100.210-IOM (FEB 2015)
Page 45
VYPER
™
VARIABLE SPEED DRIVE
OPERATION
Figure 45 - Communications Screen
PROGRAMMING VYPER™ / QUANTUM™Lx
COMMUNICATIONS
Step 1:
(See.Figure.45).The.communication.rate.between.the.
Vyper
™
.and.the.Quantum
™
LX.requires.programming...Advance.
to.the.Communications.Screen.by.pressing.the.[
MENU
].key.
and.then.selecting.“
Setpoints
”.and.“
Communications
”.
Step 2:
(See.Figure.45).Use.the.cursor.arrow.and.[
Tab
].keys.
to.navigate.between.setpoints..Use.the.keypad.to.program.
the.parameters.listed.in.Table.12.under.“Comm1”.(Callout.
1).at.the.Communications.Screen..Press.the.[
Enter
].key.to.
accept.each.setpoint.
1
TABlE 12 – Comm1 SETPoInTS
Comm 1 Parameter
Setpoint
Baud.Rate
19200
Data.Bits
8
Stop.Bits
1
Parity
None
RS-485.Connection
No
Protocol
Vyper
Map.File
No
Step 3:
Press.the.[
Submit
].key.to.accept.the.changes.to.
Comm1.and.return.to.the.operating.status.screen.