JC-24x - Version Update from 3.25 to 3.26
Fixed Software Bugs
Reading and Writing Analog I/Os at the BWU1821
The BWU1821 is a gateway between AS interface and CANopen of the
Bihl+Wiedemann GmbH. It can be directly connected to the Jetter CAN
system bus.
BWU1821
Reading and writing of AS interface slaves by means of analog inputs and
outputs renders wrong results.
Effects of this Bug
The following revisions are affected by this bug:
Affected Revisions
OS revision
JX6-SB(-I)
JC-24x
JM-D203-JC24x
< 2.21.0.00
< 3.26.0.00
< 1.13.0.00
Hardware revision
not relevant
Configuration or operating mode
not relevant
Comment 600
Carry out the following step for a workaround:
Remedy / Workaround
Step
Action
1
Configuring a NODE ID of the BWU1821 on 70
Starting from the following revisions this bug has been fixed:
Bug Fix
OS revision
JX6-SB(-I)
JC-24x
JM-D203-JC24x
2.21.0.00
3.26.0.00
1.13.0.00
Hardware revision
not relevant
Configuration or operating mode
not relevant
Jetter AG
15