Timed Output
Latching
Follow Alarm
PGM Output
OFF
OFF
OFF
ON upon zone opening
(including tamper and
fault), OFF upon zone
closing
OFF
OFF
ON
ON upon zone alarm,
OFF upon bell cut-off
or alarm silenced
OFF
ON
OFF
ON upon zone
opening, OFF upon
valid code
OFF
ON
ON
ON upon zone alarm,
OFF upon valid code
ON
OFF
OFF
ON upon zone
opening, OFF upon
PGM timer expires
ON
OFF
ON
ON upon zone alarm,
OFF upon PGM timer
expires
ON
ON
OFF
ON upon zone
opening, OFF upon
valid code
ON
ON
ON
ON upon zone alarm,
OFF upon valid code
201 - 216 Zone Follower Zones 1-128
01 - True Output/Inverted
ON: deactivated during normal operation. Activated when triggered.
OFF: activated during normal operation. Deactivated when triggered.
02 - Timed Output
ON: output remains active until the PGM output timer expires.
OFF: output remains active until an access code has been entered.
09-16 – Zone Terminals 1-8
ON: zones associated with terminals 1-8 are enabled for zone follower operation.
OFF: zones are not enabled for zone follower operation.
[011] PGM Configuration Options
This section is used to configure PGM types that offer multiple options.
[001]-[164] Select PGM
The following options may be selected for each PGM:
Zone Follow PGM By Zone
This option is used to specify the zone that PGM type 200 follows. Enter 001-128 to select zone
1-128.
PowerSeries Neo HS2016/HS2016-4/HS3032/HS2064/HS2064 E/HS2128/HS2129 E Alarm Controller Reference
Manual
110