• Transport the FX-PCV controller in the original container to minimize vibration and shock damage
to the FX-PCV controller.
• Do not drop the FX-PCV controller or subject it to physical shock.
Parts included
• One FX-PCV18 Series controller with removable N2/FC bus terminal block
• One installation instructions sheet
• Two 6.35 mm x 6.35 mm (1/4 in. x 1/4 in. ) brass fittings
• One self-drilling No. 10 x 25 mm (1 in.) screw
• Two 12-in. (30.48 cm.) pieces of flexible tubing
• One controller/sensor Y cable adapter
• One 8-pin to 6-pin single-socket cable adapter
Note:
Remove the cap plug from the TSTAT port of the controller and save for future use. The
cap plug is used on existing sensor ports that are no longer used.
Materials and special tools needed
Note:
You may not require all the materials listed for your controller installation.
• Several 6 mm (1/4 in.) female spade terminals for input and output wiring and crimping tool or
spade mounted terminal blocks
• Small straight-blade screwdriver for securing wires in the terminal blocks
• 8 mm (5/16 in.) wrench or 10 mm (3/8 in.) 12-point socket to tighten the square coupler bolt
• Several shims or washers to mount the FX-PCV
• Power screwdriver, 100 mm (4 in.) extension socket, punch, drill, and 3.5 mm (9/64 in.) drill bits to
mount the FX-PCV
• Pliers to open and close the damper
• Required length of 3.97 mm (5/32 in.) ID pneumatic tubing and barbed fittings
Mounting
Observe these guidelines when mounting an FX-PCV:
Important:
When the air supply to the VAV box is below 10°C (50°F), make sure that any
condensation on the VAV box, particularly on the damper shaft, does not enter the FX-
PCV electronics. Mount the FX-PCV vertically above the damper shaft to allow any shaft
condensation to fall away from the FX-PCV. Additional measures may be required in some
installations.
• Ensure the mounting surface can support the FX-PCV and any user-supplied enclosure.
• Mount the FX-PCV on a hard, even surface whenever possible.
• Use shims or washers to mount the FX-PCV securely and evenly on the mounting surface.
• Mount the FX-PCV in an area free of corrosive vapors that matches the ambient conditions
specified in the
section.
FX-PCV1826/1832 Programmable VAV Box Controller Installation Instructions
2