ntroduction

These warm air limit controls "lock out" on a
temperature increase to the control setpoint.
Manual reset is required to re-close the
electrical contacts. A typical application is to
stop air-conditioning or ventilating fans in the
event of excessive return air temperature, as

from a fire.

D

escription

A rod and tube type sensing element actuates
the switch contacts. Main contacts (1 - 2) are
normally closed, and open when the
temperature at the element rises to the dial
setpoint. Contacts are re-closed only by
operation of the reset lever. The reset lever is
"trip-free" and cannot be used to block contacts
in a closed position.

L

ocation

Select a location in the duct or plenum where the

temperature element senses the average

temperature to be controlled and is in free air

circulation.

M

ounting

The instrument is mounted by means of the

flange which is supplied with the control. The

element is to be inserted in the duct and must be

in the airstream as much as possible. It should

not be in contact with any object inside the duct.

A25CN

N

ote

These controls are designed for use only as

operating controls. Where an operating control

failure would result in personal injury or loss of

property it is the responsibility of the installer

to add devices or systems that protect against,

or warn of, control failure.

A

djustment

These thermostats are standard available with a

knob adjustment. This knob can be removed in

the field to provide screwdriver adjustment.

Feature and Benefits

‰

Rod and tube type of element

Gives maximum response
Allows high maximum element temperature

‰

Adjustable duct mounting flange

Allows various lengths insertion of the element

into the airstream

‰

Trip-free manual reset

Override is not possible in the control function

‰

Dust-tight Penn switch

Prevent pollution of the contacts by
electromagnetic influences

Serie A25CN

Limit Control Manual Reset