JOHNSON CONTROLS
32
FORM 100.50-NOM6
ISSUE DATE: 8/07/2017
SECTION 2 – INSTALLATION
LD14762
NOTES:
1. 10’
clearance minimal over the top of the condensing unit.
2. Only one adjacent wall can exceed unit height. 3. 12’
clearance required to adjacent units.
4. 8’
service access recommended on one side.
5. Economizer and exhaust hoods, where applicable are folded inside unit for shipment.
FIGURE 8 -
LOCATION AND DIMENSION DRAWING / 050-061 MODELS, BOTTOM SUPPLY / SIDE RETURN,
EXTENDED CABINET
170.31
AIRFLOW
60.00 CLEAR
FOR AIR
INT
AKE
BOTH SIDES
136.82
106.00
38.37
6.28
4.79
49.94
210.40
1.50
11.25
1-1/4" FPT
DRAIN
LEFT
SIDE ONL
Y
84.00 CLEAR
385.81
ELECTRICAL
SER
VICE
4.22
246.81
277.56
5.74
63.25
2-1/8" OD COPPER
CONNECTION
TYP
120.00 CLEAR
91.00 CLEAR FOR COIL
PULL
30.00 DOOR
SWING CLEARANCE
BOTH SIDES
78.00 CLEAR FOR COIL
PULL
92.00 95.25
82.00
80.51
86.26
TOP
VIEW
REAR VIEW
FRONT
VIEW
SIDE VIEW
Содержание 050
Страница 112: ...JOHNSON CONTROLS 112 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE SENSOR READINGS LD13017 ...
Страница 113: ...JOHNSON CONTROLS 113 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ECONOMIZER EXHAUST LD13018 ...
Страница 114: ...JOHNSON CONTROLS 114 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE FANS LD13019 ...
Страница 115: ...JOHNSON CONTROLS 115 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 COOLING SETUP LD13020 ...
Страница 116: ...JOHNSON CONTROLS 116 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE COOLING STATUS LD13021 ...
Страница 117: ...JOHNSON CONTROLS 117 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 HEATING SETUP LD13022 ...
Страница 118: ...JOHNSON CONTROLS 118 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE HEATING STATUS LD13023 ...
Страница 119: ...JOHNSON CONTROLS 119 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 SYSTEM OPTIONS LD13024 ...
Страница 120: ...JOHNSON CONTROLS 120 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE OUTPUTS STATUS LD13025 ...
Страница 122: ...JOHNSON CONTROLS 122 FORM 100 50 NOM6 ISSUE DATE 8 07 2017 SECTION 6 USER INTERFACE GRAPHIC LD13027 CLOCK LD13028 ...
Страница 125: ...JOHNSON CONTROLS 125 SECTION 6 USER INTERFACE FORM 100 50 NOM6 ISSUE DATE 8 07 2017 6 ALARMS LD13031 ...