JC-400-004 

I56-3366-000 

This  sensor  must  be  installed  in  compliance  with  the  control  panel  system 
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ). Sensors offer maximum performance when 
installed in compliance with the National Fire Protection Association (NFPA); 
see NFPA 72. 

GENERAL DESCRIPTION

Model 2951J-COPTIR is a plug-in type smoke sensor that is a photoelectronic 
sensing chamber combined with Carbon Monoxide (CO), thermal, and infra-
red (IR) sensors with addressable-analog communications. The sensors trans-
mit an analog representation of smoke density over a communication line to 
a control panel. Rotary decade switches are provided for setting the sensor’s 
address.

Two LEDs on the sensor are controlled by the panel to indicate sensor status. 
An output is provided for connection to an optional remote LED annunciator 
(P/N RA400Z).

Johnson Controls panels offer different features sets across different models. 
As a result, certain features of the 2951J-COPTIR may be available on some 
control panels, but not on others. The possible features available in the 2951J-
COPTIR, if supported by the control unit are:

1.   The panel controls the LED operation on the sensor. Operational modes 

are RED blink, RED continuous, GREEN blink, and off.

2.   The remote output may be synchronized to the LED operation or con-

trolled independent of the LEDs.

Please refer to the operation manual for the UL listed control unit for specific 
operation of the 2951J-COPTIR.

The 2951J-COPTIR requires compatible addressable communications to func-
tion properly. Connect these sensors to listed-compatible control panels only.

SPACING

Johnson Controls recommends spacing sensors in compliance with NFPA 72. 
In low air flow applications with smooth ceilings, space sensors 30 feet apart. 
For specific information regarding sensor spacing, placement, and special ap-
plications, refer to NFPA 72 or the System Smoke Detector Application Guide, 
available from Johnson Controls.

WIRING GUIDE

All wiring must be installed in compliance with the National Electrical Code, 
applicable local codes, and any special requirements of the Authority Having 
Jurisdiction.Proper wire gauges should be used. The installation wires should 
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper  connections  will  prevent  a  system  from  responding  properly  in  the 
event of a fire.

Remove power from the communication line before installing sensors.

1.   Wire the sensor base (supplied separately) per the wiring diagram, see 

Figure 1.

2.  Set the desired address on the sensor address switches, see Figure 2.
3.   Install  the  sensor  into  the  sensor  base.  Push  the  sensor  into  the  base 

while turning it clockwise to secure it in place.

4.   After all sensors have been installed, apply power to the control unit and 

activate the communication line.

2951J-COPTIR Intelligent Photoelectric 
Multi-Criteria Smoke Sensor

I56-3366-000

INSTALLATION AND MAINTENANCE INSTRUCTIONS

SPECIFICATIONS

Operating Voltage Range: 

15 to 32 VDC

Standby Current: 

300µA @ 24 VDC (one communication every 5 seconds with LED blink enabled)

Max. Alarm Current (LED on): 

7 mA @ 24 VDC

Operating Humidity Range: 

10% to 93% Relative Humidity, Non-condensing

Operating Temperature Range: 

0°C to 38°C (32°F to 100°F)

Height: 

2.7˝ (69 mm) installed in B710LP Base

Diameter: 

6.0˝ (155 mm) installed in B710LP Base; 4.0˝ (102 mm) installed in B501 Base

Weight: 

4.6 oz. (130 g)

5.  Test the sensor(s) as described in the TESTING section of this manual.

FIGURE 1. WIRING DIAGRAM:

3

2

1

3

2

1

+

+

+

REMOTE ANNUNCIATOR

CAUTION: DO NOT LOOP WIRE 

UNDER TERMINAL 1 OR 2.

BREAK WIRE RUN TO PROVIDE 

SUPERVISION OF CONNECTIONS.

UL

 LISTED COM

P

A

TIBLE 

CONTROL

 P

ANEL

OPTIONAL RETURN LOOP

C0100-01

FIGURE 2. ROTARy ADDRESS SWITChES:

TENS

ONES

9

10

11

12

13

14

15

8

7

6

5

4

3

2

1 0

9

8

7

6

5

4

3

2

1 0

C0955-00

CAUTION

Dust covers provide limited protection against airborne dust particles during 
shipping. Dust covers must be removed before the sensors can sense smoke. 
Remove sensors prior to heavy remodeling or construction.

TAMPER-RESISTANCE

Model 2951J-COPTIR includes a tamper-resistant capability that prevents their 
removal from the bracket without the use of a tool. Refer to the base manual 
for details on making use of this capability.

TESTING

Before  testing,  notify  the  proper  authorities  that  the  system  is  undergoing 
maintenance,  and  will  temporarily  be  out  of  service.  Disable  the  system  to 
prevent unwanted alarms.

All sensors must be tested after installation and periodically thereafter. Test-
ing  methods  must  satisfy  the  Authority  Having  Jurisdiction  (AHJ).  Sensors 
offer maximum performance when tested and maintained in compliance with 
NFPA 72. 

The sensor can be tested in the following ways:

A.  Functional: Magnet Test (P/N M02-04-01 or M02-09-00) 

 

 This sensor can be functionally tested with a test magnet. The test mag-
net  electronically  simulates  smoke  in  the  sensing  chamber,  testing  the 
sensor electronics and connections to the control panel.

507 E. Michigan Street

Milwaukee, WI 53201

Phone: 414.524.4000