SEQUENCE OF OPERATION FOR DPM 
MODELS

COOLING

The following sequences of operation are based on using a 
standard single-stage cooling thermostat.

WITH POWER TO UNIT AND THERMOSTAT IN COOLING 
MODE.

1.

If the fan switch on the thermostat is in the “ON” position, 
the 24 volts at “G” will be sent to the indoor motor and the 
blower will operate at the selected airflow. If the fan switch 
is in the “AUTO” position, the blower will operate at the 
selected airflow only when there is a call for cooling by the 
thermostat.

2.

On a call for cooling, the thermostat will send 24 volts to “Y” 
on the fan control board. The 24 volt signal will energize 
contactor “M1", and power will be supplied to the 
compressor and outdoor fan motor. If the fan switch on the 
thermostat is on the ”AUTO" position, the thermostat will 
also send a 24 volt signal to “G” on the fan control board 
and the indoor blower will operate as indicated in step 1.

3.

When the demand for cooling has been satisfied, the “M1" 
contactor will be de-energized when the 24 volt ”Y" signal 
is removed. If the fan switch on the thermostat is in the 
“ON” position, the indoor blower will continue to run. If the 
fan switch is in the “AUTO” position, the 24 volt “G” signal 

will be removed, and after a 30 second delay, the indoor 
blower motor will shut down.

HEATING

WITH POWER TO UNIT AND THERMOSTAT IN HEATING 
MODE.

1.

If the fan switch on the thermostat is in the “ON” position, 
the 24 volts at “G” will be sent to the indoor motor and the 
blower will operate at the selected airflow. If the fan switch 
is in the “AUTO” position, the blower will operate at the 
selected airflow only when there is a call for heating by the 
thermostat.

2.

On a call for heating, the thermostat will send 24 volts to 
“W1" on the fan control board. The 24 volts signal will 
energize relay ”K2" on the fan control board, and the first 
stage of electric heat will be energized. The indoor blower 
will operate as indicated in step 1.

3.

On units with 2 (two) stages of electric heat, the second 
bank of heaters will be energized by a 24 volt signal to “W2" 
on the fan control board. After a 20 second delay, the third 
bank of heaters will be energized if the unit is so equipped.

4.

When the heating demand is satisfied, the electric heat will 
be de-energized when the 24 volt “W1" and ”W2" signals 
are removed. If the fan switch on the thermostat is in the 
“ON” position, the indoor blower will continue to run. If the 
fan switch is in the “AUTO” position, the indoor motor will 
shut off after the appropriate time delay.

Please refer to Tables 13 and 14 for more information.

Содержание DP M 024 Series

Страница 1: ...alert installer that personal injury and or equipment damage may result if installation procedure is not handled properly CAUTION READ ALL SAFETY GUIDES BEFORE YOU BEGIN TO INSTALL YOUR UNIT SAVE THIS...

Страница 2: ...IAGRAM 6 4 COIL DELTA P VS AIRFLOW 10 5 DIMENSIONS AND CLEARANCES 13 6 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY DPM MODELS 17 7 TYPICAL WIRING DIAGRAM 208 230 3 60 POWER SUPPLY DPM MODELS 18 8...

Страница 3: ...writing REFERENCE Additional information on the design installation operation and service of this equipment is available in the following reference forms 343635 General Installation 035 16605 003 E 06...

Страница 4: ...t to 1 8 maximum RIGGING OR HANDLING Care must be exercised when moving the unit Do not remove any packaging until the unit is near the place of installation Rig unit with slings placed under the unit...

Страница 5: ...ll into an open drain SERVICE ACCESS Access to all serviceable components is provided by the following removable panels Blower service access Electrical filter access Compressor service access Refer t...

Страница 6: ...20 20 20 FACE AREA Sq Ft 12 9 12 9 12 9 12 9 16 4 16 4 CHARGE REFRIGERANT 22 lbs oz 4 10 5 9 5 0 4 12 6 0 10 8 FILTER FACE AREA Sq Ft Qty Size 2 14 1 14 x 22 COMPRESSOR HERMETIC QTY 1 Type Recip Rotar...

Страница 7: ...1 31 4 36 1 44 3 50 2 45 60 460 3 60 5 8 45 9 0 8 2 1 None 10 1 15 2NH04501046 10 1 12 17 6 20 2NH04501546 15 1 18 25 1 30 042 3 5 208 230 1 60 21 1 115 33 1 2 6 0 None 33 6 45 2NH04500506 3 8 5 1 18...

Страница 8: ...96 227 1078 High 5 985 245 952 913 257 1022 813 261 1090 030 Low 1 844 119 686 767 133 782 Low Medium 2 1003 175 762 949 192 844 884 208 925 808 222 1003 Medium 3 1068 204 795 1020 221 871 961 236 945...

Страница 9: ...3 0 05 1200 0 04 0 02 0 03 0 06 1300 0 04 0 03 0 03 0 07 1400 0 04 0 04 0 03 0 08 1500 0 04 0 05 0 04 0 09 1600 0 04 0 06 0 05 0 10 1700 0 05 0 07 0 05 0 11 1800 0 05 0 07 0 06 0 11 1900 0 06 0 08 0 0...

Страница 10: ...ns would be inaccurate To ensure a dry coil the compressors should be deactivated while the test is being run 4 Knowing the pressure drop across a dry coil the actual CFM through the unit can be deter...

Страница 11: ...3 27 7 29 2 30 6 32 1 70 15 0 16 7 18 4 20 1 21 8 23 5 25 3 26 7 28 1 29 6 31 0 75 13 9 15 7 17 4 19 1 20 8 22 5 24 2 25 6 27 1 28 5 30 0 80 12 9 14 6 16 3 18 0 19 7 21 4 23 2 24 6 26 0 27 5 28 9 85...

Страница 12: ...7 23 3 24 0 24 7 25 3 26 0 70 16 9 17 6 18 3 19 1 19 8 20 5 21 3 22 2 23 1 24 0 24 9 75 14 0 14 9 15 8 16 6 17 5 18 4 19 3 20 4 21 5 22 7 23 8 80 11 2 12 2 13 2 14 2 15 2 16 2 17 2 18 6 20 0 21 3 22...

Страница 13: ...L OVERALL 4 1 2 UNIT CONDENSATE CONNECTION NPTI TRAP REQUIRED OVERALL SIDE SUPPLY AIR OPENING SIDE RETURN AIR OPENING COMPRESSOR SERVICE ACCESS COMPARTMENT PANEL HIGH VOLTAGE CONN DIA KNOCKOUT HIGH VO...

Страница 14: ...switch is in the AUTO position the 24 volt G signal will be removed and after a 30 second delay the indoor blower motor will shut down HEATING WITH POWER TO UNIT AND THERMOSTAT IN HEATING MODE 1 If th...

Страница 15: ...1 HTR 1 1 SECOND DELAY ON FAN 10 SECOND DELAY OFF OFF HEATER BANK 3 HTR 4 HTR 5 INSTANT OFF HEATER BANK 2 HTR 2 HTR 3 SEC DELAY ON HEATER BANK 1 HTR 1 1 SECOND DELAY ON FAN 10 SECOND DELAY OFF TABLE...

Страница 16: ...is used to clean the coil be sure that the power to the unit is shut off prior to cleaning TROUBLESHOOTING Prior to any of the following maintenance procedures shut off all power to the unit to avoid...

Страница 17: ...343635 BIM B 0408 Johnson Controls Unitary Products 17 FIGURE 6 TYPICAL WIRING DIAGRAM 208 230 1 60 POWER SUPPLY DPM MODELS...

Страница 18: ...343635 BIM B 0408 18 Johnson Controls Unitary Products FIGURE 7 TYPICAL WIRING DIAGRAM 208 230 3 60 POWER SUPPLY DPM MODELS...

Страница 19: ...343635 BIM B 0408 Johnson Controls Unitary Products 19 FIGURE 8 TYPICAL WIRING DIAGRAM 460 3 60 POWER SUPPLY DPM MODELS...

Страница 20: ...change without notice Printed in U S A 343635 BIM B 0408 Copyright 2008 by Johnson Controls Inc All rights reserved Supersedes 343635 BIM A 1007 Johnson Controls Unitary Products 5005 York Drive Norma...

Отзывы: