background image

M4-CV Series VAV Box Controllers Installation

Guide

Application

The CV series controllers are designed for variable air

volume (VAV) box applications.
CV series controllers feature 14 preloaded standard

applications to allow this controller to operate

standard VAV box equipment with a proven energy-

efficient sequence of operation, without the need for

programming. For information on configuring a CV series

controller to use a preloaded application, see 

Setting a

preloaded application

. These controllers are also fully

programmable, using the Controller Configuration Tool

(CCT), providing the flexibility to create custom control

sequences.
CV series controllers feature an integral damper actuator,

a digital Differential Pressure Transmitter (DPT) sensor,

and a 32-bit microprocessor. The CVM03050-0P and

CVE03050-0P models feature an integral potentiometer

to sense actual VAV box damper position. For information

on configuring an application with integrated actuator

feedback, refer to the 

M4-CV Series Actuator Feedback

Application Note (LIT-12013631)

.

CV series controllers also include an integral real-time

clock, which enables the controllers to monitor and

control schedules, calendars, and trends, and operate

for extended periods of time as stand-alone controllers

when offline from the Metasys system network. These

controllers connect easily to the wired and wireless

network sensors for zone and discharge air temperature

sensing. Their small package size facilitates quick

field installation and efficient use of space without

compromising control performance.

Communications protocols

CV series controllers can communicate using multiple

communication protocols depending on model and

configuration. The CVE controllers communicate using

the BACnet/IP communication protocol. CVM controllers

communicate using the BACnet MS/TP, N2, or wireless

Zigbee

®

 communications protocols, with the addition

of ZFR183x Pro Wireless Field Bus Routers. Equipment

Controllers in BACnet/IP or BACnet/MSTP communication

mode are BACnet network-compliant devices. The

BACnet protocol is a standard for ANSI, ASHRAE, and the

International Standards Organization (ISO) for building

controls.
Controllers running in N2 mode can be used to maintain

or modernize sites with installed legacy Johnson Controls

®

controllers. For installation and commissioning support,

and tips for efficient and safe replacement, refer

to the 

Modernization Guide for Legacy N2 Controllers

(LIT-12012005)

 and the controller-specific documentation.

For information about mapping N2 Objects in controllers

with switchable communications protocols, refer to the

N2 Compatibility Options 

chapter of the 

Controller Tool Help

(LIT-12011147)

.

To configure CVM controllers to communicate using

the N2 communications protocol, see 

Configuring N2

communications (CVM models only)

.

To configure CVM controllers to communicate using

the wireless communications protocol, see 

Configuring

wireless communications (CVM models only)

.

North American Emissions Compliance

United States

This equipment has been tested and found to comply

with the limits for a Class A digital device pursuant to

Part 15 of the FCC Rules. These limits are designed

to provide reasonable protection against harmful

interference when this equipment is operated in a

commercial environment. This equipment generates,

uses, and can radiate radio frequency energy and, if not

installed and used in accordance with the instruction

manual, may cause harmful interference to radio

communications. Operation of this equipment in a

residential area may cause harmful interference, in which

case the users will be required to correct the interference

at their own expense.

Canada

This Class (A) digital apparatus meets all the

requirements of the Canadian Interference-Causing

Equipment Regulations.

Cet appareil numérique de la Classe (A) respecte toutes

les exigences du Règlement sur le matériel brouilleur du

Canada.

Installation

Observe the following guidelines when installing the

controller:
• To minimize vibration and shock damage to the

controller, transport the controller in the original

container.

• Verify that all parts shipped with the controller.

• Do not drop the controller or subject it to physical

shock.

Parts included

• One CVM/CVE controller with removable terminal

blocks (Input/Output, Power, FC, and SA terminal blocks

bus are removable)

Note: 

The FC terminal block is only available with

the CVM model

• One installation instructions sheet

• One self-drilling No. 10 x 25 mm (1 in.) screw

*241014301590D*

Part No. 24-10143-01590 Rev. D

11.0

2022-02-07

(barcode for factory use only)

M4-CVM03050-0x, M4-CVE03050-0P

Содержание CVE03050

Страница 1: ...de can be used to maintain or modernize sites with installed legacy Johnson Controls controllers For installation and commissioning support and tips for efficient and safe replacement refer to the Modernization Guide for Legacy N2 Controllers LIT 12012005 and the controller specific documentation For information about mapping N2 Objects in controllers with switchable communications protocols refer...

Страница 2: ... 5 Dual Port Fitting 6 Manual Override Button See Mounting 7 Coupler Bolt 8 Controller Coupler See Mounting 9 Universal Serial Bus USB 2 0 Host Type A Port Note The USB feature is not currently supported 10 Universal Inputs UI Terminal Block White terminals See Table 5 11 Sensor Actuator SA Bus Terminal Block Orange terminal See SA Bus terminal block 12 CVM only Field Controller FC Bus Terminal Bl...

Страница 3: ...osition of the shoulder washer and then drill a hole into the VAV box using a 3 5mm 9 64in drill bit Insert the mounting screw and tighten against the spacer Important Do not overtighten the screw or the threads may strip If mounting to the VAV box make sure the screws do not interfere with damper blade movement 4 Locate the damper position using the typical marking on the end of the damper shaft ...

Страница 4: ...N Risk of Electric Shock Disconnect the power supply before making electrical connections to avoid electric shock ATTENTION Risque de décharge électrique Débrancher l alimentation avant de réaliser tout raccordement électrique afin d éviter tout risque de décharge électrique Important Do not connect supply power to the controller before finishing wiring and checking all wiring connections Short ci...

Страница 5: ...k is a blue removable 4 pin terminal block that fits into a board mounted pin header When connecting the CVM to the FC Bus wire the bus terminal blocks on the controller and other FC Bus devices in a daisy chain configuration using 3 wire twisted shielded cable as shown in Figure 5 For more information about FC Bus terminal functions requirements and ratings see Table 7 Figure 5 FC Bus terminal bl...

Страница 6: ...nts The FC Bus port pin assignment is shown in Figure 7 Note When the CVM is configured for N2 network communication the FC Bus port is not used Supply power terminal block The 24 VAC supply power terminal block is a gray removable 2 pin terminal block that fits into a board mounted pin header on the upper left of the controller Wire the 24 VAC supply power wires from the transformer to the HOT an...

Страница 7: ...nnect the controller to 24 VAC Class 2 power Note If you are using the CVM03050 controller with the Wireless Field Bus System refer to the WNC1800 ZFR182x Pro Series Wireless Field Bus System Bulletin LIT 12012320 or the ZFR1800 Series Wireless Field Bus System Bulletin LIT 12011336 Terminal wiring guidelines functions ratings and requirements This section provides further guidelines on input and ...

Страница 8: ...Internal 12 V 15k ohm pull up See Guideline A in Table 6 UNIVERSAL Inputs UI C or UI Cn Universal Input Common for all Universal IN terminals Note All Universal UI C UI Cn terminals are isolated from all other commons Same as Universal UI n Analog Output Voltage Mode 0 10 VDC 10 VDC maximum output voltage 10 mA maximum output current External 1k to 50k ohm load required See Guideline A in Table 6 ...

Страница 9: ...3 m 600 ft twisted wire A 0 5mm 24 AWG stranded copper 107 m 350 ft twisted wire 107 m 350 ft twisted wire 100 mV maximum voltage drop Depending on the cable length and the connected input or output device you may have to define an offset in the setup software for the input or output point 1 0 mm 18 AWG stranded copper 229 m 750 ft twisted wire 0 8 mm 20 AWG stranded copper 297 m 975 ft twisted wi...

Страница 10: ...ss of wire size must be twisted insulated stranded copper wire Shielded cable is strongly recommended for all FC and SA Bus cables Communications bus and supply power terminal blocks ratings and requirements Table 7 Communication bus and supply power terminal blocks functions ratings requirements and cables Terminal block Port label Terminal labels Function electrical ratings Requirements Recommen...

Страница 11: ...or above Wireless ZigBee WRZ 78xx Series One to One Wireless Receiver DIS1710 Local Controller Display VAV Balancing Tool 24 AWG 3 pair CAT 3 Cable 30 5m 100 ft HOT 24 VAC Power Supply Hot Supplies 20 30 VAC Nominal 24VAC 24V COM 24 VAC Power Supply Common The CVM models only isolate this terminal from the FC Bus common 0 8 mm to 1 0 mm 20 to 18 AWG 2 wire 1 The FC Bus and SA Bus wiring recommenda...

Страница 12: ...Voltage Input Self Powered UI Temperature Sensor UI Dry Contact UI 0 10 VDC Output to Actuator External Source CO 0 10 VDC Output to Actuator Internal Source CO 24 VAC Triac Output Switch Low External Source CO Note Applies to CO4 and CO5 M4 CV Series VAV Box Controllers Installation Guide 12 ...

Страница 13: ...ternal Source CO Note Applies to CO4 and CO5 Analog Output Voltage CO Incremental Control to Actuator Switch Low Internally Sourced BO Note Applies to BO3 for only BO1 and BO2 24 VAC Binary Output Switch Low Internally Sourced BO Network Stat with Phone Jack Fixed Address 199 SA Bus M4 CV Series VAV Box Controllers Installation Guide 13 ...

Страница 14: ...red for N2 to the controller Switching the communications protocol from N2 to MS TP About this task For N2 sites that are converting to BACnet MS TP you can switch the communications protocol of N2 configured controllers back to BACnet MS TP To switch the CVM controller operating in N2 mode back into BACnet MS TP mode complete the following steps 1 Disconnect the 24 VAC supply from the controller ...

Страница 15: ...ss defined in the Controller Configuration Tool CCT under Define Hardware Network Settings To set the device addresses on controllers complete the following steps 1 Set a unique and sequential device address for each of the devices connected on the FC or SA starting with device address 4 2 To ensure the best bus performance set sequential device addresses with no gaps in the device address range 4...

Страница 16: ...Bulletin LIT 12011034 3 If the controller is a terminating device on the FC Bus set the EOL switch to ON If the controller is not a terminating device on the bus set the EOL switch to OFF When a controller is connected to power with its EOL switch set to ON the amber EOL LED on the controller cover is illuminated Input and output wiring validation The controllers ship with a cooling only warm or c...

Страница 17: ...Speed Series Fan Warm Cool Adjust Elec Reheat 1 3 Stg Series Fan SP Adj Single Duct Electric Staged Reheat with 1 2 or 3 Stages Single Speed Series Fan Setpoint Adjust Elec Reheat 1 3 Stg Parallel Fan W C Adj Single Duct Electric Staged Reheat with 1 2 or 3 Stages Parallel Fan Warm Cool Adjust Elec Reheat 1 3 Stg Parallel Fan SP Adj Single Duct Electric Staged Reheat with 1 2 or 3 Stages Parallel ...

Страница 18: ...link 2 Hz Blink 2 Hz Data transmission normal communication Off Steady No data transmission auto baud in progress On Steady communication lost waiting to join communication bus SA BUS Green Blink 2 Hz Blink 2 Hz Data transmission normal communication Off Steady No data transmission N A auto baud not supported On Steady Communication lost waiting to join communication bus FC EOL CVM models Amber Of...

Страница 19: ...OM there must be no short circuit Note Some installations require the secondary of the transformer to be Earth Grounded If this is the case verify that the Earth Ground connection is valid and not shared between multiple pieces of equipment Configurable output analog mode is invalid 0 10 V output is set to 10 100 but 0 V is at output terminals Output is in protection mode a state the analog portio...

Страница 20: ...g Product Bulletin LIT 12011640 for a list of available products WRZ SST 120 Wireless System Survey Tool for use with the lower power 10mW WRZ and WRZ 7860 systems Refer to the WRZ SST 120 Wireless Sensing System Tool Installation Instructions LIT 24 10563 55 for usage instructions WRG1830 ZFR183x Pro Wireless Field Bus System This system is used for installations that support BACnet IP but can al...

Страница 21: ... IN terminals for active 3 wire input devices Ambient Conditions Operating 0 C to 50 C 32 F to 122 F 10 to 90 RH noncondensing Storage 40 C to 70 C 40 F to 158 F 5 to 95 RH noncondensing Network Engines M4 CVM models All network engine model types M4 CVE03050 0P All network engine model types at R9 0 or later Communications Protocol M4 CVM models BACnet MS TP N2 Zigbee Wireless also supported at F...

Страница 22: ... lb Compliance United States UL Listed File E107041 CCN PAZX UL 916 Energy Management Equipment FCC Compliant to CFR47 Part 15 Subpart B Class A Suitable for Use in Other Environmental Air Space Plenums in Accordance with Section 300 22 C of the National Electrical Code Canada UL Listed File E107041 CCN PAZX7 CAN CSA C22 2 No 205 Signal Equipment Industry Canada Compliant ICES 003 Europe CE Mark J...

Страница 23: ...m Single point of contact APAC Europe NA SA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS VOLTAWEG 20 6101 XK ECHT THE NETHERLANDS JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA Contact information Contact your local branch office www johnsoncontrols com locations Contact Johnson Controls www johnson...

Страница 24: ... 2022 Johnson Controls All rights reserved All specifications and other information shown were current as of document revision and are subject to change without notice www johnsoncontrols com ...

Отзывы: