Installation & Operation Guide

Thank you for purchasing the Johnson Controls  

Single Phase Building Management Motor Starter! 

Please read this manual thoroughly to ensure 

safe installation and proper operation.

Precautions

To prevent injury and property damage, follow these instructions.  

Failure to adhere to installation/operation procedures and all applicable 

codes may result in hazards as indicated by warning 

codes outlined below:

indicates an imminently hazardous situation which, if not avoided, will 

result in death or serious injury. This signal word is to be limited to the 

most extreme situations.

indicates a potentially hazardous situation which, if not avoided, could 

result in death or serious injury.

indicates a potentially hazardous situation which, if not avoided, may 

result in minor or moderate injury. It may also be used to alert against 

unsafe practices.

This is the safety alert symbol.

 Read and follow instructions carefully to 

avoid a dangerous situation.

This symbol alerts the user to the presence of “dangerous voltage”

 

inside the product that might cause harm or electrical shock.

DANGER

WARNING

CAUTION

Safety Instructions

Equipment starts automatically. Lockout/tagout before servicing.

As  with  all  electrical  products,  read  manual  thoroughly.  Only 

qualified, 

expert personnel should perform maintenance and installation. Contact the 

nearest authorized service facility for examination, repair, or adjustment. 

Do not disassemble or repair unit unless described in this manual; death 

or injury to electrical shock or 

fire

 hazard may result. 

Specifications

 and 

manual data subject to change. Consult factory for additional information.

DANGER

CAUTION

1Ø AC Input 50/60 Hz

L1

L2/N

T1

T2

M

Voltage Input 

Auto Run

Fault 

Output

Status 

Output

Dry Input 

Auto Run

Normally Open 

Input

12-120VAC/DC 

Input

Main Power Wiring

Wire main power input and output to the appropriate 12AWG wire leads utilizing 

properly sized wire nuts. Use only copper conductors rated at least 60°C.  

Maintain proper clearances and verify that no possibility of an electrical short 

exists between the power conductors or enclosure. Ensure that wires are not 

under stress and all insulation is intact. 

Low Voltage Wiring

Automation system control wiring should be run in a separate conduit. The 

control terminals accept 26~14AWG wire torqued to 3.5 in-lb.

Installation

FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN DEATH OR 

SERIOUS INJURY

Mounting

Mount the starter on a minimum 14 cu-in single gang junction box. To access 

mounting holes, slide upper and lower covers to the open position. 

(See Figure 1) 

Using provided mounting screws (6-32 x 7/8”), attach starter housing to junction 

box (once appropriate wiring has been completed).

•  

materials. Contact arcing can induce e

xplosion or fir

e.

•  Install starter in UL Type 1 (NEMA 1) appropriate locations only. Safe mounting 

requires a dry, protected environment.

• The BAS-1P is rated for maximum ambient temperature of 40°C

•  Do not allow any metal shavings or debris from installation to enter enclosure.

WARNING

Figure 1

HAZARDOUS VOLTAGE

•  Disconnect and lock out all power before installing or servicing equipment.

•  This equipment may require locking out multiple power sources prior to service

•  Install and wire in accordance with all applicable local & national electrical and 

construction codes

LIT-12013012