A419 Series Electronic Temperature Controls with Display and NEMA 1 or NEMA 4X Watertight Enclosures

Product/Technical Bulletin    

5

In 

Cooling/Cutout mode

 the differential is above

Setpoint. The output relay energizes and LED
illuminates when the temperature rises to Setpoint 

plus

the differential value. When the temperature drops to
Setpoint, the relay and LED de-energize.

Setpoint

(+)

Cooling/Cut-out

Cooling/Cut-in

Cut-out

(-)

Differential

Differential

Temperature

(Off)

Cut-in

(On)

Cut-in

(On)

Cut-out

(Off)

Figure 7: Cooling Modes

When the 

Heating/Cut-in mode

 is selected, the

differential is above Setpoint. The output relay
energizes and LED indicator illuminates when the
temperature drops to Setpoint. When the temperature
rises to Setpoint 

plus

 the differential value, the output

relay and LED de-energize.

When 

Heating/Cutout mode

 is selected, the

differential is below Setpoint. The output relay
energizes and LED indicator illuminates when the
temperature drops to Setpoint 

minus

 the differential

value. When the temperature rises to Setpoint, the
output relay and LED indicator de-energize.

Setpoint

(+)

Heating/Cut-out

Heating/Cut-in

(-)

Temperature

Differential

Cut-out

(Off)

Cut-in

(On)

Differential

Cut-in

(On)

Cut-out

(Off)

Figure 8: Heating Modes

Mounting

An A419 control has either a standard high-impact
plastic NEMA 1 or a NEMA 4X corrosion-resistant,
watertight enclosure.

The A419 control is not position sensitive but should
be mounted for convenient wiring and adjustment.

Note:

When mounting the control to rigid conduit,

attach the hub to the conduit before securing the hub
to the control enclosure.

The mounting hole pattern of the NEMA 1 enclosure is
identical to that of the System 350

 controls, and most

models of the A19 control. The NEMA 1 enclosure
may also be mounted on 35 mm DIN rail. See Figure 1
and Figure 2.

The NEMA 4X models may be mounted to flat vertical
surfaces using the four screw holes at the enclosure
corners. See Figure 3 and Figure 4. To maintain the
watertight and corrosion resistant integrity of the
NEMA 4X enclosure, use a conduit fitting rated for the
environment in which the control is installed.

An additional (low-voltage) two-wire cable is required
to operate the temperature offset function. On
NEMA 4X enclosures you must install a suitable
liquid-tight fitting in an available knockout to pass the
two-wire cable through the enclosure wall.

IMPORTANT:

The short-lead A99 sensor,

included with A419 NEMA 4X model controls, must
be mounted on the bottom of the control in the
bracket molded on the NEMA 4X housing. Mounting
the sensor on top of the control may reduce the
accuracy of the displayed temperature. See Figure 3
and Figure 4 for proper sensor position.

Содержание A419 Series

Страница 1: ...Temperature Sensor Features and Benefits Easy to Read Front Panel Liquid Crystal Display Displays the sensed temperature and control function status clearly custom icons on the display indicate the control and system status at a glance Wide Temperature Differential Adjustment Range 1 to 30F or C Allows the user to set a precise 1F or C temperature differential from 1 to 30F or C providing a much t...

Страница 2: ...e harmful interference and 2 this device must accept any interference that may cause undesired operation This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of FCC rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipment gen...

Страница 3: ...n to adjust the control setting Output Relay Status Indicator LED A green LED on the control s front panel illuminates when the SPDT output relay is energized and the Normally Open N O contacts are closed See Figure 5 A419 Control Definitions Cut in is the temperature at which the N O contacts on the SPDT output relay close Cutout is the temperature at which the N O contacts on the SPDT output rel...

Страница 4: ...ue set in Temperature Offset The BIN and COM terminals may be connected to a user supplied external switching device such as a time clock that has a set of Single Pole Single Throw SPST contacts Closing a circuit between the BIN and COM terminals activates the Temperature Offset See Wiring This function enables the control to alternate between two temperature setpoints based on the position of the...

Страница 5: ...n A419 control has either a standard high impact plastic NEMA 1 or a NEMA 4X corrosion resistant watertight enclosure The A419 control is not position sensitive but should be mounted for convenient wiring and adjustment Note When mounting the control to rigid conduit attach the hub to the conduit before securing the hub to the control enclosure The mounting hole pattern of the NEMA 1 enclosure is ...

Страница 6: ...igure 10 and Figure 11 Keep the leads between the control and sensor as short as possible practical in your application The additional resistance in long sensor leads creates error between the actual temperature and the displayed temperature Refer to Table 1 when extending sensor leads Temperature sensor signals may be affected by electrical interference When extending sensor cable beyond 50 ft 15...

Страница 7: ...pers to set Cooling Heating Setpoint and Touchpad Lock functions 4 Replace the cover and fasten in place with the four screws 5 Restore power to the control IMPORTANT Verify that the Cooling Heating jumper is positioned properly before powering the A419 control to ensure that the relay operates as intended See Figure 13 and Table 2 Jumper Pins Removed Jumper Positioned on One Pin Installed Jumper ...

Страница 8: ...everts to the previously saved setpoint value Any saved A419 control setting values are non volatile and remain in the control s memory during power interruptions Table 3 Function Ranges and Settings Function Range Factory Setting SP Setpoint 30 to 212 F 34 to 100 C 30 dIF Differential 1 to 30 F or C 5 ASd Anti short Cycle Delay 0 to 12 minutes 1 OFS Temperature Offset 0 to 50 F or C 0 SF Sensor F...

Страница 9: ...sly saved value for that function Any saved A419 control setting values are non volatile and remain in the control s memory during power interruptions Checkout Before applying power make sure installation and wiring connections are according to job specifications After necessary adjustments and electrical connections have been made put the system in operation and observe the control for at least t...

Страница 10: ...s 1 and 2 before performing this step b Disconnect the load from the output relay terminals c Ensure that the Touchpad Lock jumper is installed so that the touchpad is unlocked d Reconnect the sensor leads and supply power to the control e Replace the cover f Check the control settings for proper values g Press and hold the MENU button until Setpoint appears occurs in about 2 seconds h Use the Up ...

Страница 11: ...he control Ordering Information Refer to Table 6 to order controls and accessories Table 6 Ordering Information Product Code Number Item Description A419ABC 1C Line Voltage NEMA 1 Enclosure A419 Series Electronic Temperature Control with Display A99 Sensor Included A419AEC 1C Line Voltage NEMA 4X Enclosure A419 Series Electronic Temperature Control with Display A99 Sensor Included Supply Voltage 1...

Страница 12: ...hp Full Load Amperes N O N C 16 5 8 A 9 2 4 0 A 8 0 4 9 A Locked Rotor Amperes N O N C 96 34 8 A 55 2 24 A 48 29 4 A Non inductive Amperes N O N C 15 10 A 10 10 A 10 10 A Pilot Duty 125 VA N O contacts 24 to 240 VAC 125 VA N C contacts 120 to 240 VAC 50 VA N C contacts 24 VAC Sensor Type A99BB Type PTC Sensor See Table 6 Control Ambient Temperature Operating 26 to 140 F 32 to 60 C Shipping 40 to 1...

Отзывы: