WARNING: THIS APPLIANCE MUST BE EARTHED

This appliance is for use with natural gas only.

1.

GENERAL DESCRIPTION

1.1

JANUS 6/30 is an open flued gas fired circulator designed for floor or wall mounting, which can generate up to
64.8 litres per hour (14.3 gal/h) of hot water. It is suitable for use in a gravity fed circuit serving a hot water storage
cylinder (tank) and may be used efficiently with indirect storage systems or, in soft water areas, direct systems. Indirect
systems are preferred; direct systems should be used only when recommended by the local water company.

1.2

The gas supply to the main burner is controlled by a multi-functional gas control valve. The main burner operates in
conjunction with a permanent pilot  burner and a thermoelectric sensing device. Pilot ignition is by means of a Piezo unit.

1.3

JANUS 6/30 pilot burner contains an Atmospheric Sensing Device which is able to detect a reduction in the oxygen
content of the combustion air to the appliance under adverse conditions, and will cause the pilot burner to be
extinguished. The appliance must then be re-ignited in accordance with the Ignition Instructions.

2.

TECHNICAL DATA

2.1

NATURAL GAS:

Injector:

             Amal type 187/001/004. Diameter 1.7mm.

Setting pressure:

14.0 mbar (5.6 in wg).

Gas rate:

0.42m

3

/h (14.85ft

3

/h).

Input:

4.4kW (15,000Btu/h).

Output:

3.32kW   (11,340Btu/h).

Gas connection:          Rc

1

/

4

 (

1

/

4

in BSP).

Gas service cock:       Rc

1

/

4

 (

1

/

4

in BSP) union gas cock (supplied loose).

Table 1.

HIJAN Janus 6/30 Gas configuration

2

.

2

WATER:

Maximum output:

Up to 64.8 litres/h (14.3 gal/h) with 44.5

o

C (80

o

F) rise.

Maximum water temperature: Normal factory setting

60

o

C (140

o

F) see Section 10.2.2.

User temperature control allows settings below maximum.
Maximum working head: 20m (65ft).
Minimum circulation head: 610mm (24in) with indirect cylinder, 356mm (14in) with direct cylinder.

2.3

FLUE:

75mm (3in) as standard, with adapter plate to convert to 100mm (4in) flue.

2.4

OVERALL DIMENSIONS:

Height:

496mm (19.5in).

Width:

123mm (4.9in).

Length:

416mm (16.9in) including controls cover.
353mm (13.9in) excluding controls cover.

1

JANUS 6/30

CIRCULATOR WATER HEATER

INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS

G.C. No 53 416 27

Publication No.ZZ 1057/3

June 2009

Johnson and Starley prides itself on its ability to supply spare parts quickly and efficiently. If your service engi-
neer indicates a problem in obtaining a spare par t, advise him to contact Johnson and Starley Spares Department at
the address below.

Telephone:

01604 762881

JOHNSON AND STARLEY Ltd.,

Rhosili Road,

Brackmills,

Fax :

01604 767408

Northampton NN4 7LZ

Содержание JANUS 6/30

Страница 1: ...AS Injector Amal type 187 001 004 Diameter 1 7mm Setting pressure 14 0 mbar 5 6 in wg Gas rate 0 42m3 h 14 85ft3 h Input 4 4kW 15 000Btu h Output 3 32kW 11 340Btu h Gas connection Rc1 4 1 4 in BSP Gas service cock Rc1 4 1 4 in BSP union gas cock supplied loose Table 1 HIJAN Janus 6 30 Gas configuration 2 2 WATER Maximum output Up to 64 8 litres h 14 3 gal h with 44 5o C 80o F rise Maximum water te...

Страница 2: ...relevant recommendations of the following British Standard Codes of Practice BS 6798 Specification for installation of gas fired hot water boilers of rated input not exceeding 60kW BS5546 Installation of gas hot water supplies for domestic purposes 2nd family gasses BS5440 Pt 1 Flues BS5440 Pt 2 Air supply BS6891 Installation of low pressure gas pipe work up to 28mm R1 in domestic premises BS6700 ...

Страница 3: ...match to the opening and observing whether all the smoke is pulled up the flue In certain conditions there may be spillage of smoke due to inversion caused by the flue being colder than the outside air If such occurrences arise heat is to introduced into the flue i e by blowlamp and the spillage test repeated If either downdraught or no definite upflow is indicated this must be investigated and co...

Страница 4: ...as possible to the injector shoulder NOTE If burner is not vertically aligned the burner and control assembly will not fit into the water body for re assembly 7 5 DRAUGHTDIVERTER 7 5 1 Release flue split collar 7 5 2 Release 4 x screws securing upper front plate to top cover and withdraw upper front plate 7 5 3 Release screw securing draught diverter to appliance and withdraw draught diverter and ...

Страница 5: ...fficient operation of the appliance 6 4 Hand User s Instructions to the customer for retention 7 MAINTENANCE IMPORTANT Before commencing any maintenance or component replacement ENSURE that the Gas supply is turned OFF On completion of maintenance ENSURE the appliance is tested for GAS SOUNDNESS 7 1 ROUTINESERVICING 7 1 1 Remove and inspect the Burner and Control Assembly cleaning the main burner ...

Страница 6: ... 2 Insert thermostat phial fully into flow pocket and secure using thermostat retaining plug 4 7 GAS CONNECTIONS 4 7 1 Connect a suitable gas supply to the appliance via the union service cock supplied Ensure that the pipe work does not cause obstruction for Burner and Control assembly removal 4 7 2 Test the gas installation for gas soundness and purge in accordance with BS6891 4 8 FINALASSEMBLY 4...

Страница 7: ... 2 Insert thermostat phial fully into flow pocket and secure using thermostat retaining plug 4 7 GAS CONNECTIONS 4 7 1 Connect a suitable gas supply to the appliance via the union service cock supplied Ensure that the pipe work does not cause obstruction for Burner and Control assembly removal 4 7 2 Test the gas installation for gas soundness and purge in accordance with BS6891 4 8 FINALASSEMBLY 4...

Страница 8: ...fficient operation of the appliance 6 4 Hand User s Instructions to the customer for retention 7 MAINTENANCE IMPORTANT Before commencing any maintenance or component replacement ENSURE that the Gas supply is turned OFF On completion of maintenance ENSURE the appliance is tested for GAS SOUNDNESS 7 1 ROUTINESERVICING 7 1 1 Remove and inspect the Burner and Control Assembly cleaning the main burner ...

Страница 9: ...as possible to the injector shoulder NOTE If burner is not vertically aligned the burner and control assembly will not fit into the water body for re assembly 7 5 DRAUGHTDIVERTER 7 5 1 Release flue split collar 7 5 2 Release 4 x screws securing upper front plate to top cover and withdraw upper front plate 7 5 3 Release screw securing draught diverter to appliance and withdraw draught diverter and ...

Страница 10: ...match to the opening and observing whether all the smoke is pulled up the flue In certain conditions there may be spillage of smoke due to inversion caused by the flue being colder than the outside air If such occurrences arise heat is to introduced into the flue i e by blowlamp and the spillage test repeated If either downdraught or no definite upflow is indicated this must be investigated and co...

Страница 11: ...relevant recommendations of the following British Standard Codes of Practice BS 6798 Specification for installation of gas fired hot water boilers of rated input not exceeding 60kW BS5546 Installation of gas hot water supplies for domestic purposes 2nd family gasses BS5440 Pt 1 Flues BS5440 Pt 2 Air supply BS6891 Installation of low pressure gas pipe work up to 28mm R1 in domestic premises BS6700 ...

Страница 12: ...AS Injector Amal type 187 001 004 Diameter 1 7mm Setting pressure 14 0 mbar 5 6 in wg Gas rate 0 42m3 h 14 85ft3 h Input 4 4kW 15 000Btu h Output 3 32kW 11 340Btu h Gas connection Rc1 4 1 4 in BSP Gas service cock Rc1 4 1 4 in BSP union gas cock supplied loose Table 1 HIJAN Janus 6 30 Gas configuration 2 2 WATER Maximum output Up to 64 8 litres h 14 3 gal h with 44 5o C 80o F rise Maximum water te...

Отзывы: