Part No. 24-11443-00006, Rev. B

7

NS8000 Series

Activating and deactivating the screen lockout mode

Lock the screen to prevent users from making setpoint changes or accessing the settings screens. To activate and deactivate the 

screen lockout, complete the following steps:

1.  Press the 

Settings

 icon for 10 seconds to enter 

Lockout

 mode.The lock symbols replaces the 

Settings

 icon.

2.  In Lockout mode, you cannot access the 

Temperature

 setpoint screen, the 

Settings

 screen, or the 

Network

 screen.

3.  Press the 

Settings

 icon for 10 seconds to exit 

Lockout

 mode.

Changing the decimal separator

1.  Press the 

Settings

 icon and tap the arrow in the top right to navigate to the second page.

2.  To change the decimal separator, tap the 

Toggle

 icon to switch between the decimal comma and decimal point.

Selecting the maximum fan speed setting

The default fan speed is automatic. To change the value of the maximum fan speed, complete the following steps:

1.  Press the 

Settings

 icon and tap the arrow in the top right to navigate to the second page. 

2.  Tap the 

Fan Speed

 bars to select the maximum setting as No Fan, Low, Medium, or High.

Hiding icons on the home screen

1.  Press the 

Settings

 icon and tap the arrow in the top right to navigate to the third page. 

2.  Press an icon to toggle between showing the icon and hiding the icon.

3.  Press the green 

Checkmark

 icon to confirm the change or the red 

Cancel

 icon to cancel the change, and return to the 

previous screen. 

Adjusting the temperature unit

1.  Press the 

Settings

 icon and use the scroll arrow to navigate to the second page.

2.  To change the temperature unit, tap the 

Toggle

 icon to switch between Fahrenheit and Celsius.

Title 24 error indicators

In the event of a Title 24 related error, the graphical screen displays the 

Error

 icon in the upper left of the display screen with the 

corresponding error code number for all the required state of California Title 24 economizer fault conditions. See the following talbe 

for fault error codes. 

       Table 2: Fault error codes

Display text  California Title 24 economizer fault condition Possible problem

E0

Air temperature sensor failure/fault

Problem with one of the air temperature sensors. Check 

outdoor air, return air, or supply air sensors.

E1

Not economizing when it should

The economizer is not using outdoor air when it should.

E2

Economizing when it should not

The economizer is allowing outdoor air inside when the 

conditions are not suitable for economizer operation.

E3

Damper not modulating

The economizer damper is not able to modulate properly. 

Check damper, linkage to actuator, or the actuator.

E4

Excess outdoor air

The economizer is allowing excess outdoor air inside.

Notes: 

• 

The fan icon is hidden by default in a newly shipped unit. You can activate it in the 

Settings

 menu.

• 

RH and CO

icons are only visible in units that support these features.

• 

An icon displays as blue when enabled and an icon displays as gray when disabled.

• 

Hidden or visible icons remain in a fixed position and cannot be realigned.

• 

Hidden icons are grayed out in 

Settings 

mode and are not visible in screen display mode.

• 

It is not possible to scroll from Page 3 to Page 2. Confirm or cancel a change to return to the previous screen.  

Содержание 24-11443-00006

Страница 1: ...es dispositifs de sécurité ou de limitation ayant une fonction d avertissement ou de protection en cas de défaillance ou de dysfonctionnement du network sensor Mounting 466 72 0 74 5 40 CO2 F 466 ppm 72 CO2 40 North American Emissions Compliance United States This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These l...

Страница 2: ...Note Locate the network sensor away from steam or water pipes warm air stacks unconditioned areas not heated or cooled or sources of electrical interference Height requirements may vary depending on the site Network sensors without CO2 sensing are shock and vibration resistant but not shock and vibration proof Be careful not to drop the unit or mount it where it could be exposed to excessive vibra...

Страница 3: ...adhere to these wiring details causes the network sensor to function incorrectly You will not be able to connect to the system using the Bluetooth Wireless Comissioning Converter BTCVT Mobile Access Portal Gateway MAP or the handheld VAV balancing tool and you will not be able to expand the system with future offerings IMPORTANT Do not connect the SA bus ground the modular phone jack GND or the sc...

Страница 4: ...Part No 24 11443 00006 Rev B 4 NS8000 Series 5 2 1 4 SA SA COM 15 VDC 15 VDC COM 15 VDC 1 2 5 6 4 3 COM SA SA 3 ...

Страница 5: ...e setpoint temperature Network Network connection to host controller over SA bus No No network Sensor not connected to host controller No Settings Settings menu Settings lock Lockout mode Temperature Displays current temperature No Setting enabled Toggle setting is blue Setting disabled Toggle setting is white Error Title 24 error indicator Page indicator Settings screen page indicator Scroll arro...

Страница 6: ... temperature relative humidity RH or CO2 show below the relevant icon Any interaction with a display screen activates temporary occupancy mode for 2 minutes See Figure 1 to 3 for individual graphical display screens Main screens overview Viewing the settings screens 1 Tap the Settings icon to access the settings screens 2 Tap the left and right arrows at the top of the screen to scroll through the...

Страница 7: ...s icon and use the scroll arrow to navigate to the second page 2 To change the temperature unit tap the Toggle icon to switch between Fahrenheit and Celsius Title 24 error indicators In the event of a Title 24 related error the graphical screen displays the Error icon in the upper left of the display screen with the corresponding error code number for all the required state of California Title 24 ...

Страница 8: ...curacy of the CO2 concentration measurement is essential modify the offset property of the NS Series CO2 Network Sensors Zone Quality ZN Q Analog Input AI The offset represents the local atmospheric pressure in hectopascals hPa Set the offset to the known local pressure or use the local altitude value listed in Table 3 The factory default value is 978 hPa As of Release 5 3 of the Controller Config...

Страница 9: ...e measurement range 32 0 F 0 C to 104 F 40 C Temperature sensor type Digital temperature sensor Humidity sensor type Thin film capacitive sensor Ambient conditions Operating 32 F to 122 F 0 C to 50 C 10 to 90 RH noncondensing 85 F 29 C maximum dew point Storage 40 F to 122 F 40 C to 50 C 5 to 95 RH noncondensing Temperature resolution 0 5 F 0 5 C Temperature accuracy NS Series Network Zone Sensor ...

Страница 10: ...ontact Johnson Controls www johnsoncontrols com contact us APAC JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA Europe JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN GERMANY NA SA JOHNSON CONTROLS 507 E MICHIGAN ST MILWAUKEE WI 53202 USA Single point of contact The performance specifications are nominal and conform to acceptable indu...

Отзывы: