FX-PCA3611 Advanced Application

Programmable Controller Installation

Instructions

Application

The FX-PCA3611 Programmable Controller is part of the Facility Explorer

®

 Programmable Controller

(FX-PC) family. The FX-PCA36 Series controllers run pre-engineered and user-programmed

applications and provide the inputs and outputs required to monitor and control a wide variety of

HVAC and other facility equipment.
FX-PCA36 controllers operate on an RS-485 BACnet

®

 MS/TP Bus as BACnet Advanced Application

Controllers (B-AACs) and integrate into Johnson Controls

®

 and third-party BACnet systems.

FX-PCA36 controllers include an integral real-time clock, which enables the controllers to monitor

and control schedules, calendars, and trends, and operate for extended periods of time as stand-

alone controllers when offline from the system network.

Switchable communications protocol

The FX-PCA3611 controllers can communicate using BACnet MS/TP, N2, or wireless Zigbee. By

default, the FX-PC family controllers and network sensors communicate using the standard

BACnet® protocol, based on the ANSI/ASHRAE 135-2004.
The BACnet protocol is a standard for ANSI, ASHRAE, and the International Standards Organization

(ISO) for building controls.
FX-PCG, FX-PCX, and FX-PCV controllers are BTL tested and listed as BACnet Application Specific

Controllers (B-ASCs). FX-PCA field controllers are BTL-listed as BACnet Advanced Application

Controllers (B-AACs). The NS Series Sensors are BTL-listed as BACnet Smart Sensors (B-SSs).
Release 10.1 of the Controller Configuration Tool (CCT) 13.0 can be used to switch the Field Bus

communications protocol in FX-PC Controllers to be either the standard BACnet MS/TP or the N2

protocol. BACnet MS/TP is the default communications protocol for all new controllers. Switchable

communications protocols provide a cost-effective upgrade and modernization path for customers

with existing N2 controllers. 

The Modernization Guide for Legacy N2 Controllers (LIT-12012045)

and the controller-specific documentation provide installation and commissioning support and

include tips for efficient and safe replacement. Refer to the 

N2 Compatibility Options

 chapter of the

Controller Tool Help (LIT-12011147)

 for information about mapping N2 Objects in controllers with

switchable communications protocols. The N2-capable FX-PC controllers can be used as functional

replacements for legacy N2 controllers.
The N2-capable FX-PC controllers:
• have the I/O quantities and characteristics of the FX-PC family controllers
• must be programmed with CCT 13.0 and later, which has programming capabilities that are

similar (but not identical) to HVACPro, GX9100, GPL, and other legacy tools

• support SA Bus devices
• support FX-WRZ wireless sensors from the controller using the FX-WRZ7860 receiver when

configured for BACnet MS/TP communication

The N2-capable FX-PC controllers:
• do not support Zone Bus (for example, TMZ sensors and M100 actuators)
• do not support pass through in the commissioning mode
• do not support remote downloading or commissioning using BACnet routing

Part No. 24-10143-616 Rev D
2019-03-22

(barcode for factory use only)

FX-PCA3611

*2410143616D*

Содержание FX-PCA3611

Страница 1: ...ACnet Smart Sensors B SSs Release 10 1 of the Controller Configuration Tool CCT 13 0 can be used to switch the Field Bus communications protocol in FX PC Controllers to be either the standard BACnet MS TP or the N2 protocol BACnet MS TP is the default communications protocol for all new controllers Switchable communications protocols provide a cost effective upgrade and modernization path for cust...

Страница 2: ...American Emissions United States This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not instal...

Страница 3: ...n an area free of corrosive vapors and observe the ambient conditions requirements in Technical specifications Provide sufficient space around the controller for cable and wire connections easy cover removal and good ventilation through the controller 50 mm 2 in minimum on the top bottom and front of the controller Do not mount the controller on surfaces prone to vibration such as ductwork Do not ...

Страница 4: ...controller from the DIN rail pull the bottom mounting clips out to the extended position and carefully lift the controller off the DIN rail Wall mount applications To mount an FX PCA3611 directly on a wall or other flat vertical surface complete the following steps 1 Pull the two bottom mounting clips outward and ensure they are locked in the extended position as shown in Figure 2 2 Mark the mount...

Страница 5: ...s Overtightening the screws may damage the mounting clips Figure 2 Back of Controller showing extended mounting clips DIN rail channel and mounting dimensions mm in 5 FX PCA3611 Advanced Application Programmable Controller Installation Instructions ...

Страница 6: ...wo 7 FC Bus Terminal Block see FC bus terminal block 8 SA Bus Terminal Block see SA bus terminal block 9 Sensor Port SA Bus RJ 12 6 Pin Modular Jack see Sensor port 10 Binary Input BI Terminal Block Dry Contact Maintained or Pulse Counter Accumulator Mode see Terminal wiring guidelines functions ratings and requirements 11 Universal Inputs UI Terminal Block Can be defined as Voltage Analog Input 0...

Страница 7: ...équipement Important Do not exceed the controller electrical ratings Exceeding controller electrical ratings can result in permanent damage to the controller and void any warranty Important Use copper conductors only Make all wiring in accordance with local national and regional regulations Important Electrostatic discharge can damage controller components Use proper electrostatic discharge precau...

Страница 8: ...s shown in Figure 4 For more information about the FC Bus terminal function requirements and ratings see Table 5 Figure 4 FC bus terminal block wiring Note The FC bus Shield SHLD terminal is isolated and can be used to connect daisy chain the shields for FC bus wiring SA bus terminal block The SA Bus terminal block is a brown removable 4 terminal plug that fits into a board mounted jack Wire the r...

Страница 9: ...ing Converter or the FX ZFR ZFR Pro Wireless Field Bus Router The FC bus port is connected internally to the FC bus terminal block For more information about the FC Bus port functions requirements and ratings see Table 5 The FC bus port pin assignment is shown in Figure 6 Note The MAP Gateway serves as a replacement for the BTCVT which is no longer available for purchase but continues to be suppor...

Страница 10: ... supply power terminal block is a gray removable 3 terminal plug that fits into a board mounted jack on the top right of the controller Wire the 24 VAC supply power wires from the transformer to the HOT and COM terminals on the terminal plug as shown in Figure 7 Do not use the middle terminal on the supply power terminal block See Table 5 for more information about the Supply Power Terminal Block ...

Страница 11: ... in this section for the applicable termination diagrams Table 2 Termination details Type of field device Type of Input Output Termination diagrams Temperature Sensor UI Voltage Input External Source UI Voltage Input Internal Source UI Voltage Input Self Powered UI 11 FX PCA3611 Advanced Application Programmable Controller Installation Instructions ...

Страница 12: ... diagrams Current Input External Source Isolated UI Current Input Internal Source 2 wire UI Current Input Internal Source 3 wire UI Current Input External Source in Loop UI Feedback from EPP 1000 UI FX PCA3611 Advanced Application Programmable Controller Installation Instructions 12 ...

Страница 13: ...ntact Binary Input UI or BI 0 10 VDC Output to Actuator External Source CO or AO 0 10 VDC Output to Actuator Internal Source CO or AO Current Output CO or AO 24 VAC Triac Output Switch Low External Source CO or AO 13 FX PCA3611 Advanced Application Programmable Controller Installation Instructions ...

Страница 14: ... Output Termination diagrams Analog Output Current AO 4 20 mA Output to Actuator AO 4 20 mA Output to Actuator AO Incremental Control to Actuator Switch Low Externally Sourced BO FX PCA3611 Advanced Application Programmable Controller Installation Instructions 14 ...

Страница 15: ... Output Switch High Externally Sourced BO Incremental Control to Actuator Switch High Externally Sourced BO Network Stat with Phone Jack Fixed Address 199 SA Bus Note The bottom jack J2 on the TE 700 and TE 6x00 Series Sensors is not usable as a zone bus or an SAB connection 15 FX PCA3611 Advanced Application Programmable Controller Installation Instructions ...

Страница 16: ...guidelines for determining proper wire sizes and cable lengths In addition to the wiring guidelines in Table 3 observe these guidelines when you wire controller inputs and outputs Run all low voltage wiring and cables separate from high voltage wiring All input and output cables regardless of wire size or number of wires should consist of stranded insulated and twisted copper wires Shielded cable ...

Страница 17: ...e 0 10 VDC 10 VDC maximum input voltage Internal 75k ohms pull down See Guideline A in Table 4 Analog Input Current Mode 4 20 mA Internal 100 ohms load impedance See Setting the Input Jumpers Note A current loop fail safe jumper must be in the Enable position to maintain a closed 4 to 20 mA current loop See UI current loop jumpers See Guideline B in Table 4 Analog Input Resistive Mode 60 600k ohms...

Страница 18: ...se Counter Accumulator Mode 0 01 second minimum pulse width 50 Hz at 50 duty cycle Internal 18 V 3k ohms pull up BINARY Inputs ICOMn Binary Input Common for all Binary Input IN terminals Note All Binary ICOMn terminals share a common which is isolated from all other commons See Guideline A in Table 4 ANALOG Outputs OUTn Analog Output Voltage Mode 0 10 VDC 10 VDC maximum output voltage 10 mA maximu...

Страница 19: ...al points OUTn Binary Output 24 VAC Triac Class 2 24 V 500 mA External Power Source Connects OUTn to OCOMn when activated External Power Source Requirements 30 VAC maximum output voltage 0 5 A maximum output current 1 3 A at 25 duty cycle 40 mA minimum load current BINARY Output OCOMn Binary Output Common for OUTn terminal Note Each Binary Output Common terminal OCOMn is isolated from all other co...

Страница 20: ...0 ft twisted wire 0 8 mm 20 AWG stranded copper 137 m 450 ft twisted wire 0 6 mm 22 AWG stranded copper 91 m 300 ft twisted wire B 0 5 mm 24 AWG stranded copper 61 m 200 ft twisted wire 100 mV maximum voltage drop Depending on cable and the connected input or output device you may have to define an offset in the setup software for the input or output point C See Figure 8 to select wire size gauge ...

Страница 21: ...ring and cables separate from high voltage wiring All SA and FC bus cables regardless of wire size should be twisted insulated stranded copper wire Shielded cable is strongly recommended for all SA and FC bus cables Refer to the FX PC Series Controllers MS TP Communications Bus Technical Bulletin LIT 12011670 for detailed information regarding wire size and cable length requirements for SA and FC ...

Страница 22: ...ire are one twisted pair and the COM and SA PWR are the second twisted pair of wires FC BUS Port FC BUS RJ 12 6 Position Modular Connector provides FC Bus Communications FC Bus Signal Reference and 15 VDC Common 15 VDC 180 mA Power for Bluetooth Commissioning Converter Bluetooth Commissioning Converter retractable cable or 24 AWG 3 pair CAT 3 cable or above Sensor Port SENSOR RJ 12 6 Position Modu...

Страница 23: ...lying power to the controller on the bus To set the device addresses on FX PCA controllers complete the following steps 1 Set all of the switches on the address DIP switch block 128 through 1 to OFF 2 Set one or more of the seven address switches 64 though 1 to ON so that the sum of the switch numbers set to ON equals the intended device address Set the highest number switch that is less than or e...

Страница 24: ...ship with switch 128 ON and the remaining address switches off rendering the controllers wired subordinate devices which do not operate on MS TP buses 4 to 127 Switch 128 ON Valid for MS TP Master controllers on wireless FC Buses only Note Do not connect a controller with switch 128 ON to an active hard wired SA or FC bus When a controller with switch 128 ON and a device address from 4 to 127 is c...

Страница 25: ... controller before you remove the cover and change the position of any jumper or the EOL switch on the controller Failure to disconnect power before changing a jumper or EOL switch position can result in damage to the controller and void any warranties The controller cover is held in place by four plastic latches that extend from the base and snap into slots on the inside of the housing cover To r...

Страница 26: ... the controller must be set as a terminating device on the bus Note For detailed information regarding EOL termination rules and EOL switch settings on FC buses refer to the MS TP Communications Bus for the BCPro System Technical Bulletin LIT 12011908 or FX PC Series Controllers MS TP Communications Bus Technical Bulletin LIT 12011670 3 If the controller is a terminating device on the FC bus set t...

Страница 27: ... Figure 10 Note Current Loop Jumpers are not included with the FX PCA3611 OA Asia only model Figure 12 Current loop jumper positions Set the current loop jumper to the Enabled position Figure 12 to connect an internal 100 ohms resistor across the UI terminals which maintains the 4 20 mA current loop circuit even when power to the controller is interrupted or off Important Current loop jumpers must...

Страница 28: ...controllers Note The MAP Gateway serves as a replacement for the BTCVT which is no longer available for purchase but continues to be supported Troubleshooting the Controllers Observe the Status LEDs on the front of the field controller and see the table below to troubleshoot the controller To troubleshoot an integral or local controller display refer to the FX DIS Local Controller Display Technica...

Страница 29: ...ment controller contact your Johnson Controls representative Accessories Table 9 Accessories Ordering Information Product Code Number Description FX BTCVT 1 Bluetooth Commissioning Converter with Bluetooth Technology FX DIS1710 0 Local Controller Display for use with FX PCG1611 model only FX ZFR1811 0 Wireless Field Bus Router TP 2420 Transformer 120 VAC Primary to 24 VAC secondary 20 VA Wall Plug...

Страница 30: ...less commissioning of the wirelessly enabled FX PCG FX PCA FX PCX and FX PCV field controllers Also allows use of the FX ZFR Checkout Tool FX ZCT in CCT 13 0 and later Note The ZFR USBHA 0 replaces the IA OEM DAUBI_2400 ZigBee USB dongle For additional information on the ZFR USBHA 0 ZigBee dongle refer to the FX ZFR Series Wireless Field Bus System Technical Bulletin LIT 12011660 or FX ZFR Series ...

Страница 31: ...ng for N2 DIP switch set valid control device addresses 1 255 Communications Bus RS 484 BACnet MS TP 3 wire FC Bus between the supervisory controller and other controllers 4 wire SA Bus between controller network sensors and other sensor actuator devices includes a lead to source 15 VDC supply power from controller to bus devices Processor RX630 32 Bit Renesas microcontroller Memory 4 MB flash mem...

Страница 32: ...1 lb United States UL Listed File E107041 CCN PAZX UL 916 Energy Management Equipment FCC Compliant to CFR47 Part 15 Subpart B Class A Canada UL Listed File E107041 CCN PAZX7 CAN CSA C22 2 No 205 Signal Equipment Industry Canada Compliant ICES 003 Europe Johnson Controls Inc declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directi...

Страница 33: ...DUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA 33 FX PCA3611 Advanced Application Programmable Controller Installation Instructions ...

Страница 34: ... 2019 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com ...

Отзывы: