Figure 3: FX-PCA2611-0 Physical Features
Table 1: FX-PCA2611-0 Physical Features
Physical Feature: Description and References
Callout
Binary Output (BO) Source Power Selection Jumpers: Position jumpers to select internal or external 24 VAC
supply power for Binary Outputs. (See
Binary Output (BO) Source Power Selection Jumpers
)
1
Device Address DIP Switch Block (See
2
Mounting Clips (Three)
3
Configurable Outputs (CO) Terminal Block: Can be defined as Voltage Analog Output (0-10 VDC) or Binary Output
(24 VAC Triac). (See
4
Analog Output (AO) Terminal Block: Can be defined as Voltage Analog Output (0-10 VDC) Current Analog Output
(4-20 mA). (See
)
5
24 VAC, Class 2 Supply Power Terminal Block (See
)
6
Cover Lift Tab (One of Two)
7
FC Bus Terminal Block (See
8
SA Bus Terminal Block (See
9
Sensor Port: (SA Bus) RJ-12 6-Pin Modular Jack (See
10
Binary Input (BI) Terminal Block: Dry Contact Maintained or Pulse Counter/Accumulator Mode (See
)
11
Universal Inputs (UI) Terminal Block: Can be defined as Voltage Analog Input (0-10 VDC), Current Analog Input
(4-20 mA), Resistive Analog Inputs (0-600k ohm), or Dry Contact Binary Input. (See
12
End-of-Line (EOL) Switch, located under the cover. (See
Setting the End-of-Line (EOL) Switch
)
13
LED Status Indicators (See
14
FC Bus Port (RJ-12 6-pin Modular Jack) (See
)
15
Binary Outputs (BO) Terminal Block: 24 VAC Triac (See
16
Wiring
Observe the following guidelines when wiring an
FX-PCA2611 controller:
4
FX-PCA2611-0 Advanced Application Programmable Controller Installation Instructions