9
Figure 6-2: wrench storage
7.0
Electrical connections
The JWP-13BT is wired for 115-volt power. The
planer comes with a plug designed for use on a
circuit with a
grounded outlet
that looks like the one
pictured in
A
, Figure 7-1.
Keep in mind that a circuit being used by other
machines, tools, lights, heaters, etc. at the same
time will add to the electrical load. A dedicated
circuit to the machine will offer best results.
Before connecting to power source, be sure switch
is in
off
position.
It is recommended that the planer be connected to
a dedicated 20 amp circuit with circuit breaker or
fuse. If connected to a circuit protected by fuse, use
time delay fuse marked “D”.
Local codes take
precedence over recommendations.
7.1
GROUNDING INSTRUCTIONS
1. All Grounded, Cord-connected Tools:
In the event of a malfunction or breakdown,
grounding provides a path of least resistance for
electric current to reduce the risk of electric shock.
This tool is equipped with an electric cord having an
equipment-grounding conductor and a grounding
plug. The plug must be plugged into a matching
outlet that is properly installed and grounded in
accordance with all local codes and ordinances.
Do not modify the plug provided - if it will not fit the
outlet, have the proper outlet installed by a qualified
electrician.
Improper connection of the equipment-grounding
conductor can result in a risk of electric shock. The
conductor with insulation having an outer surface
that is green with or without yellow stripes is the
equipment-grounding conductor. If repair or
replacement of the electric cord or plug is
necessary, do not connect the equipment-grounding
conductor to a live terminal.
Check with a qualified
electrician or service pe
r
sonnel if the grounding
instructions are not completely understood, or if
in doubt as to whether the tool is properly
grounded. Failure to comply may cause serious
or fatal injury.
Use only 3-wire extension cords that have 3-prong
grounding plugs and 3-pole receptacles that accept
the tool's plug.
Repair or replace damaged or worn cord
immediately.
2. Grounded, cord-connected tools intended for use
on a supply circuit having a nominal rating
less than
150
volts:
This tool is intended for use on a circuit that has an
outlet that looks like the one illustrated in
A,
Figure
7-1. An adapter, shown in
B
, may be used to
connect this plug to a 2-pole receptacle as shown in
B
if a properly grounded outlet is not available. The
temporary adapter should be used only until a
properly grounded outlet can be installed by a
qualified electrician. The green-colored rigid ear,
lug, and the like, extending from the adapter must
be connected to a permanent ground such as a
properly grounded outlet box.
In Canada, the use of a temporary adaptor is not
permitted by the Canadian Electrical Code, C22.1.
Figure 7-1
7.2
Extension cords
The use of extension cords is discouraged; try to
position equipment within reach of the power
source. If an extension cord becomes necessary, be
sure it is heavy enough to carry the current your
product will draw. An undersized cord will cause a
drop in line voltage resulting in loss of power and
overheating.
Table 2 shows recommended size to use depending
on cord length and nameplate ampere rating. If in
doubt, use the next heavier gauge. The smaller the
gauge number, the heavier the cord.
Ampere
Rating
Volts
Total length of cord
in feet
More
Than
Not
More
Than
120
25
50
100
150
AWG
0
6
18
16
16
14
6
10
18
16
14
12
10
12
16
16
14
12
12
16
14
12
Not
Recommended
Table 2: Extension Cord Recommendations
Содержание JWP-13BT
Страница 20: ...20 12 1 1 Base Assembly Exploded View ...
Страница 22: ...22 12 2 1 Head Assembly Exploded View ...