background image

Metasys

 System FEC1611 and FEC1621 Field

Equipment Controller Installation Guide

Application

The FEC16 Field Equipment Controller (FEC) is part of

the 

 Metasys

®

 system Field Equipment Controller family.

The FEC16 controller runs pre-engineered and user-

programmed applications and provides the inputs and

outputs required to monitor and control a wide variety of

HVAC equipment.
The FEC controllers can communicate using either BACnet

MS/TP or N2 communications protocols. These controllers

used as MS/TP devices operate on an RS-485 BACnet

®

MS/TP Bus as BACnet Application Specific Controllers (B-

ASC) and integrate into Johnson Controls

®

 and third-party

BACnet systems.
With Release 10.1, you can use the Controller

Configuration Tool (CCT) 13.0 and later software to switch

the FEC to use the N2 protocol.
The FEC16 controller is available with or without an

integral LCD and push-button user interface.

Communications protocol

The 

Metasys

®

 

 system FEC Family Controllers and network

sensors communicate using either the standard BACnet

protocol, based on the ANSI/ASHRAE 135-2008, or the

BACnet/IP protocol. The BACnet protocol is a standard

for ANSI, ASHRAE, and the International Standards

Organization (ISO) for building controls.
FEC, VMA16, VMA18, and most IOM field controllers are

BTL-listed as BACnet Application Specific Controllers

(B-ASCs). FAC field controllers and the VMA1930 Field

Controller are BTL-listed as BACnet Advanced Application

Controllers (B-AACs).
Release10.1 and later of the Controller Configuration Tool

(CCT) can be used to switch Field Bus communications

protocol in supported FAC, FEC, and VMA controllers to be

either the standard BACnet MS/TP or the N2 protocol. All

new controllers use either BACnet MS/TP as the default

communications protocol, or BACnet/IP. Switchable

communications protocols in the MS/TP models provide

a cost-effective upgrade and modernization path for

customers with existing N2 controllers.

North American emissions compliance

United States

This equipment has been tested and found to comply with

the limits for a Class A digital device pursuant to Part 15

of the FCC Rules. These limits are designed to provide

reasonable protection against harmful interference when

this equipment is operated in a commercial environment.

This equipment generates, uses, and can radiate radio

frequency energy and, if not installed and used in

accordance with the instruction manual, may cause

harmful interference to radio communications. Operation

of this equipment in a residential area may cause harmful

interference, in which case the users will be required to

correct the interference at their own expense.

Canada

This Class (A) digital apparatus meets all the requirements

of the Canadian Interference-Causing Equipment

Regulations.
Cet appareil numérique de la Classe (A) respecte toutes

les exigences du Règlement sur le matériel brouilleur du

Canada.

Installation

Observe these guidelines when installing a field controller:
• Transport the controller in the original container to

minimize vibration and shock damage.

• Verify that all parts shipped with the controller.

• Do not drop the controller or subject it to physical

shock.

Parts included

• One field controller with removable terminal blocks

• One installation instructions sheet

Materials and special tools needed

• Three fasteners appropriate for the mounting surface

(M4 screws or #8 screws)

• One 20 cm (8 in.) or longer piece of 35 mm DIN rail and

appropriate hardware for DIN rail mount (only)

• Small straight-blade screwdriver for securing wires in

the terminal blocks

Mounting

Observe these guidelines when mounting a field

controller:
• Ensure the mounting surface can support the

controller, DIN rail, and any user-supplied enclosure.

• Mount the controller horizontally on 35 mm DIN rail

whenever possible.

• Mount the controller in the proper mounting position

(Figure 1).

• Mount the controller on a hard, even surface whenever

possible in wall-mount applications.

• Use shims or washers to mount the controller securely

and evenly on the mounting surface.

• Mount the controller in an area free of corrosive vapors

and observe the Ambient Conditions requirements in

Table 10.

*2410143136N*

Part No. 24-10143-136 Rev. N

2019-10-18

(barcode for factory use only)

MS-FEC1611-1, MS-FEC1621-1, MS-

FEC1611-1ET

Содержание FEC1611

Страница 1: ...ply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interfe...

Страница 2: ... 2 3 Hang the controller on the DIN rail by the hooks at the top of the DIN rail channel on the back of the controller Figure 2 and position the controller snugly against the DIN rail 4 Push the bottom mounting clips inward up to secure the controller on the DIN rail To remove the controller from the DIN rail pull the bottom mounting clips out to the extended position and carefully lift the contro...

Страница 3: ...y before making electrical connections to avoid electric shock ATTENTION Risque de décharge électrique Débrancher l alimentation avant de réaliser tout rac cordement électrique afin d éviter tout risque de décharge électrique CAUTION Risk of Property Damage Do not apply power to the system before checking all wiring connections Short circuited or improperly con nected wires may result in permanent...

Страница 4: ... is a brown removable 4 terminal plug that fits into a board mounted jack Wire the removable SA Bus terminal block plugs on the controller and other SA Bus devices in a daisy chain configuration using 4 wire twisted shielded cable as shown in Figure 5 See Table 4 for more information Figure 5 SA bus terminal block wiring Note The SA PWR terminal supplies 15 VDC The SA PWR terminal can be used to c...

Страница 5: ...s system 1 Wire the input output terminals and SA bus Note In wireless network applications do not connect any wires to the FC Bus terminal block Connect the SA FC terminal block on an Input Output Module IOM to an SA bus only 2 Connect the ZFR ZFR Pro Wireless Field Bus Router to the FC bus port RJ 12 modular jack on the front of the controller 3 Ensure that the controller s device address DIP sw...

Страница 6: ...inimum pulse width Internal 12 V 15k ohm pull up See Guideline A in Table 3 UNIVERSAL Inputs ICOMn Universal Input Common for all Universal Input terminals Note All Universal ICOMn terminals share a common which is isolated from all other commons Same as Universal INn Binary Input Dry Contact Maintained Mode 0 01 second minimum pulse width Internal 18 V 3k ohm pull up INn Binary Input Pulse Counte...

Страница 7: ...s share a common which is isolated from all other commons except the Binary Input common Binary Output Signal Common All Configurable Outputs COs defined as Binary Outputs are isolated from all other commons including other CO commons Same as Configurable OUTn Cable and wire length guidelines The table below defines cable length guidelines for the various wire sizes that may be used for wiring low...

Страница 8: ...ications Bus Technical Bulletin LIT 12011034 for detailed information about wire size and cable length requirements for the SA and FC buses Table 4 Communications bus and supply power terminal blocks functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements Recommended cable type FC Bus Communications COM Signal Reference Common fo...

Страница 9: ...er Supply Common Isolated from all other Common terminals on controller 35 VA 0 8 mm to 1 0 mm 18 AWG 2 wire Note The SA Bus and FC Bus wiring recommendations in this table are for MS TP bus communications at 38 4k baud For more information refer to the MS TP Communications Bus Technical Bulletin LIT 12011034 for detailed information about wire size and cable length requirements for the SA and FC ...

Страница 10: ...cable termination diagrams Table 5 Termination details Type of Input Output Termination diagrams Temperature Sensor UI Voltage Input External Source UI Voltage Input Internal Source UI Voltage Input Self Powered UI Current Input External Source Isolated UI Current Input Internal Source 2 wire UI Metasys System FEC1611 and FEC1621 Field Equipment Controller Installation Guide 10 ...

Страница 11: ... Source in Loop UI Feedback from EPP 1000 UI Dry Contact Binary Input UI or BI 0 10 VDC Output to Actuator External Source CO or AO Note Add jumper from 24 VAC Com to only one CO Com on FEC16xx or only one AO Com or CO com on FEC26xx per transformer Metasys System FEC1611 and FEC1621 Field Equipment Controller Installation Guide 11 ...

Страница 12: ...nal Source CO or AO Incremental Control to Actuator Switch Low Externally Sourced CO or AO 24 VAC Binary Output Switch High Externally Sourced CO or AO Incremental Control to Actuator Switch High Externally Sourced CO or AO 24 VAC Binary Output Switch Low Externally Sourced BO Metasys System FEC1611 and FEC1621 Field Equipment Controller Installation Guide 12 ...

Страница 13: ...ed BO Incremental Control to Actuator Switch Low Externally Sourced BO Incremental Control to Actuator Switch High Externally Sourced BO Network Stat with Phone Jack Fixed Address 199 SA Bus Network Stat with Terminals Addressable SA Bus Metasys System FEC1611 and FEC1621 Field Equipment Controller Installation Guide 13 ...

Страница 14: ... DIP switch block 128 through 1 to off 2 Set one or more of the seven address switches 64 though 1 to ON so that the sum of the switch numbers set to ON equals the intended device address See Table 6 for valid device addresses Set the highest number switch that is less than or equal to the intended device address to ON Then continue set ting lower numbered switches until the total equals the inten...

Страница 15: ...ke sure that your controller has been converted from BACnet to N2 protocol first Refer to the Modernization Guide for Legacy N2 Controllers LIT 12012005 for more information Note This special configuration is required because controller addresses above 127 were originally intended for use with the Wireless Field Bus system 1 Disconnect the 24 VAC supply from the controller 2 Remove the FC Bus conn...

Страница 16: ...controller cover is lit Setting the Input and Output Jumpers Binary Output BO source power selection jumpers CAUTION Risk of Electric Shock Disconnect supply power to the controller before at tempting to adjust the Binary Output Source Power Selection Jumpers Failure to disconnect the supply power may result in electric shock ATTENTION Risque de décharge électrique Débrancher l alimentation de l c...

Страница 17: ...s with CCT 13 0 and later software either via a Bluetooth Wireless Commissioning Converter a USB wireless dongle or in BACnet Router mode when connected to a Network Automation Engine NAE or Network Control Engine NCE Refer to the Controller Tool Help LIT 12011147 for detailed information on commissioning controllers Note The MAP Gateway serves as a replacement for the BTCVT which is no longer ava...

Страница 18: ...roller fails to operate within its specifications replace the controller For a replacement controller contact your Johnson Controls representative Metasys System FEC1611 and FEC1621 Field Equipment Controller Installation Guide 18 ...

Страница 19: ...4 Position Blue Bulk Pack of 10 AP TBK3PW 0 Replacement Power Terminal Blocks 3 Position Gray Bulk Pack of 10 WNC1800 ZRF182x Pro Wireless Field Bus System This system is used for installations that support BACnet IP but can also coexist with the ZFR1800 Series when installed under the same supervisor i e network engine Refer to the WNC1800 ZFR182x ProSeries Wireless Field Bus System Product Bulle...

Страница 20: ...trollers 4 wire SA bus between controller network sensors and other sensor actuator devices includes a lead to source 15 VDC supply power from controller to bus devices N2 Open Protocol N2 FC Bus 1 0 mm 18 AWG standard 3 wire twisted shielded cable recommended between the supervisory controller and field controllers Processor H8SX 166xR Renesas 32 bit microcontroller Memory 640 KB flash memory and...

Страница 21: ...formance specifications are nominal and conform to acceptable industry standard For application at conditions beyond these specifications consult the local Johnson Controls office Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products Product warranty This product is covered by a limited warranty details of which can be found at www johnsoncontrols...

Страница 22: ...Metasys System FEC1611 and FEC1621 Field Equipment Controller Installation Guide 22 ...

Отзывы: