Updated 11.8.17
© Copyright 2018 Johnson Controls
www.johnsoncontrols.com | 414.524.1200 | 5757 N. Green Bay Ave., P.O. Box 591, Milwaukee, WI 53201
Installation & Operation Guide
Thank you for purchasing the Johnson Controls
Single Phase Building Management Motor Starter!
Please read this manual thoroughly to ensure
safe installation and proper operation.
Precautions
To prevent injury and property damage, follow these instructions.
Failure to adhere to installation/operation procedures and all applicable
codes may result in hazards as indicated by warning
codes outlined below:
indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury. This signal word is to be limited to the
most extreme situations.
indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
indicates a potentially hazardous situation which, if not avoided, may
result in minor or moderate injury. It may also be used to alert against
unsafe practices.
This is the safety alert symbol.
Read and follow instructions carefully to
avoid a dangerous situation.
This symbol alerts the user to the presence of “dangerous voltage”
inside the product that might cause harm or electrical shock.
DANGER
WARNING
CAUTION
Safety Instructions
Equipment starts automatically. Lockout/tagout before servicing.
As with all electrical products, read manual thoroughly. Only
qualified,
expert personnel should perform maintenance and installation. Contact the
nearest authorized service facility for examination, repair, or adjustment.
Do not disassemble or repair unit unless described in this manual; death
or injury to electrical shock or
fire
hazard may result.
Specifications
and
manual data subject to change. Consult factory for additional information.
DANGER
CAUTION
1Ø AC Input 50/60 Hz
L1
L2/N
T1
T2
M
Voltage Input
Auto Run
Fault
Output
Status
Output
Dry Input
Auto Run
Normally Open
Input
12-120VAC/DC
Input
Main Power Wiring
Wire main power input and output to the appropriate 12AWG wire leads utilizing
properly sized wire nuts. Use only copper conductors rated at least 60°C.
Maintain proper clearances and verify that no possibility of an electrical short
exists between the power conductors or enclosure. Ensure that wires are not
under stress and all insulation is intact.
Low Voltage Wiring
Automation system control wiring should be run in a separate conduit. The
control terminals accept 26~14AWG wire torqued to 3.5 in-lb.
Installation
FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN DEATH OR
SERIOUS INJURY
Mounting
Mount the starter on a minimum 14 cu-in single gang junction box. To access
mounting holes, slide upper and lower covers to the open position.
(See Figure 1)
Using provided mounting screws (6-32 x 7/8”), attach starter housing to junction
box (once appropriate wiring has been completed).
•
materials. Contact arcing can induce e
xplosion or fir
e.
• Install starter in UL Type 1 (NEMA 1) appropriate locations only. Safe mounting
requires a dry, protected environment.
• The BAS-1P is rated for maximum ambient temperature of 40°C
• Do not allow any metal shavings or debris from installation to enter enclosure.
WARNING
Figure 1
HAZARDOUS VOLTAGE
• Disconnect and lock out all power before installing or servicing equipment.
• This equipment may require locking out multiple power sources prior to service
• Install and wire in accordance with all applicable local & national electrical and
construction codes
LIT-12013012