Fan performance
Table 5: CSV060B supply air blower performance
Available external static pressure - inches W.C.*
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
Supply
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field supplied
low static drive
Standard drive + 1HP
Optional hi- 1.5HP
1600
645 0.29 733 0.36 814 0.43 888 0.50 958 0.57 1024 0.64 1087 0.72 1154 0.83 1211 0.91 1245 0.99
1800
708 0.40 788 0.48 863 0.55 933 0.63 999 0.71 1061 0.79 1121 0.87 1178 0.95 1233 1.04 1295 1.17
2000
763 0.52 837 0.61 907 0.69 973 0.77 1035 0.86 1095 0.95 1152 1.04 1207 1.13 1260 1.22 1311 1.31
2200
836 0.69 904 0.78 969 0.87 1030 0.97 1089 1.06 1145 1.15 1199 1.25 1252 1.35 1303 1.45
~
~
2400
898 0.88 961 0.98 1021 1.08 1079 1.18 1135 1.28 1188 1.38 1240 1.48
~
~
~
~
~
~
Note:
At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur.
Decrease airflow downward as necessary.
* Blower performance includes evaporator coil and 2" filters.
Table 6: CSV096B supply air blower performance
Available external static pressure - inches W.C.*
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
Supply
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field supplied
low static drive
Standard drive + 1.5HP
Optional hi- 2HP
2400
510 0.31 600 .45 672 0.60 741 0.78 810 0.96 878 1.14 936 1.33 982 1.54 1033 1.76 1074 2.00
2800
538 0.44 628 0.57 700 0.71 778 0.89 830 1.10 890 1.29 950 1.50 1010 1.72 1048 1.92
~
~
3200
599 0.62 675 0.79 745 0.98 815 1.18 875 1.38 927 1.58 985 1.78 1037 1.99
~
~
~
~
3600
661 0.86 730 1.03 795 1.23 853 1.43 915 1.64 973 1.85
~
~
~
~
~
~
~
~
4000
712 1.10 773 1.28 830 1.50 888 1.72 946 1.95
~
~
~
~
~
~
~
~
~
~
Note:
At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur.
Decrease airflow downward as necessary.
* Blower performance includes evaporator coil and 2" filters.
Table 7: CSV120B supply air blower performance
Available external static pressure - inches W.C.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
Supply
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field supplied
low static drive
Standard drive + 2HP
Optional hi- 2.5HP
3200
599 0.62 675 0.79 745 0.98 815 1.18 875 1.38 927 1.58 984 1.78 1037 1.99 1082 2.22 1128 2.42
3600
661 0.86 730 1.03 795 1.23 853 1.43 915 1.64 973 1.85 1020 2.10 1070 2.37 1114 2.67 1160 2.89
4000
712 1.10 773 1.28 830 1.50 888 1.72 946 1.95 1004 2.19 1062 2.44 1098 2.70 1146 2.97
~
~
4400
768 1.42 824 1.62 877 1.82 930 2.04 985 2.30 1035 2.60 1085 2.90
~
~
~
~
~
~
4800
822 1.78 875 1.98 925 2.20 975 2.43 1026 2.68 1078 2.96
~
~
~
~
~
~
~
~
Note:
At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur.
Decrease airflow downward as necessary.