8 - Fire Bell Continues
ON: For all Fire type alarms, the siren sounds until an access code is entered to silence the alarm or
disarm the system regardless of the time programmed for bell timeout.
OFF: For all Fire type alarms, the siren sounds for the length of Bell Timeout or until an access code
is entered.
Note:
Must be disabled for ULC installations.
[015] System Option 3
1 - [F] Key Enabled
ON: Pressing and holding the [F] key for 2 seconds triggers a Fire alarm.
OFF: The [F] key does not sound or report an alarm when pressed.
Note:
Use only for residential fire installations.
2 - [P] Key Enabled
ON: When a valid [P] key alarm is generated, the keypad buzzer emits a series of 3 beeps to
acknowledge the alarm and the siren sounds for the length of bell timeout.
OFF: When a valid [P] key alarm is generated, the keypad buzzer and the siren are silent, but the
alarm is still transmitted (if programmed).
Note:
Fire, Medical, and Panic key transmissions follow the partition 1 alarm/restore call
direction options (Fire, Medical, and Panic key). The Fire, Medical, Panic keys operate even if
keypad blanking and keypad lockout are active.
3 - Quick Exit
ON: When the system is armed, users may enter the [*][0] command to temporarily bypass a single
Delay 1 or Delay 2 zone to exit the premises. Only one delay zone may be activated. Activity on
another delay zone initiates the appropriate alarm sequence. If the delay zone is still open two
minutes after the [*][0] command is entered, entry delay is initiated. If armed in the Stay mode, the
automatic bypass on Stay/Away zones remains.
OFF: When the system is armed, users can not perform a quick exit using [*][0].
4 - Quick Arming /Function Key
ON: [*][0] arming and Stay/Away function keys may be used to arm the system without the entry of
a valid access code.
OFF: [*][0] arming is not permitted. All arming functions require the entry of an access code to
activate (including Stay/Away keys).
5 - Not Used
6 - Master Code Not User Changeable
ON: The master code (access code 01) may not be changed by the user and may only be
programmed in Installer Programming.
OFF: The master code may be programmed by the user using the [*][5][Master Code] command.
The master code may also be programmed in Installer Programming.
7 - Telephone Line Monitor Enable
ON: The TLM function is active and the system indicates a trouble condition when using the [*][2]
View Trouble Conditions command.
OFF: The TLM function is deactivated and telephone line troubles are not indicated by the system.
Note:
Must be ON for UL/ULC listed installations.
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual
114