The User Manual of JAC200 Series General Frequency Converter
- 56 -
Function
code
Name
Set range
Default
value
Chan
ge
A2-65
The oscillation
suppression gain of
second motor
0
~
100
Model
dependent
☆
Group A5 Parameters of control optimization
A5-00
Upper limiting
frequency of DPWM
switching
5.00Hz
~
Maximum frequency
8.00Hz
☆
A5-01
PWM modulation
mode
0: Asynchronous modulation
1: Synchronizing modulation
0
☆
A5-02
The selection of
compensation mode
in dead zone
0: No compensation
1: Compensation mode 1
1
☆
A5-03
The depth of the
random PWM
0: Random PWM is invalid
1
~
10: The random depth of PWM carrier
frequency
0
☆
A5-04
Rapid current
limiting enabled
0: Not enabled
1: Enabled
1
☆
A5-05
Compensation of
current detection
0
~
100
5
☆
A5-06
Setting for
under-voltage points
60.0%
~
140.0%
100.0%
☆
A5-07
The selection of SVC
optimization mode
1: Optimization mode 1
2: Optimization mode 2
2
☆
A5-09
Setting of
over-voltage points
200.0V
~
2200.0V
Model
dependent
★
5.2 Monitoring parameter list
Table 5-2 The monitoring parameter list
Function
code
Name
The minimum
unit
Address
Group U0 Basic Monitoring Parameters
U0-00
Operation frequency (Hz)
0.01Hz
7000H
U0-01
Set frequency (Hz)
0.01Hz
7001H
U0-02
Bus voltage (V)
0.1V
7002H
U0-03
Output voltage (V)
1V
7003H
U0-04
Output current (A)
0.01A
7004H