.
–
Interior Delay
Commonly assigned to interior motion sensors. When Away armed, this zone type functions like
the Interior zone type. When Stay or night armed, tripping the zone activates entry delay 1. Tripping
this zone during exit delay does not cause the system to arm in Away mode, as tripping a regular
Delay type zone does.
–
Day Zone
Commonly used in areas where immediate notification of entry is desired. When disarmed, tripping
this zone activates the keypad buzzer but does not log or report the event. When armed, tripping
this zone activates the siren then logs and reports the event.
Note:
An alarm during exit delay causes the siren to activate and remain on when exit delay
expires.