[701]-[716] Placement Test Wireless Keypads 1-16
Test each enrolled wireless keypad (LCD keypads only).
Two test results are provided:
• 24-hour: Average status results received during a 24-hour period.
• Now: Signal status results of the current test.
During testing, the Ready and Armed LED's flash to indicate data is being received. A flashing
Trouble LED indicates RF interference. The following status indicators may be displayed:
Table 24: Table 19 Wireless Device Status Indications
Keypad
Status
Strong
Strong signal strength
Good
Good signal strength
Poor
Poor signal strength
1-Way
The device is operating in 1-way mode only. The
alarm panel cannot configure or control the
device
Not Test
Displayed as the Now result if no test was
performed.
None
Always displayed as the 24-hour result when
testing wireless keys.
[912] Soak Test
This feature is used to diagnose false alarms. After a false alarm has occurred on a zone, Soak Test
mode impedes any audible alarm conditions or additional false alarm reporting. A record of the
false alarm is stored for diagnostic purposes.
[000] – Soak Test Duration
This option is used to program the length of time the system remains in soak test. The default is 14
days.
[001]-[128] Zone Soak Test
Soak test can be performed on individual zones. The zone remains in soak test, regardless of the
status of the system, until the soak test timer has expired. If the system is armed when the timer
expires, the zones are removed from soak test when the system is disarmed.
No communications occur for events from a zone in soak test, with the exception of low battery and
low battery restore events and faults generated by low sensitivity in a smoke detector.
A message indicating that the zone is in soak test is displayed when scrolling left or right in the
base disarmed keypad menu.
Note:
Soak test is not applied to temperature detector events if it is enabled.
[982] Battery Settings
[000] – Panel Battery Settings
01 – When disabled, the panel battery is charged at 400mA. When enabled, the battery is charged at
700mA.
[010] – High Current Output Battery
Enables and disables the high-current battery charge option for HSM2204 1-4.
157
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual