Control - Heat pump EB101
S-series – VVM S / SMO S
These settings are made on the display on the indoor
module/control module.
Menu 7.3.2 - Installed heat pump
Here, you make specific settings for the installed heat
pump.
Silent mode permitted
Setting range: on/off
Max. frequency 1
Setting range: 25 – 120 Hz
Max. frequency 2
Setting range: 25 – 120 Hz
Compressor phase
Setting range JÄSPI Inverter Nordic 1 x 230 V: L1, L2,
L3
Detect compressor phase
Setting range JÄSPI Inverter Nordic 1 x 230 V: off/on
Current limit
Setting range JÄSPI Inverter Nordic 1 x 230 V: off/on
Max. current
Setting range JÄSPI Inverter Nordic 1 x 230 V: 6 – 32
A
blockFreq 1
Setting range: on/off
From frequency
Setting range: 25 – 117 Hz
To frequency
Setting range: 28 – 120 Hz
blockFreq 2
Setting range: on/off
From frequency
Setting range: 25 – 117 Hz
To frequency
Setting range: 28 – 120 Hz
Defrosting
Start manual defrosting
Setting range: on/off
Start temperature for defrost function
Setting range: -3 – 3 °C
Cut-out value activation passive defrosting
Setting range: 2 – 10 °C
Defrost more often
Alternatives: Yes / No
Silent mode permitted
: Here, you set whether silent mode
is to be activated for the heat pump. Please note that
you now have the option to schedule when silent mode
will be active.
The function should only be used for limited periods,
because JÄSPI Inverter Nordic possibly may not reach its
dimensioned output.
Detect compressor phase
: This shows in which the phase
the heat pump has detected whether you have
JÄSPI Inverter Nordic 230V~50Hz. Phase detection nor-
mally occurs automatically in connection with start-up
of the indoor module/control module. This setting can
be changed manually.
Current limitation
: Here, you set whether the current
limitation function will be activated for the heat pump,
if you have JÄSPI Inverter Nordic 230V~50Hz. During
active function, you can limit the value of the maximum
current.
BlockFreq 1
: Here, you can select a frequency range
within which the heat pump is not permitted to work.
This function can be used if certain compressor speeds
cause noise disturbance in the house.
BlockFreq 2
: Here, you can select a frequency range
within which the heat pump is not permitted to work.
Defrosting
: Here, you can change the settings that affect
the defrost function.
Start manual defrosting
: Here, you can start "active de-
frosting” manually, if the function needs to be tested for
servicing or if necessary. This can also be used to acceler-
ate the start of "fan de-icing".
Start temperature for defrost function
: Here, you set the
temperature (BT16) at which the defrost function will
start. The value must only be changed in consultation
with the installer.
Cut-out value activation passive defrosting
: Here, you set
the temperature (BT28) at which "passive defrosting"
will be activated. During passive defrosting, the ice is
melted by the energy from the ambient air. The fan is
active during passive defrosting. The value must only be
changed in consultation with the installer.
Defrost more often
: Here, you activate whether defrosting
will occur more frequently than normal. This selection
can be made if the heat pump receives an alarm due to
build-up of ice during operation caused, for example, by
snow.
JÄSPI Inverter Nordic